Three-Phase Motor MCQs — Set 4
10 practice questions on starting methods for three-phase motors — DOL, star-delta and reduced-voltage starting — with answers.
Q1. How large is the starting current of a direct-on-line (DOL) started induction motor?
- (a) About the same as full-load current
- (b) About 5 to 7 times full-load current
- (c) About half the full-load current
- (d) Zero until the motor reaches full speed
Answer: (b) About 5 to 7 times full-load current — at standstill the motor looks like a short-circuited transformer, so it draws a heavy inrush that falls as it speeds up.
Q2. In star-delta starting, how does the line current in star compare with direct-on-line starting?
- (a) The same
- (b) Three times larger
- (c) One-third of the DOL starting current
- (d) Half of the DOL starting current
Answer: (c) One-third of the DOL starting current — in star each winding gets 1/√3 of line voltage, so phase current falls to 1/3 and line current to 1/3 of the DOL value.
Q3. In star-delta starting, how does the starting torque in star compare with DOL starting torque?
- (a) The same
- (b) One-third of the DOL starting torque
- (c) Three times larger
- (d) Half of the DOL starting torque
Answer: (b) One-third of the DOL starting torque — torque varies with the square of voltage, and star voltage is 1/√3 of delta voltage, so torque is (1/√3)² = 1/3.
Q4. In star connection, what is the voltage across each motor winding?
- (a) The full line voltage
- (b) Line voltage divided by √3
- (c) Line voltage multiplied by √3
- (d) Half the line voltage
Answer: (b) Line voltage divided by √3 — in star, phase voltage = line voltage ÷ √3, about 58% of line voltage.
Q5. When is the motor switched from star to delta in a star-delta starter?
- (a) Immediately at switch-on
- (b) When it has run up to near full speed
- (c) When it stalls
- (d) Only when it is switched off
Answer: (b) When it has run up to near full speed — the timer changes over once the motor is close to running speed, so the second current surge is small.
Q6. How many motor terminals must be brought out for star-delta starting?
- (a) Three
- (b) Four
- (c) Six — both ends of all three windings
- (d) Two
Answer: (c) Six — both ends of all three windings — the starter must be able to connect the windings in star and then re-connect them in delta.
Q7. Why is starting current reduced instead of always using DOL starting?
- (a) To make the motor run faster
- (b) To avoid a large voltage dip on the supply and disturbance to other loads
- (c) To increase the starting torque
- (d) To reduce the power factor
Answer: (b) To avoid a large voltage dip on the supply and disturbance to other loads — a 5–7 times inrush can dim lights and trip other equipment on a weak supply.
Q8. For which motors is DOL starting normally suitable?
- (a) Only very large motors above 100 kW
- (b) Small motors, typically up to about 5–7.5 kW, on a stiff supply
- (c) Only wound-rotor motors
- (d) Motors that must start on full load torque
Answer: (b) Small motors, typically up to about 5–7.5 kW, on a stiff supply — their inrush is small in absolute terms, so the supply can absorb it without a harmful dip.
Q9. What does a soft starter do at switch-on?
- (a) Applies full voltage instantly
- (b) Ramps the voltage up gradually so current and torque rise smoothly
- (c) Changes the supply frequency
- (d) Reverses the phase sequence
Answer: (b) Ramps the voltage up gradually so current and torque rise smoothly — thyristors raise the voltage over a set time, giving a gentle start with less mechanical shock than DOL.
Q10. What is the main disadvantage of star-delta starting?
- (a) It needs a variable-frequency drive
- (b) Starting torque falls to one-third, so it cannot start heavy loads
- (c) It increases the running current
- (d) It changes the synchronous speed
Answer: (b) Starting torque falls to one-third, so it cannot start heavy loads — star-delta suits fans and pumps that start light, not crushers or conveyors that need full torque at standstill.