Testing and Commissioning MCQs — Set 10
10 mixed practice questions on testing and commissioning — leakage and fault-current calculations plus the test order every electrician must know.
Q1. A circuit has an insulation resistance of 0.5 MΩ. What leakage current would flow to earth at 230 V?
- (a) 0.115 mA
- (b) 0.23 mA
- (c) 0.46 mA
- (d) 4.6 mA
Answer: (c) 0.46 mA — I = V ÷ R = 230 ÷ 500,000 = 0.00046 A = 0.46 mA, a small leakage that shows why low insulation resistance matters.
Q2. A 400 V circuit has an insulation resistance of 2 MΩ. What leakage current would flow to earth?
- (a) 0.2 mA
- (b) 0.8 mA
- (c) 2 mA
- (d) 5 mA
Answer: (a) 0.2 mA — I = V ÷ R = 400 ÷ 2,000,000 = 0.0002 A = 0.2 mA.
Q3. The external earth loop impedance Ze is 0.4 Ω and (R1+R2) is 0.6 Ω. What is Zs?
- (a) 0.2 Ω
- (b) 1.0 Ω
- (c) 0.24 Ω
- (d) 1.5 Ω
Answer: (b) 1.0 Ω — Zs = Ze + (R1+R2) = 0.4 + 0.6 = 1.0 Ω.
Q4. A 230 V circuit has Zs = 1.15 Ω. What earth fault current will flow?
- (a) 115 A
- (b) 230 A
- (c) 265 A
- (d) 200 A
Answer: (d) 200 A — I = V ÷ Zs = 230 ÷ 1.15 = 200 A.
Q5. A 230 V circuit has Zs = 0.46 Ω. What earth fault current will flow?
- (a) 500 A
- (b) 106 A
- (c) 230 A
- (d) 460 A
Answer: (a) 500 A — I = V ÷ Zs = 230 ÷ 0.46 = 500 A, a very large fault current that will operate the protective device almost instantly.
Q6. A megger applies 1,000 V DC and the leakage current through the insulation is 0.5 mA. What is the insulation resistance?
- (a) 0.5 MΩ
- (b) 1 MΩ
- (c) 2 MΩ
- (d) 5 MΩ
Answer: (c) 2 MΩ — R = V ÷ I = 1,000 ÷ 0.0005 = 2,000,000 Ω = 2 MΩ, comfortably above the 1 MΩ minimum.
Q7. Why is insulation tested at 500 V DC when the circuit normally runs at 230 V?
- (a) Because 230 V would damage the megger
- (b) Because a test voltage higher than the operating voltage stresses weak insulation and reveals faults the normal voltage would not show
- (c) Because the test is faster at 500 V
- (d) Because 230 V is not available on site
Answer: (b) Because a test voltage higher than the operating voltage stresses weak insulation and reveals faults the normal voltage would not show — insulation that holds at 230 V can still break down under the higher test voltage.
Q8. What is the correct order for the dead tests on a new circuit?
- (a) Polarity first, then insulation resistance, then continuity
- (b) Insulation resistance first, then polarity, then continuity
- (c) Live tests first, then dead tests
- (d) Continuity of protective conductors first, then insulation resistance, then polarity
Answer: (d) Continuity of protective conductors first, then insulation resistance, then polarity — continuity proves the conductors are complete, insulation proves they are sound, and polarity proves they are the right way round, all before any live test.
Q9. Which two tests must always be carried out with the supply isolated (dead)?
- (a) Insulation resistance and continuity
- (b) RCD testing and loop impedance testing
- (c) Load testing and functional testing
- (d) Voltage measurement and load testing
Answer: (a) Insulation resistance and continuity — both apply the tester’s own voltage or current to the conductors, so the supply must be off and the circuit proved dead first.
Q10. Before touching a circuit that should be dead, how is the voltage indicator proved to be working?
- (a) By shaking it
- (b) By testing it on the circuit itself
- (c) By checking it on a known live source before testing the circuit, and again afterwards
- (d) By leaving it in the toolbox
Answer: (c) By checking it on a known live source before testing the circuit, and again afterwards — this prove-test-prove routine makes sure a faulty indicator cannot falsely show a live circuit as dead.
Also read: AFCI Breaker Keeps Tripping | All MCQ Topics