Testing and Commissioning MCQs — Set 4
10 practice questions on earth loop impedance — how Zs is calculated, what it means, and the fault currents it produces.
Q1. How is the earth fault loop impedance Zs of a circuit calculated?
- (a) Zs = Ze − (R1+R2)
- (b) Zs = Ze × (R1+R2)
- (c) Zs = Ze + (R1+R2)
- (d) Zs = Ze ÷ (R1+R2)
Answer: (c) Zs = Ze + (R1+R2) — Zs is the external loop impedance Ze plus the resistance of the circuit’s line and protective conductors.
Q2. The external earth loop impedance Ze is 0.2 Ω and (R1+R2) is 0.3 Ω. What is Zs?
- (a) 0.5 Ω
- (b) 0.1 Ω
- (c) 0.6 Ω
- (d) 1.5 Ω
Answer: (a) 0.5 Ω — Zs = Ze + (R1+R2) = 0.2 + 0.3 = 0.5 Ω.
Q3. The external earth loop impedance Ze is 0.35 Ω and (R1+R2) is 0.45 Ω. What is Zs?
- (a) 0.10 Ω
- (b) 0.8 Ω
- (c) 1.2 Ω
- (d) 0.35 Ω
Answer: (b) 0.8 Ω — Zs = Ze + (R1+R2) = 0.35 + 0.45 = 0.8 Ω.
Q4. The external earth loop impedance Ze is 0.15 Ω and (R1+R2) is 0.45 Ω. What is Zs?
- (a) 0.30 Ω
- (b) 0.45 Ω
- (c) 0.15 Ω
- (d) 0.6 Ω
Answer: (d) 0.6 Ω — Zs = Ze + (R1+R2) = 0.15 + 0.45 = 0.6 Ω.
Q5. A 230 V circuit has Zs = 0.5 Ω. What earth fault current will flow if the line conductor touches an earthed metal case?
- (a) 115 A
- (b) 230 A
- (c) 460 A
- (d) 920 A
Answer: (c) 460 A — I = V ÷ Zs = 230 ÷ 0.5 = 460 A, a large fault current that will trip the protective device quickly.
Q6. A 230 V circuit has Zs = 0.8 Ω. What earth fault current will flow?
- (a) 287.5 A
- (b) 184 A
- (c) 230 A
- (d) 640 A
Answer: (a) 287.5 A — I = V ÷ Zs = 230 ÷ 0.8 = 287.5 A.
Q7. Why must the earth loop impedance Zs be low enough?
- (a) To make the lights brighter
- (b) So a large fault current flows and the breaker or fuse disconnects the fault quickly
- (c) To reduce the electricity bill
- (d) To keep the cable cool in summer
Answer: (b) So a large fault current flows and the breaker or fuse disconnects the fault quickly — a high Zs gives a small fault current, and the protective device may take too long to trip.
Q8. Where is the external earth loop impedance Ze measured?
- (a) At the farthest socket on the circuit
- (b) At the light switch
- (c) At the electricity meter
- (d) At the origin of the installation, where the supply enters
Answer: (d) At the origin of the installation, where the supply enters — Ze is the impedance of the supply’s own earth path, before any of the installation’s circuits are added.
Q9. A circuit’s measured Zs is much higher than the allowed maximum. What is the danger?
- (a) The circuit will use more power
- (b) The breaker will trip too fast
- (c) The lights will flicker
- (d) A fault may not trip the breaker in time, leaving metal parts live and a shock risk
Answer: (d) A fault may not trip the breaker in time, leaving metal parts live and a shock risk — high Zs means low fault current, so disconnection is too slow and the fault stays dangerous.
Q10. Which instrument measures earth loop impedance Zs directly?
- (a) A megger
- (b) An earth loop impedance tester
- (c) A clamp meter
- (d) A tachometer
Answer: (b) An earth loop impedance tester — it briefly applies a test load between line and earth and measures the resulting loop impedance.