Electrical Troubleshooting MCQs — Set 7

10 practice questions on diagnosing a tripping breaker — overload, short circuit or earth fault, and which one the symptoms point to, with answers explained.

Q1. A breaker trips a few minutes after a heavy load is switched on, and resets and works again for a while. What is the most likely cause?

  • (a) A dead short circuit
  • (b) An overload — the load is above the breaker rating, heating the thermal trip over minutes
  • (c) An open circuit
  • (d) A faulty meter

Answer: (b) An overload — the load is above the breaker rating, heating the thermal trip over minutes — overloads trip on a time delay, while short circuits trip instantly.

Q2. A 20 A circuit breaker supplies a 120 V circuit. What is the maximum continuous load allowed under the NEC 80% rule?

  • (a) 2,400 W
  • (b) 1,920 W
  • (c) 1,200 W
  • (d) 3,000 W

Answer: (b) 1,920 W — continuous load is limited to 80% of the breaker rating: 20 × 120 × 0.8 = 1,920 W.

Q3. A breaker trips instantly every time it is reset, with a loud click. What should you check first?

  • (a) Whether the load is too small
  • (b) For a short circuit — isolate the circuit and test insulation and continuity between live and neutral
  • (c) The colour of the wires
  • (d) The weather outside

Answer: (b) For a short circuit — isolate the circuit and test insulation and continuity between live and neutral — an instant magnetic trip means very high fault current, typical of a short.

Q4. An RCD trips when a particular appliance is switched on, but the MCB never trips. What does this point to?

  • (a) The appliance is overloaded
  • (b) An earth leakage fault inside that appliance
  • (c) A short circuit in the wall wiring
  • (d) The appliance draws no current

Answer: (b) An earth leakage fault inside that appliance — the RCD detects current leaking to earth; the MCB does not trip because the total current is not excessive.

Q5. A 30 mA RCD should trip within 300 ms at its rated residual current. You press its test button and it does not trip. What do you do?

  • (a) Ignore it — the button is only decorative
  • (b) Replace the RCD — it has failed its functional test and no longer provides protection
  • (c) Fit a larger RCD
  • (d) Press the button harder

Answer: (b) Replace the RCD — it has failed its functional test and no longer provides protection — a 30 mA RCD must trip within 300 ms at 1× rated current; a failed test button means it cannot be trusted.

Q6. A breaker trips only when two specific appliances run at the same time. Each one alone is fine. What is the diagnosis?

  • (a) A short circuit in one appliance
  • (b) A combined overload — together they exceed the circuit rating, though each alone does not
  • (c) An earth fault in the meter
  • (d) An open circuit

Answer: (b) A combined overload — together they exceed the circuit rating, though each alone does not — for example, a 1,500 W heater (6.5 A at 230 V) plus a 2,000 W kettle (8.7 A) together draw 15.2 A, which can overload a lightly rated circuit.

Q7. A breaker feels hot to the touch and trips on a load well below its rating. What is a likely cause?

  • (a) The load is too small
  • (b) A loose terminal connection at the breaker, causing heating at the joint
  • (c) The cable is too thick
  • (d) The supply voltage is too high

Answer: (b) A loose terminal connection at the breaker, causing heating at the joint — a poor connection generates heat at the terminal and can trip the breaker’s thermal element early.

Q8. Which test separates an overload from a short circuit when a breaker keeps tripping?

  • (a) Checking the paint colour
  • (b) Measuring the running current with a clamp meter and comparing it with the breaker rating
  • (c) Measuring the supply frequency
  • (d) Counting the sockets

Answer: (b) Measuring the running current with a clamp meter and comparing it with the breaker rating — current near or above the rating means overload; normal current with instant tripping points to a short or earth fault.

Q9. A circuit trips only in wet weather and the RCD is the device that trips. What is the most likely fault?

  • (a) An overload from too many lights
  • (b) Water ingress causing earth leakage in an outdoor light or cable joint
  • (c) A blown fuse
  • (d) A loose neutral at the meter

Answer: (b) Water ingress causing earth leakage in an outdoor light or cable joint — rain creates a leakage path to earth, and the RCD trips on the imbalance while the MCB sees no overcurrent.

Q10. Why is fitting a larger breaker never the correct fix for a tripping breaker?

  • (a) Larger breakers cost more
  • (b) The breaker protects the cable — a bigger breaker lets the cable carry more current than it is rated for, risking fire
  • (c) Larger breakers trip faster
  • (d) It voids the paint warranty

Answer: (b) The breaker protects the cable — a bigger breaker lets the cable carry more current than it is rated for, risking fire — the fault or overload must be fixed; the breaker rating must match the cable.