Three-Phase Motor MCQs — Set 5

10 practice questions on variable-frequency drives and speed control of three-phase motors, with worked answers.

Q1. How does a variable-frequency drive (VFD) change the speed of an induction motor?

  • (a) By changing the number of poles
  • (b) By varying the supply frequency (and voltage) fed to the motor
  • (c) By adding resistance to the stator
  • (d) By changing the rotor bars

Answer: (b) By varying the supply frequency (and voltage) fed to the motor — synchronous speed follows frequency, so lowering frequency lowers speed and raising it raises speed.

Q2. A 4-pole motor is run from a VFD at 25 Hz. What is its synchronous speed?

  • (a) 1,500 rpm
  • (b) 750 rpm
  • (c) 3,000 rpm
  • (d) 1,000 rpm

Answer: (b) 750 rpm — Ns = 120 × f ÷ P = 120 × 25 ÷ 4 = 3,000 ÷ 4 = 750 rpm.

Q3. A 4-pole motor is run from a VFD at 60 Hz. What is its synchronous speed?

  • (a) 1,500 rpm
  • (b) 1,200 rpm
  • (c) 1,800 rpm
  • (d) 900 rpm

Answer: (c) 1,800 rpm — Ns = 120 × 60 ÷ 4 = 7,200 ÷ 4 = 1,800 rpm.

Q4. Why does a VFD keep the voltage-to-frequency (V/f) ratio roughly constant below base speed?

  • (a) To keep the motor flux constant and avoid saturation or weak torque
  • (b) To keep the power factor at unity
  • (c) To reduce the number of poles
  • (d) To increase slip

Answer: (a) To keep the motor flux constant and avoid saturation or weak torque — flux depends on V/f, so voltage must fall in step with frequency to hold torque steady.

Q5. A 4-pole motor is run from a VFD at 40 Hz. What is its synchronous speed?

  • (a) 1,500 rpm
  • (b) 1,200 rpm
  • (c) 1,000 rpm
  • (d) 750 rpm

Answer: (b) 1,200 rpm — Ns = 120 × 40 ÷ 4 = 4,800 ÷ 4 = 1,200 rpm.

Q6. What is the main energy-saving benefit of a VFD on a fan or pump?

  • (a) It removes the need for a motor
  • (b) Slowing the fan slightly cuts power sharply, instead of wasting energy in a damper or valve
  • (c) It raises the supply voltage
  • (d) It increases the starting current

Answer: (b) Slowing the fan slightly cuts power sharply, instead of wasting energy in a damper or valve — fan power falls roughly with the cube of speed, so a small speed cut saves a lot of energy.

Q7. What type of output waveform does a modern VFD produce?

  • (a) Pure sine wave from the mains
  • (b) A pulse-width-modulated (PWM) waveform that approximates a sine wave
  • (c) A DC output
  • (d) A square wave at fixed 50 Hz

Answer: (b) A pulse-width-modulated (PWM) waveform that approximates a sine wave — fast switching builds a variable-frequency, variable-voltage output from the DC link.

Q8. Why can a standard self-cooled (TEFC) motor overheat when run very slowly from a VFD?

  • (a) The supply voltage rises
  • (b) Its shaft-mounted fan turns slowly, so cooling airflow falls while losses continue
  • (c) The slip becomes zero
  • (d) The rotor bars melt at low speed

Answer: (b) Its shaft-mounted fan turns slowly, so cooling airflow falls while losses continue — at low speed the fan moves little air, so a separate cooling fan may be needed for continuous slow running.

Q9. What happens above base frequency when a VFD raises frequency but voltage stays at its rated maximum?

  • (a) Torque stays constant
  • (b) Flux falls and available torque drops, in the constant-power (field-weakening) region
  • (c) The motor stops
  • (d) Slip becomes negative

Answer: (b) Flux falls and available torque drops, in the constant-power (field-weakening) region — voltage cannot rise above rated, so V/f and flux fall as frequency rises.

Q10. Which braking method feeds the motor’s kinetic energy back to the supply through the VFD?

  • (a) DC injection braking
  • (b) Regenerative braking
  • (c) Plugging
  • (d) Mechanical braking

Answer: (b) Regenerative braking — the motor acts as a generator and the drive returns energy to the supply instead of wasting it as heat.

Also read: Watt Calculator | All MCQ Topics