Testing and Commissioning MCQs — Set 2
10 practice questions on insulation resistance testing — the megger, test voltages, pass limits and worked calculations.
Q1. Which instrument is used to measure insulation resistance?
- (a) A megger (insulation resistance tester)
- (b) A clamp meter
- (c) A wattmeter
- (d) A frequency meter
Answer: (a) A megger (insulation resistance tester) — it applies a high DC test voltage and measures the very small leakage current through the insulation.
Q2. What DC test voltage is normally used for insulation resistance testing of low-voltage circuits?
- (a) 12 V
- (b) 230 V
- (c) 500 V
- (d) 5,000 V
Answer: (c) 500 V — the standard megger test voltage for low-voltage circuits is 500 V DC, which stresses the insulation more than normal supply voltage.
Q3. What is the usual minimum acceptable insulation resistance for a low-voltage circuit?
- (a) 0.1 MΩ
- (b) More than 1 MΩ
- (c) 100 Ω
- (d) 10 kΩ
Answer: (b) More than 1 MΩ — an insulation resistance above 1 MΩ is the standard pass value for low-voltage circuits; below that, the insulation is suspect.
Q4. A megger applies 500 V DC and the leakage current through the insulation is 0.5 mA. What is the insulation resistance?
- (a) 0.25 MΩ
- (b) 1 MΩ
- (c) 2 MΩ
- (d) 10 MΩ
Answer: (b) 1 MΩ — R = V ÷ I = 500 ÷ 0.0005 = 1,000,000 Ω = 1 MΩ, just at the minimum pass value.
Q5. A megger applies 500 V DC and the leakage current is 0.25 mA. What is the insulation resistance, and does the circuit pass?
- (a) 0.5 MΩ — fail
- (b) 1 MΩ — pass
- (c) 1.25 MΩ — pass
- (d) 2 MΩ — pass
Answer: (d) 2 MΩ — pass — R = V ÷ I = 500 ÷ 0.00025 = 2,000,000 Ω = 2 MΩ, which is above the 1 MΩ minimum, so the circuit passes.
Q6. A megger applies 500 V DC and the leakage current is 1 mA. What is the insulation resistance, and does the circuit pass?
- (a) 0.5 MΩ — fail
- (b) 1 MΩ — pass
- (c) 2 MΩ — pass
- (d) 5 MΩ — pass
Answer: (a) 0.5 MΩ — fail — R = V ÷ I = 500 ÷ 0.001 = 500,000 Ω = 0.5 MΩ, below the 1 MΩ minimum, so the insulation must be investigated and the fault fixed.
Q7. Why must electronic equipment be disconnected before an insulation resistance test?
- (a) It makes the test faster
- (b) It saves battery power in the tester
- (c) The 500 V DC test voltage can damage sensitive electronic components
- (d) Electronics change the colour of the test leads
Answer: (c) The 500 V DC test voltage can damage sensitive electronic components — dimmers, electronic controls and appliances with electronics must be disconnected or the test will destroy them.
Q8. Between which conductors is insulation resistance measured?
- (a) Only between the two live conductors
- (b) Between live conductors and between each live conductor and earth
- (c) Only between the cable and the wall
- (d) Only between the neutral and the meter
Answer: (b) Between live conductors and between each live conductor and earth — both checks are needed, because a fault can exist between lives or from a live to earth.
Q9. What test voltage is typically used for insulation testing of higher-voltage equipment rather than low-voltage circuits?
- (a) 50 V
- (b) 230 V
- (c) 500 V
- (d) 1,000 V
Answer: (d) 1,000 V — higher-voltage equipment is tested at 1,000 V DC, while ordinary low-voltage circuits use 500 V DC.
Q10. An insulation resistance reading comes back very low on a cable that was fine last year. What is the most likely cause?
- (a) Damp or damaged insulation letting current leak away
- (b) The cable has become too short
- (c) The supply voltage has increased
- (d) The test leads are new
Answer: (a) Damp or damaged insulation letting current leak away — moisture, heat damage or a nicked sheath lowers insulation resistance, and a low reading is the warning sign.