AC Electrical MCQs — Set 2

10 practice questions on EER, star ratings and AC input power — work each one out before checking the answer.

Q1. EER (Energy Efficiency Ratio) is calculated as:

  • (a) Input watts ÷ cooling BTU/hr
  • (b) Cooling BTU/hr ÷ input watts
  • (c) Input watts × cooling BTU/hr
  • (d) Voltage ÷ current

Answer: (b) Cooling BTU/hr ÷ input watts — EER tells how much cooling you get per watt of electricity.

Q2. A 1.5-ton AC (18,000 BTU/hr) has an EER of 10. What is its input power?

  • (a) 1,200 W
  • (b) 1,500 W
  • (c) 1,800 W
  • (d) 2,400 W

Answer: (c) 1,800 W — input power = 18,000 ÷ 10 = 1,800 W.

Q3. The same 1.5-ton AC (18,000 BTU/hr) with an EER of 12 draws:

  • (a) 1,200 W
  • (b) 1,500 W
  • (c) 1,800 W
  • (d) 2,000 W

Answer: (b) 1,500 W — input power = 18,000 ÷ 12 = 1,500 W.

Q4. A 1-ton AC (12,000 BTU/hr) with an EER of 10 draws:

  • (a) 1,000 W
  • (b) 1,200 W
  • (c) 1,500 W
  • (d) 1,800 W

Answer: (b) 1,200 W — input power = 12,000 ÷ 10 = 1,200 W.

Q5. A 2-ton AC (24,000 BTU/hr) with an EER of 12 draws:

  • (a) 1,500 W
  • (b) 1,800 W
  • (c) 2,000 W
  • (d) 2,400 W

Answer: (c) 2,000 W — input power = 24,000 ÷ 12 = 2,000 W.

Q6. A higher EER means the AC:

  • (a) Cools faster only
  • (b) Uses less electricity for the same cooling
  • (c) Uses more electricity
  • (d) Needs a bigger breaker

Answer: (b) Uses less electricity for the same cooling — more cooling per watt means a lower electricity bill.

Q7. Compared with a 3-star AC of the same tonnage, a 5-star AC:

  • (a) Uses more power
  • (b) Uses less power
  • (c) Cools less
  • (d) Costs the same to run

Answer: (b) Uses less power — more stars mean a higher EER and lower electricity consumption.

Q8. A 1-ton AC (12,000 BTU/hr) with an EER of 9 draws about:

  • (a) 1,000 W
  • (b) 1,200 W
  • (c) 1,333 W
  • (d) 1,500 W

Answer: (c) 1,333 W — input power = 12,000 ÷ 9 = 1,333 W.

Q9. A 2-ton AC (24,000 BTU/hr) with an EER of 10 draws:

  • (a) 1,800 W
  • (b) 2,000 W
  • (c) 2,400 W
  • (d) 3,000 W

Answer: (c) 2,400 W — input power = 24,000 ÷ 10 = 2,400 W.

Q10. Which EER gives the lowest electricity bill for the same cooling?

  • (a) EER 8
  • (b) EER 10
  • (c) EER 11
  • (d) EER 12

Answer: (d) EER 12 — the highest EER draws the least power for the same amount of cooling.