Testing and Commissioning MCQs — Set 5
10 practice questions on RCD and RCCB testing — trip currents, trip times and what the test button really proves.
Q1. What rated tripping current is normally used for an RCD protecting socket outlets for personal protection?
- (a) 10 A
- (b) 30 mA
- (c) 100 mA
- (d) 300 mA
Answer: (b) 30 mA — a 30 mA RCD is the standard rating for personal protection, tripping on a leakage current small enough to limit shock harm.
Q2. A 30 mA RCD is tested at its rated current (1 × 30 mA). Within what time must it trip?
- (a) Within 300 ms
- (b) Within 40 ms
- (c) Within 5 seconds
- (d) Within 1 minute
Answer: (a) Within 300 ms — at 1 × rated current (30 mA) a 30 mA RCD must trip within 300 ms.
Q3. A 30 mA RCD is tested at 5 × its rated current. Within what time must it trip?
- (a) Within 300 ms
- (b) Within 5 seconds
- (c) Within 40 ms
- (d) Within 1 second
Answer: (c) Within 40 ms — at 5 × rated current the RCD must trip much faster, within 40 ms, to cut off a serious fault quickly.
Q4. What is the 5 × test current for a 30 mA RCD?
- (a) 35 mA
- (b) 60 mA
- (c) 100 mA
- (d) 150 mA
Answer: (d) 150 mA — 5 × 30 mA = 150 mA, the current applied in the 5 × trip-time test.
Q5. What does pressing the test button on an RCD actually prove?
- (a) That the RCD trips at exactly 30 mA in 40 ms
- (b) Only that the mechanical trip mechanism works — it does not check the trip current or trip time
- (c) That the earth loop impedance is correct
- (d) That the insulation resistance is above 1 MΩ
Answer: (b) Only that the mechanical trip mechanism works — it does not check the trip current or trip time — the button creates an internal imbalance to trip the device; proper testing needs an RCD tester.
Q6. An RCD fails to trip when tested at 30 mA with an RCD tester. What should be done?
- (a) Leave it in service and test it again next year
- (b) Press the test button harder
- (c) Replace the RCD — it no longer gives the protection it is there for
- (d) Fit a larger circuit breaker
Answer: (c) Replace the RCD — it no longer gives the protection it is there for — a device that will not trip at its rated current is faulty and must not stay in service.
Q7. Which instrument is used to test an RCD’s tripping current and tripping time properly?
- (a) A megger
- (b) A wattmeter
- (c) An RCD tester
- (d) A phase rotation tester
Answer: (c) An RCD tester — it applies a known leakage current (for example 30 mA or 150 mA) and times how fast the RCD trips.
Q8. Why is an RCD also tested at 5 × its rated current?
- (a) To check it does not trip on normal load
- (b) To prove it trips fast enough when a large fault current flows
- (c) To measure the supply voltage
- (d) To warm up the test instrument
Answer: (b) To prove it trips fast enough when a large fault current flows — a real earth fault can be far larger than 30 mA, and the RCD must clear it within 40 ms at 5 × rated current.
Q9. An RCD keeps tripping even though the circuit wiring tests fine. What is a likely cause?
- (a) A faulty appliance on the circuit leaking current to earth
- (b) The cable being too short
- (c) The supply frequency being 50 Hz
- (d) The sockets being new
Answer: (a) A faulty appliance on the circuit leaking current to earth — damp, damaged or ageing appliances leak small currents that add up and trip a healthy RCD; unplug appliances one by one to find the culprit.
Q10. What does an RCD ramp test measure?
- (a) The supply voltage under load
- (b) The actual leakage current at which the RCD trips, by slowly increasing the test current
- (c) The resistance of the circuit cable
- (d) The speed of the electricity meter
Answer: (b) The actual leakage current at which the RCD trips, by slowly increasing the test current — the ramp test finds the real tripping current, which should be at or below the 30 mA rating.