Busbar MCQs — Set 3

10 practice questions on busbar shapes — flat, round and tubular — and why each shape is used.

Q1. Why are flat rectangular busbars the standard choice inside low-voltage switchboards?

  • (a) They are the only shape that conducts electricity
  • (b) They are easy to bolt, tap and joint, and expose a large surface for cooling
  • (c) They are always cheaper than any other shape
  • (d) They cannot carry short-circuit current

Answer: (b) They are easy to bolt, tap and joint, and expose a large surface for cooling — flat bars give a wide flat face for bolted connections and a large area to shed heat.

Q2. What is the cross-sectional area of a 25 mm × 6 mm flat copper busbar?

  • (a) 31 mm²
  • (b) 150 mm²
  • (c) 250 mm²
  • (d) 19 mm²

Answer: (b) 150 mm² — area = width × thickness = 25 × 6 = 150 mm², the figure used with current density to estimate the bar’s rating.

Q3. What is skin effect in an AC busbar?

  • (a) Current flows evenly through the whole bar
  • (b) Alternating current concentrates near the surface of the conductor, leaving the centre underused
  • (c) The bar’s surface becomes an insulator
  • (d) The bar loses all its current to the air

Answer: (b) Alternating current concentrates near the surface of the conductor, leaving the centre underused — at power frequency the centre of a thick solid bar carries little current, which is why large bars are often hollow or split.

Q4. Why are tubular (hollow) busbars used in high-voltage substations?

  • (a) They waste material in the centre where skin effect leaves current low, and their smooth round surface reduces corona
  • (b) They are easier to paint
  • (c) They carry only direct current
  • (d) They are the cheapest shape available

Answer: (a) They waste material in the centre where skin effect leaves current low, and their smooth round surface reduces corona — a hollow tube uses metal only where the current flows and its large radius keeps the surface electric field low.

Q5. A flat busbar is normally mounted on edge (narrow side vertical) rather than flat. Why?

  • (a) Mounting on edge improves cooling and gives a higher current rating for the same bar
  • (b) Mounting on edge is only done for appearance
  • (c) A bar mounted flat carries more current
  • (d) The mounting position makes no difference at all

Answer: (a) Mounting on edge improves cooling and gives a higher current rating for the same bar — the vertical faces set up a stronger natural air flow, so an edge-mounted bar runs cooler than the same bar laid flat.

Q6. A 150 mm² copper busbar is rated at a typical current density of 1.5 A/mm². Roughly what current can it carry?

  • (a) 100 A
  • (b) 225 A
  • (c) 150 A
  • (d) 450 A

Answer: (b) 225 A — current = area × current density = 150 × 1.5 = 225 A, a typical rating estimate for an enclosed copper bar.

Q7. Why are two or more flat bars used in parallel for each phase instead of one very thick bar?

  • (a) Parallel bars cool better, suffer less skin effect and are easier to bend and joint
  • (b) Parallel bars always cost less than one bar
  • (c) A single thick bar cannot be manufactured
  • (d) Parallel bars remove the need for insulators

Answer: (a) Parallel bars cool better, suffer less skin effect and are easier to bend and joint — several thinner bars expose more surface to air and share the current, giving a higher rating than one thick bar of the same total area.

Q8. What is corona, and why does busbar shape matter for it?

  • (a) Corona is a glow and power loss in the air around a high-voltage conductor, worst at sharp edges
  • (b) Corona is the paint colour on the busbar
  • (c) Corona only happens in low-voltage panels
  • (d) Corona is the sound of a loose joint

Answer: (a) Corona is a glow and power loss in the air around a high-voltage conductor, worst at sharp edges — sharp edges concentrate the electric field, so HV busbars use smooth round or tubular shapes to keep corona low.

Q9. A three-phase load draws 30 kW at 400 V with a power factor of 0.9. What current must the busbar carry?

  • (a) 48.1 A
  • (b) 33.3 A
  • (c) 75 A
  • (d) 54.1 A

Answer: (a) 48.1 A — I = P ÷ (√3 × V × pf) = 30,000 ÷ (1.732 × 400 × 0.9) = 30,000 ÷ 624 = 48.1 A.

Q10. Where are round solid busbars most likely to be found?

  • (a) In small-current switchgear and control panels where short straight runs are needed
  • (b) Only in outdoor 400 kV substations
  • (c) As the main bus of a large power station
  • (d) Inside transformer oil tanks

Answer: (a) In small-current switchgear and control panels where short straight runs are needed — round bars suit small currents and simple runs, while flat bars dominate main distribution and tubes dominate high voltage.

Also read: Cable Sizing MCQs | All MCQ Topics