Three-Phase Motor MCQs — Set 8

10 practice questions on protection, faults and troubleshooting of three-phase motors, with answers.

Q1. A 4-pole motor on a 50 Hz supply has a synchronous speed of 1,500 rpm and runs at 1,440 rpm. What is its slip?

  • (a) 2%
  • (b) 4%
  • (c) 6%
  • (d) 10%

Answer: (b) 4% — slip = (Ns − Nr) ÷ Ns × 100 = (1,500 − 1,440) ÷ 1,500 × 100 = 60 ÷ 1,500 × 100 = 4%.

Q2. What is single phasing in a three-phase motor?

  • (a) Running the motor on one phase only after a fuse blows or a connection opens
  • (b) Starting the motor in star
  • (c) Reversing the phase sequence
  • (d) Running the motor at half speed

Answer: (a) Running the motor on one phase only after a fuse blows or a connection opens — the motor loses one supply phase and continues on the other two.

Q3. What happens to a running three-phase motor that loses one phase?

  • (a) It stops instantly with no damage
  • (b) It keeps running but draws much higher current in the remaining phases and overheats
  • (c) It speeds up to synchronous speed
  • (d) Its power factor becomes unity

Answer: (b) It keeps running but draws much higher current in the remaining phases and overheats — the two remaining phases must carry the load, so winding current rises and the motor can burn out if protection does not trip.

Q4. A three-phase motor hums loudly but does not start. What is the most likely cause?

  • (a) The motor is running at full speed
  • (b) Single phasing — one phase is missing, so no rotating field is produced
  • (c) The VFD frequency is too high
  • (d) The bearings are over-greased

Answer: (b) Single phasing — one phase is missing, so no rotating field is produced — with only two phases the field pulsates instead of rotating, the motor hums and stays still.

Q5. What size of RCCB is used for personal protection against electric shock?

  • (a) 300 mA
  • (b) 100 mA
  • (c) 30 mA
  • (d) 500 mA

Answer: (c) 30 mA — a 30 mA RCCB trips fast enough on earth leakage to protect people from a dangerous shock.

Q6. What does a low insulation-resistance (megger) reading on a motor winding indicate?

  • (a) The winding is in perfect condition
  • (b) Damp, dirty or damaged insulation that may fail to earth
  • (c) The motor is running efficiently
  • (d) The rotor is balanced

Answer: (b) Damp, dirty or damaged insulation that may fail to earth — a low reading means leakage current can flow through the insulation, so the motor should be dried or repaired before use.

Q7. Which device protects a motor circuit against short circuits?

  • (a) A thermal overload relay
  • (b) An MCCB or fuse, which clears heavy fault current quickly
  • (c) A thermostat
  • (d) A timer

Answer: (b) An MCCB or fuse, which clears heavy fault current quickly — short-circuit protection must act in milliseconds, far faster than an overload relay.

Q8. What is a common symptom of a failing motor bearing?

  • (a) The motor runs cooler than normal
  • (b) Excessive vibration, noise and heat at the bearing end
  • (c) Higher power factor
  • (d) Lower starting current

Answer: (b) Excessive vibration, noise and heat at the bearing end — worn or dry bearings rumble, vibrate and run hot, and will seize if left.

Q9. What effect does unbalanced supply voltage have on a three-phase motor?

  • (a) No effect at all
  • (b) It creates a negative-sequence field that causes extra heating and vibration
  • (c) It increases the synchronous speed
  • (d) It reduces the starting current

Answer: (b) It creates a negative-sequence field that causes extra heating and vibration — the unbalanced voltages produce a field rotating against the rotor, wasting energy as heat.

Q10. Why does undervoltage make a loaded induction motor draw more current?

  • (a) The load torque falls
  • (b) Torque falls with the square of voltage, so slip and current must rise to deliver the same load torque
  • (c) The motor speeds up
  • (d) The power factor becomes unity

Answer: (b) Torque falls with the square of voltage, so slip and current must rise to deliver the same load torque — the motor slows, slip increases, rotor current rises and the windings overheat.

Also read: AFCI Breaker Keeps Tripping | All MCQ Topics