UPS System MCQs — Set 5

10 practice questions on UPS battery runtime calculations, with answers and explanations. Work each one out before checking the answer.

Q1. A UPS has a 12 V, 100 Ah battery and powers a 200 W load. What is the runtime at 80% usable battery capacity?

  • (a) 2.4 hours
  • (b) 4.8 hours
  • (c) 6 hours
  • (d) 12 hours

Answer: (b) 4.8 hours — battery energy = 12 × 100 = 1,200 Wh; ideal runtime = 1,200 ÷ 200 = 6 h; at 80% usable = 6 × 0.8 = 4.8 h.

Q2. A UPS has a 24 V, 100 Ah battery and powers a 400 W load. What is the runtime at 80% usable capacity?

  • (a) 2.4 hours
  • (b) 4.8 hours
  • (c) 6 hours
  • (d) 12 hours

Answer: (b) 4.8 hours — battery energy = 24 × 100 = 2,400 Wh; ideal runtime = 2,400 ÷ 400 = 6 h; at 80% = 4.8 h.

Q3. A UPS has a 12 V, 50 Ah battery and powers a 150 W load. What is the runtime at 80% usable capacity?

  • (a) 1.6 hours
  • (b) 3.2 hours
  • (c) 4 hours
  • (d) 6 hours

Answer: (b) 3.2 hours — battery energy = 12 × 50 = 600 Wh; ideal runtime = 600 ÷ 150 = 4 h; at 80% = 3.2 h.

Q4. If the load on a UPS is doubled, what happens to the battery runtime?

  • (a) It doubles
  • (b) It stays the same
  • (c) It roughly halves
  • (d) It becomes zero

Answer: (c) It roughly halves — runtime = battery energy ÷ load, so twice the load drains the battery about twice as fast.

Q5. A UPS has a 12 V, 7 Ah battery and powers a 42 W load. What is the runtime at 80% usable capacity?

  • (a) 0.8 hours
  • (b) 1.6 hours
  • (c) 2 hours
  • (d) 4 hours

Answer: (b) 1.6 hours — battery energy = 12 × 7 = 84 Wh; ideal runtime = 84 ÷ 42 = 2 h; at 80% = 1.6 h.

Q6. A UPS has a 48 V, 100 Ah battery and powers a 1,200 W load. What is the runtime at 80% usable capacity?

  • (a) 1.6 hours
  • (b) 3.2 hours
  • (c) 4 hours
  • (d) 8 hours

Answer: (b) 3.2 hours — battery energy = 48 × 100 = 4,800 Wh; ideal runtime = 4,800 ÷ 1,200 = 4 h; at 80% = 3.2 h.

Q7. A UPS has a 12 V, 200 Ah battery and powers a 300 W load. What is the runtime at 80% usable capacity?

  • (a) 3.2 hours
  • (b) 4.8 hours
  • (c) 6.4 hours
  • (d) 8 hours

Answer: (c) 6.4 hours — battery energy = 12 × 200 = 2,400 Wh; ideal runtime = 2,400 ÷ 300 = 8 h; at 80% = 6.4 h.

Q8. A UPS has a 24 V, 50 Ah battery and powers a 300 W load. What is the runtime at 80% usable capacity?

  • (a) 1.6 hours
  • (b) 2.4 hours
  • (c) 3.2 hours
  • (d) 4 hours

Answer: (c) 3.2 hours — battery energy = 24 × 50 = 1,200 Wh; ideal runtime = 1,200 ÷ 300 = 4 h; at 80% = 3.2 h.

Q9. A UPS has a 12 V, 9 Ah battery and powers a 54 W load. What is the runtime at 80% usable capacity?

  • (a) 1 hour
  • (b) 1.6 hours
  • (c) 2 hours
  • (d) 3.2 hours

Answer: (b) 1.6 hours — battery energy = 12 × 9 = 108 Wh; ideal runtime = 108 ÷ 54 = 2 h; at 80% = 1.6 h.

Q10. A UPS has a 24 V, 200 Ah battery and powers an 800 W load. What is the runtime at 80% usable capacity?

  • (a) 2.4 hours
  • (b) 3.2 hours
  • (c) 4.8 hours
  • (d) 6 hours

Answer: (c) 4.8 hours — battery energy = 24 × 200 = 4,800 Wh; ideal runtime = 4,800 ÷ 800 = 6 h; at 80% = 4.8 h.