Electrical Troubleshooting MCQs — Set 6

10 practice questions on megger and insulation resistance testing — reading IR values and finding damaged insulation, with answers explained.

Q1. What does a megger (insulation resistance tester) measure?

  • (a) The current drawn by a load
  • (b) The resistance of the insulation between conductors, and between conductors and earth
  • (c) The voltage of the supply
  • (d) The frequency of the supply

Answer: (b) The resistance of the insulation between conductors, and between conductors and earth — it applies a high DC test voltage (typically 500 V) and measures how much current leaks through the insulation.

Q2. An insulation resistance reading above 1 MΩ on a 230 V circuit is generally treated as what?

  • (a) A fail — the cable must be replaced
  • (b) A pass — the insulation is in acceptable condition
  • (c) A short circuit
  • (d) An open circuit

Answer: (b) A pass — the insulation is in acceptable condition — readings above 1 MΩ show the insulation is resisting leakage; below 1 MΩ needs investigation.

Q3. A cable’s insulation resistance reads 0.2 MΩ between live and earth. What should you do?

  • (a) Put the circuit back in service — it is fine
  • (b) Investigate: locate the damaged or damp section, dry or repair it, and retest before use
  • (c) Fit a larger breaker
  • (d) Ignore it if the breaker does not trip

Answer: (b) Investigate: locate the damaged or damp section, dry or repair it, and retest before use — 0.2 MΩ is well below the 1 MΩ pass level, so leakage to earth is already significant.

Q4. Why must all loads and electronic devices be disconnected before a megger test?

  • (a) They make the test faster
  • (b) The 500 V test voltage can damage sensitive electronics and give false low readings through connected loads
  • (c) They improve the insulation
  • (d) The megger battery would charge

Answer: (b) The 500 V test voltage can damage sensitive electronics and give false low readings through connected loads — test the wiring alone, with loads removed.

Q5. A motor winding reads 50 MΩ to earth when dry, but 0.5 MΩ after a damp night. What is the most likely explanation?

  • (a) The winding is burnt out
  • (b) Moisture has lowered the insulation resistance — dry the motor out and retest
  • (c) The winding is shorted turn-to-turn
  • (d) The megger is faulty

Answer: (b) Moisture has lowered the insulation resistance — dry the motor out and retest — damp insulation leaks more current, so IR falls; drying usually restores the reading.

Q6. What does an insulation resistance reading of 0 MΩ (near zero) between live and earth mean?

  • (a) Perfect insulation
  • (b) A direct fault — live is effectively connected to earth, a dead short to earth
  • (c) An open circuit
  • (d) The cable is too long

Answer: (b) A direct fault — live is effectively connected to earth, a dead short to earth — near-zero resistance means the insulation has completely failed at some point.

Q7. You test a new cable and get 200 MΩ live-to-earth and 180 MΩ neutral-to-earth. How do you judge these readings?

  • (a) Both are failures
  • (b) Both are good — well above the 1 MΩ minimum, as expected for new, dry cable
  • (c) Only the higher one passes
  • (d) The cable is open-circuited

Answer: (b) Both are good — well above the 1 MΩ minimum, as expected for new, dry cable — new insulation typically reads in the hundreds of MΩ.

Q8. An IR test on a lighting circuit gives a low reading. You split the circuit in half and one half reads 100 MΩ while the other reads 0.4 MΩ. What next?

  • (a) Replace the good half
  • (b) Focus on the 0.4 MΩ half — split it again to find the damaged fitting or cable section
  • (c) Reconnect everything and switch on
  • (d) Fit a bigger RCD

Answer: (b) Focus on the 0.4 MΩ half — split it again to find the damaged fitting or cable section — half-splitting works for insulation faults too: the low-reading half contains the damage.

Q9. Which of these can cause a gradually falling insulation resistance over years?

  • (a) Heat ageing, UV damage, and mechanical wear of the cable insulation
  • (b) Using the circuit less often
  • (c) Fitting a new socket
  • (d) A higher supply voltage

Answer: (a) Heat ageing, UV damage, and mechanical wear of the cable insulation — insulation degrades slowly with heat, sunlight and movement, so IR trends downward over a cable’s life.

Q10. A megger test is a dead test. What safety step is essential before starting it?

  • (a) Switch the circuit on
  • (b) Isolate the circuit, prove it dead, and discharge any capacitance after the test
  • (c) Leave all loads connected
  • (d) Hold the test leads by hand

Answer: (b) Isolate the circuit, prove it dead, and discharge any capacitance after the test — the megger itself generates a high test voltage, so the circuit must be isolated and the stored charge discharged safely afterwards.