Busbar MCQs — Set 2

10 practice questions comparing copper and aluminium busbars — conductivity, weight, joints, corrosion and cost.

Q1. How does the conductivity of aluminium compare with that of copper?

  • (a) Aluminium conducts about 61% as well as copper
  • (b) Aluminium conducts better than copper
  • (c) Both conduct exactly the same
  • (d) Aluminium conducts only 10% as well as copper

Answer: (a) Aluminium conducts about 61% as well as copper — aluminium has about 61% IACS conductivity, so for the same current it needs a larger cross-section than copper.

Q2. For the same current rating, roughly how much larger must an aluminium busbar be than a copper one?

  • (a) About the same size
  • (b) About 1.6 times the cross-section
  • (c) About 3 times the cross-section
  • (d) About half the cross-section

Answer: (b) About 1.6 times the cross-section — aluminium resistivity (2.82 × 10⁻⁸ Ω·m) is about 1.68 times copper resistivity (1.68 × 10⁻⁸ Ω·m), so an aluminium bar needs roughly 1.6 times the area for equal resistance.

Q3. What is the biggest weight advantage of an aluminium busbar over a copper one?

  • (a) Aluminium weighs about one-third as much as copper for the same volume
  • (b) Aluminium weighs the same as copper
  • (c) Aluminium is heavier but stronger
  • (d) Aluminium weighs twice as much as copper

Answer: (a) Aluminium weighs about one-third as much as copper for the same volume — aluminium density is about 2.7 g/cm³ against copper at about 8.96 g/cm³, so aluminium busbars are much lighter to handle and support.

Q4. What problem does the thin oxide layer on aluminium create at busbar joints?

  • (a) It makes the joint stronger
  • (b) It is an insulating layer that raises joint resistance unless cleaned off
  • (c) It improves the conductivity of the joint
  • (d) It prevents the joint from ever overheating

Answer: (b) It is an insulating layer that raises joint resistance unless cleaned off — aluminium forms aluminium oxide instantly in air, so joint surfaces must be cleaned and protected, otherwise the joint runs hot.

Q5. A load is 50 kW at a power factor of 0.8. What is its apparent power in kVA?

  • (a) 40 kVA
  • (b) 50 kVA
  • (c) 62.5 kVA
  • (d) 80 kVA

Answer: (c) 62.5 kVA — kVA = kW ÷ pf = 50 ÷ 0.8 = 62.5 kVA, the value used to size the transformer and busbar feeding the load.

Q6. Why must copper and aluminium busbars never be bolted directly together?

  • (a) The joint would be too strong
  • (b) Galvanic corrosion forms at the copper–aluminium contact and the joint loosens and overheats
  • (c) Copper melts the aluminium instantly
  • (d) The two metals repel each other magnetically

Answer: (b) Galvanic corrosion forms at the copper–aluminium contact and the joint loosens and overheats — dissimilar metals in contact corrode, so a bimetallic lug or washer is used between copper and aluminium.

Q7. Which metal melts at the higher temperature — copper or aluminium?

  • (a) Copper, at about 1,085 °C against aluminium at about 660 °C
  • (b) Aluminium, at about 1,085 °C against copper at about 660 °C
  • (c) Both melt at the same temperature
  • (d) Neither metal ever melts in a fault

Answer: (a) Copper, at about 1,085 °C against aluminium at about 660 °C — copper’s higher melting point is one reason it withstands severe short-circuit heating better.

Q8. On cost per ampere carried, which busbar material is usually cheaper?

  • (a) Aluminium, because the metal is cheaper even though a bigger bar is needed
  • (b) Copper, because it is cheaper per kilogram
  • (c) Both always cost exactly the same
  • (d) Iron, which is cheapest of all

Answer: (a) Aluminium, because the metal is cheaper even though a bigger bar is needed — aluminium’s low price per kilogram usually outweighs the larger cross-section it needs.

Q9. Why is copper still preferred for busbars in most high-current switchgear despite its higher cost?

  • (a) Copper needs less space, makes compact joints and has high mechanical strength
  • (b) Copper is lighter than aluminium
  • (c) Copper never needs any joint maintenance
  • (d) Copper is the only metal that conducts electricity

Answer: (a) Copper needs less space, makes compact joints and has high mechanical strength — its high conductivity gives a smaller bar for the same current, and its joints stay reliable under thermal cycling.

Q10. Which property of aluminium makes its busbars need extra care against loosening at joints?

  • (a) Aluminium creeps and expands more with temperature, so bolted joints can relax over time
  • (b) Aluminium shrinks permanently after first use
  • (c) Aluminium joints never loosen
  • (d) Aluminium becomes magnetic when hot

Answer: (a) Aluminium creeps and expands more with temperature, so bolted joints can relax over time — aluminium’s higher thermal expansion and creep mean joints need correct torque and periodic re-checking.

Also read: Batten Wiring System Explained | All MCQ Topics