Switchgear MCQs — Set 6

10 practice questions on switchgear ratings — breaking capacity in MVA, making capacity, short-time current and rated voltage — with worked calculations.

Q1. A breaker at 11 kV has a symmetrical breaking current of 25 kA. What is its breaking capacity?

  • (a) 476 MVA
  • (b) 275 MVA
  • (c) 1,429 MVA
  • (d) 381 MVA

Answer: (a) 476 MVA — breaking capacity = √3 × kV × kA = 1.732 × 11 × 25 = 476.3 ≈ 476 MVA.

Q2. What is the breaking capacity of a 33 kV breaker rated at 25 kA?

  • (a) 476 MVA
  • (b) 915 MVA
  • (c) 1,429 MVA
  • (d) 1,800 MVA

Answer: (c) 1,429 MVA — breaking capacity = √3 × 33 × 25 = 1.732 × 825 = 1,428.9 ≈ 1,429 MVA.

Q3. The making capacity of a breaker is about 2.55 times its symmetrical breaking current (peak value). A 25 kA breaker therefore has a making capacity of about:

  • (a) 25 kA
  • (b) 40 kA
  • (c) 64 kA peak
  • (d) 100 kA peak

Answer: (c) 64 kA peak — making capacity = 2.55 × 25 = 63.75 ≈ 64 kA peak.

Q4. An 11 kV breaker rated at 16 kA has a breaking capacity of:

  • (a) 238 MVA
  • (b) 305 MVA
  • (c) 381 MVA
  • (d) 476 MVA

Answer: (b) 305 MVA — breaking capacity = √3 × 11 × 16 = 1.732 × 176 = 304.8 ≈ 305 MVA.

Q5. What does the rated short-time current of a breaker mean?

  • (a) The current it can break instantly
  • (b) The current it can carry for a specified short time (1 s or 3 s) without damage
  • (c) The normal load current
  • (d) The charging current of the line

Answer: (b) The current it can carry for a specified short time (1 s or 3 s) without damage — it proves the breaker can withstand fault current until the protection clears it.

Q6. What is the breaking capacity of a 132 kV breaker rated at 40 kA?

  • (a) 1,800 MVA
  • (b) 3,601 MVA
  • (c) 9,145 MVA
  • (d) 12,000 MVA

Answer: (c) 9,145 MVA — breaking capacity = √3 × 132 × 40 = 1.732 × 5,280 = 9,144.9 ≈ 9,145 MVA.

Q7. A 33 kV breaker with a breaking current of 31.5 kA has a breaking capacity of:

  • (a) 915 MVA
  • (b) 1,429 MVA
  • (c) 1,800 MVA
  • (d) 3,601 MVA

Answer: (c) 1,800 MVA — breaking capacity = √3 × 33 × 31.5 = 1.732 × 1,039.5 = 1,800.4 ≈ 1,800 MVA.

Q8. For an 11 kV system, switchgear is commonly rated at what voltage?

  • (a) 11 kV exactly
  • (b) 12 kV
  • (c) 24 kV
  • (d) 6.6 kV

Answer: (b) 12 kV — the standard rated voltage for an 11 kV system is 12 kV, giving a margin above the nominal system voltage.

Q9. What is the breaking capacity of a 66 kV breaker rated at 31.5 kA?

  • (a) 1,800 MVA
  • (b) 3,601 MVA
  • (c) 9,145 MVA
  • (d) 915 MVA

Answer: (b) 3,601 MVA — breaking capacity = √3 × 66 × 31.5 = 1.732 × 2,079 = 3,600.8 ≈ 3,601 MVA.

Q10. What is the breaking capacity of an 11 kV breaker rated at 20 kA?

  • (a) 305 MVA
  • (b) 381 MVA
  • (c) 476 MVA
  • (d) 238 MVA

Answer: (b) 381 MVA — breaking capacity = √3 × 11 × 20 = 1.732 × 220 = 381.0 ≈ 381 MVA.