Switchgear MCQs — Set 9
10 practice questions on switchgear maintenance and testing — insulation tests, contact resistance, timing tests and gas and oil checks, with answers and explanations.
Q1. An insulation-resistance (megger) test on switchgear checks:
- (a) The resistance of the copper busbar
- (b) The health of insulation between live parts and earth
- (c) The breaking capacity
- (d) The relay settings
Answer: (b) The health of insulation between live parts and earth — low readings point to damp, dirty or damaged insulation.
Q2. A contact-resistance test is done to detect:
- (a) Worn or pitted contacts and loose joints
- (b) Low SF6 pressure
- (c) Wrong relay settings
- (d) Busbar vibration
Answer: (a) Worn or pitted contacts and loose joints — high contact resistance causes overheating at the joint under load.
Q3. A breaker timing test measures:
- (a) The time taken to charge the battery
- (b) The opening and closing times of the breaker
- (c) The insulation resistance
- (d) The CT ratio
Answer: (b) The opening and closing times of the breaker — slow operation can fail to clear a fault within the safe time.
Q4. What is checked during SF6 gas maintenance?
- (a) Oil colour
- (b) Gas pressure/density and leakage
- (c) Contact wear only
- (d) Battery voltage
Answer: (b) Gas pressure/density and leakage — low SF6 pressure reduces dielectric strength and breaking ability, so density is monitored continuously.
Q5. The dielectric strength (BDV) test of oil in an oil circuit breaker checks:
- (a) Whether the oil can still insulate and quench the arc
- (b) The oil level only
- (c) The colour of the oil
- (d) The viscosity of the oil
Answer: (a) Whether the oil can still insulate and quench the arc — a low breakdown voltage means the oil is contaminated and must be filtered or replaced.
Q6. Thermographic (infrared) scanning of switchgear is used to find:
- (a) Loose or overheated joints and hot spots without shutting down
- (b) Relay faults
- (c) SF6 leaks directly
- (d) The fault current level
Answer: (a) Loose or overheated joints and hot spots without shutting down — the camera sees heat while the gear stays in service.
Q7. Why must the breaker operating mechanism be lubricated and exercised regularly?
- (a) To reduce its weight
- (b) To ensure fast, reliable opening and closing when a fault occurs
- (c) To increase its voltage rating
- (d) To save electricity
Answer: (b) To ensure fast, reliable opening and closing when a fault occurs — a stiff or seized mechanism can fail to trip when it matters most.
Q8. The vacuum integrity of a VCB bottle is checked by:
- (a) A high-voltage withstand test across the open contacts
- (b) Measuring the oil level
- (c) A megger test on the trip coil
- (d) Weighing the breaker
Answer: (a) A high-voltage withstand test across the open contacts — if the vacuum is lost, the bottle will break down at the test voltage.
Q9. A sign that switchgear contacts need attention is:
- (a) A hot spot at a joint found by infrared scanning
- (b) A green indication lamp
- (c) Normal operating noise
- (d) A clean enclosure
Answer: (a) A hot spot at a joint found by infrared scanning — heat at a joint means high contact resistance from wear, pitting or looseness.
Q10. Before maintenance work begins on switchgear, it must be:
- (a) Left energised for testing
- (b) Isolated, earthed and proved dead
- (c) Sprayed with oil
- (d) Run at full load
Answer: (b) Isolated, earthed and proved dead — this is the basic safety rule before anyone touches switchgear.
Also read: Electrical Safety MCQs | All MCQ Topics