Busbar MCQs — Set 8
10 practice questions on busbar joints and connections — bolting, plating, torque and contact resistance.
Q1. What is the most common way of joining two busbars together?
- (a) Soldering only
- (b) Bolted lap joint with overlapping bars
- (c) Welding the bars into one piece
- (d) Gluing with epoxy
Answer: (b) Bolted lap joint with overlapping bars — the bars overlap and are clamped with high-tensile bolts, giving a joint that can be opened for maintenance.
Q2. Why are busbar joint surfaces often silver-plated?
- (a) For decoration
- (b) Silver resists oxidation and keeps contact resistance low
- (c) Silver plating increases the bar’s weight
- (d) Silver stops the bar from expanding
Answer: (b) Silver resists oxidation and keeps contact resistance low — a clean silvered surface does not form an insulating oxide, so the joint stays low-resistance for years.
Q3. What happens if a busbar joint bolt is left loose (under-torqued)?
- (a) Nothing — loose joints work fine
- (b) Contact resistance rises, the joint overheats and can burn or fail
- (c) The current rating of the bar increases
- (d) The joint becomes waterproof
Answer: (b) Contact resistance rises, the joint overheats and can burn or fail — a loose joint has poor metal-to-metal contact, so I²R heating at the joint climbs until it damages the bar.
Q4. What happens if a busbar joint bolt is over-tightened?
- (a) The joint becomes perfect
- (b) The bar or bolt can deform or crack, and the contact pressure can actually fall over time
- (c) The current rating doubles
- (d) Over-tightening has no effect at all
Answer: (b) The bar or bolt can deform or crack, and the contact pressure can actually fall over time — crushed metal relaxes, so over-torque is as bad as under-torque; joints must be tightened to the specified torque.
Q5. Why are spring (Belleville) washers used on busbar joint bolts?
- (a) To make the bolt look bigger
- (b) To keep steady contact pressure as the joint expands and contracts with temperature
- (c) To insulate the bolt from the bar
- (d) To increase the voltage rating
Answer: (b) To keep steady contact pressure as the joint expands and contracts with temperature — the spring washer takes up thermal movement so the clamping force stays constant through heating cycles.
Q6. How is the resistance of a busbar joint checked during maintenance?
- (a) With a micro-ohmmeter (ductor), which measures the very low joint resistance in micro-ohms
- (b) With a megger only
- (c) By weighing the joint
- (d) By listening to the joint
Answer: (a) With a micro-ohmmeter (ductor), which measures the very low joint resistance in micro-ohms — an ordinary multimeter cannot resolve such small resistances, so a low-resistance ohmmeter is used and results are compared with the maker’s values.
Q7. A three-phase load draws 25 kW at 400 V with a power factor of 0.8. What current flows through the busbar joint?
- (a) 45.1 A
- (b) 31.3 A
- (c) 62.5 A
- (d) 90.2 A
Answer: (a) 45.1 A — I = P ÷ (√3 × V × pf) = 25,000 ÷ (1.732 × 400 × 0.8) = 25,000 ÷ 554 = 45.1 A.
Q8. What fitting is used when a copper busbar must be joined to an aluminium busbar?
- (a) An ordinary steel bolt
- (b) A bimetallic (copper–aluminium) connector or washer
- (c) A plastic clamp
- (d) Direct bolting with extra grease only
Answer: (b) A bimetallic (copper–aluminium) connector or washer — the bimetallic piece separates the two metals and prevents galvanic corrosion at the joint.
Q9. Where are flexible braided copper connections used instead of solid busbar?
- (a) Wherever the connection must move or absorb vibration, such as between a busbar and a transformer or breaker
- (b) Only in outdoor substations
- (c) Where no current flows
- (d) Flexible connections are never used with busbars
Answer: (a) Wherever the connection must move or absorb vibration, such as between a busbar and a transformer or breaker — a flexible braid takes up movement and vibration that would stress a rigid bar and crack its joints.
Q10. Before a busbar joint is bolted up, what must be done to the contact surfaces?
- (a) Nothing — dirty surfaces work best
- (b) Clean them to bright metal, remove oxide and burrs, and apply contact grease if specified
- (c) Paint them thickly
- (d) Heat them until red hot
Answer: (b) Clean them to bright metal, remove oxide and burrs, and apply contact grease if specified — a clean, flat contact is what keeps joint resistance low; dirt, oxide or burrs create hot spots.
Also read: Wiring Systems MCQs | All MCQ Topics