UPS System MCQs — Set 6

10 practice questions on sizing a UPS for real loads, with answers and explanations. Work each one out before checking the answer.

Q1. A PC draws 300 W and a monitor draws 100 W. Both are at power factor 0.8. What minimum UPS rating in VA is needed?

  • (a) 320 VA
  • (b) 400 VA
  • (c) 500 VA
  • (d) 640 VA

Answer: (c) 500 VA — total load = 300 + 100 = 400 W; VA = 400 ÷ 0.8 = 500 VA.

Q2. Why should you add 20–25% headroom above the calculated load when choosing a UPS?

  • (a) To make the UPS heavier
  • (b) To allow for future loads, inrush current and battery ageing
  • (c) To reduce the UPS price
  • (d) To make the UPS run hotter

Answer: (b) To allow for future loads, inrush current and battery ageing — a UPS run at 100% load has no margin and a shorter battery life.

Q3. A UPS is rated 1,000 VA at a power factor of 0.8. What is the maximum load in watts it can supply?

  • (a) 1,000 W
  • (b) 800 W
  • (c) 1,250 W
  • (d) 600 W

Answer: (b) 800 W — watts = VA × power factor = 1,000 × 0.8 = 800 W.

Q4. A 5 kW load at 230 V with power factor 0.9 draws what current?

  • (a) 19.6 A
  • (b) 21.7 A
  • (c) 24.2 A
  • (d) 27.8 A

Answer: (c) 24.2 A — current = power ÷ (voltage × power factor) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.

Q5. What happens if you connect a load bigger than the UPS rating?

  • (a) The UPS delivers extra power anyway
  • (b) The UPS goes into overload, alarms, and may shut down or switch to bypass
  • (c) The battery charges faster
  • (d) Nothing — the UPS rating is only a suggestion

Answer: (b) The UPS goes into overload, alarms, and may shut down or switch to bypass — an overloaded UPS cannot protect the load.

Q6. Why should a laser printer NOT be plugged into a small UPS?

  • (a) Printers use DC power only
  • (b) Its fuser heater draws a large surge of power when warming up, which can overload the UPS
  • (c) Printers damage UPS batteries chemically
  • (d) Printers need three-phase power

Answer: (b) Its fuser heater draws a large surge of power when warming up, which can overload the UPS — the inrush can be several times the printer’s normal draw.

Q7. What is inrush current, and why does it matter for UPS sizing?

  • (a) The small current a UPS draws when idle
  • (b) A brief surge of current when equipment first switches on, which the UPS must be able to supply
  • (c) The charging current of the UPS battery
  • (d) The current flowing through the earth wire

Answer: (b) A brief surge of current when equipment first switches on, which the UPS must be able to supply — motors and power supplies can draw many times their running current at start-up.

Q8. A server room has three servers drawing 400 W, 500 W and 600 W. What is the total load?

  • (a) 1,000 W
  • (b) 1,200 W
  • (c) 1,500 W
  • (d) 2,000 W

Answer: (c) 1,500 W — total load = 400 + 500 + 600 = 1,500 W, before adding headroom and converting to VA.

Q9. A load needs 2,000 VA. With 25% headroom, what UPS rating should you choose?

  • (a) 2,000 VA
  • (b) 2,250 VA
  • (c) 2,500 VA
  • (d) 3,000 VA

Answer: (c) 2,500 VA — 2,000 × 1.25 = 2,500 VA, so a 2,500 VA (or next size up) UPS is the right choice.

Q10. Which of these should NOT be counted when adding up the load for a UPS?

  • (a) The server’s power draw
  • (b) The monitor’s power draw
  • (c) The power draw of a heater plugged into a different wall socket
  • (d) The network switch’s power draw

Answer: (c) The power draw of a heater plugged into a different wall socket — only equipment actually connected to the UPS counts towards its load.

Also read: Watt Calculator | All MCQ Topics