Synchronous Motor MCQs — Set 3
10 practice questions on synchronous motor excitation — V-curves, under-excitation, over-excitation and power factor.
Q1. An over-excited synchronous motor draws what kind of current from the supply?
- (a) Lagging current
- (b) Leading current
- (c) Unity power factor current only
- (d) No current at all
Answer: (b) Leading current — over-excitation makes the motor supply reactive power, so its current leads the voltage.
Q2. An under-excited synchronous motor draws what kind of current?
- (a) Leading current
- (b) Lagging current
- (c) Zero current
- (d) Direct current
Answer: (b) Lagging current — with weak field excitation the motor absorbs reactive power, so its current lags the voltage.
Q3. What does a V-curve of a synchronous motor plot?
- (a) Speed against load
- (b) Armature current against field current at constant load
- (c) Torque against speed
- (d) Power factor against load
Answer: (b) Armature current against field current at constant load — the curve is V-shaped, with minimum current at unity power factor.
Q4. At what point is the armature current of a synchronous motor at its minimum for a given load?
- (a) At maximum excitation
- (b) At minimum excitation
- (c) At unity power factor
- (d) At zero excitation
Answer: (c) At unity power factor — at unity power factor the current is purely active, so it is the smallest possible for that load.
Q5. What is “normal excitation” of a synchronous motor?
- (a) The excitation that gives zero power factor
- (b) The excitation that gives unity power factor
- (c) The excitation that gives maximum current
- (d) The excitation at no load only
Answer: (b) The excitation that gives unity power factor — this is also called critical excitation.
Q6. At constant load, if the field current is increased gradually from a low value, what happens to the power factor?
- (a) It stays lagging throughout
- (b) It changes from lagging to unity and then to leading
- (c) It changes from leading to unity and then to lagging
- (d) It stays at unity throughout
Answer: (b) It changes from lagging to unity and then to leading — under-excitation is lagging, normal excitation is unity, over-excitation is leading.
Q7. What does an inverted V-curve of a synchronous motor plot?
- (a) Armature current against field current
- (b) Power factor against field current at constant load
- (c) Speed against field current
- (d) Torque against field current
Answer: (b) Power factor against field current at constant load — the curve peaks at unity power factor at normal excitation.
Q8. What is critical excitation?
- (a) The excitation at which the motor loses synchronism
- (b) The excitation that gives unity power factor
- (c) The excitation at which hunting starts
- (d) The maximum safe field current
Answer: (b) The excitation that gives unity power factor — below it the motor is under-excited (lagging), above it over-excited (leading).
Q9. An over-excited synchronous motor running at no load behaves like what device?
- (a) An induction motor
- (b) A synchronous capacitor (condenser)
- (c) A transformer
- (d) A resistor
Answer: (b) A synchronous capacitor (condenser) — at no load with over-excitation it draws leading current and supplies reactive power, like a capacitor.
Q10. At constant load, if the excitation is increased beyond normal, what happens to the armature current?
- (a) It keeps decreasing
- (b) It first decreases to a minimum, then increases again
- (c) It stays constant
- (d) It falls to zero
Answer: (b) It first decreases to a minimum, then increases again — that minimum occurs at unity power factor; further excitation raises the leading reactive current.
Also read: Dynamo vs Alternator | All MCQ Topics