Switchgear MCQs — Set 8
10 practice questions on switchgear protection and control — relays, DC trip circuits, interlocks, auto-reclosers and SCADA, with answers and explanations.
Q1. What is the function of a protective relay in switchgear?
- (a) To interrupt the fault current itself
- (b) To detect the fault and send a trip signal to the circuit breaker
- (c) To measure the load
- (d) To earth the busbar
Answer: (b) To detect the fault and send a trip signal to the circuit breaker — the relay senses abnormal current or voltage and orders the breaker to open.
Q2. Trip circuits in switchgear are usually supplied from:
- (a) The AC mains only
- (b) A DC battery
- (c) A solar panel
- (d) The CT secondary
Answer: (b) A DC battery — a battery-backed DC supply keeps protection working even when the AC supply fails.
Q3. Why is DC preferred for breaker trip and control circuits?
- (a) DC is cheaper to generate
- (b) The battery keeps protection alive during a fault or AC supply failure
- (c) DC breakers are smaller
- (d) Relays work only on DC
Answer: (b) The battery keeps protection alive during a fault or AC supply failure — a fault can collapse the AC voltage, but the battery still trips the breaker.
Q4. What is the purpose of an interlock in switchgear?
- (a) To increase the fault current
- (b) To prevent an unsafe or wrong switching sequence
- (c) To cool the breaker
- (d) To measure insulation resistance
Answer: (b) To prevent an unsafe or wrong switching sequence — for example, stopping an isolator from opening on load or an earthing switch from closing onto a live circuit.
Q5. What does SCADA do in a modern substation?
- (a) Generates power
- (b) Allows remote monitoring and control of switchgear
- (c) Replaces the circuit breaker
- (d) Supplies the load directly
Answer: (b) Allows remote monitoring and control of switchgear — operators can see breaker status and switch feeders from a control centre.
Q6. An overcurrent relay trips the breaker when:
- (a) The voltage rises
- (b) The current exceeds its set value for a set time
- (c) The frequency falls
- (d) The temperature falls
Answer: (b) The current exceeds its set value for a set time — the time delay lets the relay grade with downstream protection.
Q7. An earth-fault relay detects:
- (a) Overvoltage
- (b) Current leaking to earth
- (c) Over-frequency
- (d) High power factor
Answer: (b) Current leaking to earth — it senses the residual current that flows when a phase touches earth.
Q8. What does breaker-failure protection do?
- (a) Repairs the breaker
- (b) If a breaker fails to clear a fault, it trips the adjacent breakers
- (c) Prevents the breaker from closing
- (d) Increases the breaking capacity
Answer: (b) If a breaker fails to clear a fault, it trips the adjacent breakers — it is the backup that stops a stuck breaker from leaving a fault on the system.
Q9. What is an auto-recloser?
- (a) A device that recloses a breaker automatically after a transient fault, to restore supply
- (b) A manual isolator
- (c) A type of CT
- (d) A battery charger
Answer: (a) A device that recloses a breaker automatically after a transient fault, to restore supply — most overhead-line faults are temporary, such as a lightning flashover.
Q10. On a switchgear panel, the standard indication is:
- (a) Red lamp = breaker open, green lamp = breaker closed
- (b) Red lamp = breaker closed, green lamp = breaker open
- (c) Red lamp = earth fault only
- (d) Green lamp = breaker tripped
Answer: (b) Red lamp = breaker closed, green lamp = breaker open — red means the circuit is live and dangerous, green means it is open and safe.
Also read: Breaker and Protection MCQs | All MCQ Topics