Busbar MCQs — Set 10

10 practice questions on busbar sizing, standards and applications — neutral and earth bars, bus ducts and IEC 61439.

Q1. A single-phase load draws 5 kW at 230 V with a power factor of 0.9. What current must its busbar carry?

  • (a) 21.7 A
  • (b) 24.2 A
  • (c) 19.6 A
  • (d) 27.8 A

Answer: (b) 24.2 A — single-phase I = P ÷ (V × pf) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.

Q2. Which standard covers low-voltage switchgear and controlgear assemblies, including their busbar systems?

  • (a) IEC 61439
  • (b) IEC 60076
  • (c) ISO 9001
  • (d) IEC 60364-1 only

Answer: (a) IEC 61439 — this is the standard for LV switchgear assemblies, covering temperature rise, short-circuit withstand and construction of busbar systems inside them.

Q3. A transformer supplies 80 kW at a power factor of 0.8. What kVA must the busbar system fed by it be able to handle?

  • (a) 64 kVA
  • (b) 80 kVA
  • (c) 100 kVA
  • (d) 120 kVA

Answer: (c) 100 kVA — kVA = kW ÷ pf = 80 ÷ 0.8 = 100 kVA, so the incoming busbar must carry the full 100 kVA load current.

Q4. What is the purpose of the neutral busbar in a three-phase four-wire panel?

  • (a) To carry the unbalanced current and provide the return path for single-phase loads
  • (b) To increase the voltage
  • (c) To protect against lightning only
  • (d) To carry the full three-phase load current at all times

Answer: (a) To carry the unbalanced current and provide the return path for single-phase loads — the neutral collects the out-of-balance current and the return current of 230 V loads fed from the phases.

Q5. Why is the neutral busbar sometimes made the same size as the phase busbars in modern installations?

  • (a) Because neutral current can approach or exceed phase current when loads produce triplen harmonics
  • (b) Because the neutral always carries twice the phase current
  • (c) Because it looks neater
  • (d) Because the neutral carries no current at all

Answer: (a) Because neutral current can approach or exceed phase current when loads produce triplen harmonics — computers, LED drivers and other non-linear loads send harmonic currents that add up in the neutral, so a half-size neutral can overload.

Q6. What is the purpose of the earth busbar inside a switchboard?

  • (a) To carry load current
  • (b) To bond all metalwork together and give fault current a low-resistance path to earth
  • (c) To support the phase busbars
  • (d) To measure the earth voltage

Answer: (b) To bond all metalwork together and give fault current a low-resistance path to earth — the earth bar connects frames, doors and enclosures so a fault trips the protection instead of leaving metal live.

Q7. A single-phase load draws 10 kW at 230 V with a power factor of 0.85. What current must its busbar carry?

  • (a) 43.5 A
  • (b) 51.2 A
  • (c) 40 A
  • (d) 60.9 A

Answer: (b) 51.2 A — single-phase I = P ÷ (V × pf) = 10,000 ÷ (230 × 0.85) = 10,000 ÷ 195.5 = 51.2 A.

Q8. Where is a busbar trunking system (bus duct) commonly used instead of cables?

  • (a) As rising mains carrying power up through the floors of a tall building
  • (b) Inside a small domestic consumer unit
  • (c) As an overhead transmission line
  • (d) Inside a battery charger

Answer: (a) As rising mains carrying power up through the floors of a tall building — bus ducts carry large currents vertically with tap-off points on each floor, where many parallel cables would be bulky and hard to manage.

Q9. In an outdoor high-voltage substation, what form do the main busbars often take?

  • (a) Flat copper bars in a closed panel
  • (b) Stranded ACSR conductors or aluminium tubes strung between gantries on insulator strings
  • (c) Ordinary PVC cables
  • (d) Steel rails

Answer: (b) Stranded ACSR conductors or aluminium tubes strung between gantries on insulator strings — outdoor substation buses span long distances in open air, so flexible stranded conductors or rigid tubes on tall insulators are used.

Q10. When sizing a busbar, which two ratings must BOTH be checked?

  • (a) Only the continuous load current
  • (b) The continuous current rating and the short-circuit withstand rating
  • (c) Only the voltage rating
  • (d) Only the colour of the bar

Answer: (b) The continuous current rating and the short-circuit withstand rating — a bar that carries the normal load may still bend or melt in a fault, so both the steady current and the fault level decide the size.