Switchgear MCQs — Set 6
10 practice questions on switchgear ratings — breaking capacity in MVA, making capacity, short-time current and rated voltage — with worked calculations.
Q1. A breaker at 11 kV has a symmetrical breaking current of 25 kA. What is its breaking capacity?
- (a) 476 MVA
- (b) 275 MVA
- (c) 1,429 MVA
- (d) 381 MVA
Answer: (a) 476 MVA — breaking capacity = √3 × kV × kA = 1.732 × 11 × 25 = 476.3 ≈ 476 MVA.
Q2. What is the breaking capacity of a 33 kV breaker rated at 25 kA?
- (a) 476 MVA
- (b) 915 MVA
- (c) 1,429 MVA
- (d) 1,800 MVA
Answer: (c) 1,429 MVA — breaking capacity = √3 × 33 × 25 = 1.732 × 825 = 1,428.9 ≈ 1,429 MVA.
Q3. The making capacity of a breaker is about 2.55 times its symmetrical breaking current (peak value). A 25 kA breaker therefore has a making capacity of about:
- (a) 25 kA
- (b) 40 kA
- (c) 64 kA peak
- (d) 100 kA peak
Answer: (c) 64 kA peak — making capacity = 2.55 × 25 = 63.75 ≈ 64 kA peak.
Q4. An 11 kV breaker rated at 16 kA has a breaking capacity of:
- (a) 238 MVA
- (b) 305 MVA
- (c) 381 MVA
- (d) 476 MVA
Answer: (b) 305 MVA — breaking capacity = √3 × 11 × 16 = 1.732 × 176 = 304.8 ≈ 305 MVA.
Q5. What does the rated short-time current of a breaker mean?
- (a) The current it can break instantly
- (b) The current it can carry for a specified short time (1 s or 3 s) without damage
- (c) The normal load current
- (d) The charging current of the line
Answer: (b) The current it can carry for a specified short time (1 s or 3 s) without damage — it proves the breaker can withstand fault current until the protection clears it.
Q6. What is the breaking capacity of a 132 kV breaker rated at 40 kA?
- (a) 1,800 MVA
- (b) 3,601 MVA
- (c) 9,145 MVA
- (d) 12,000 MVA
Answer: (c) 9,145 MVA — breaking capacity = √3 × 132 × 40 = 1.732 × 5,280 = 9,144.9 ≈ 9,145 MVA.
Q7. A 33 kV breaker with a breaking current of 31.5 kA has a breaking capacity of:
- (a) 915 MVA
- (b) 1,429 MVA
- (c) 1,800 MVA
- (d) 3,601 MVA
Answer: (c) 1,800 MVA — breaking capacity = √3 × 33 × 31.5 = 1.732 × 1,039.5 = 1,800.4 ≈ 1,800 MVA.
Q8. For an 11 kV system, switchgear is commonly rated at what voltage?
- (a) 11 kV exactly
- (b) 12 kV
- (c) 24 kV
- (d) 6.6 kV
Answer: (b) 12 kV — the standard rated voltage for an 11 kV system is 12 kV, giving a margin above the nominal system voltage.
Q9. What is the breaking capacity of a 66 kV breaker rated at 31.5 kA?
- (a) 1,800 MVA
- (b) 3,601 MVA
- (c) 9,145 MVA
- (d) 915 MVA
Answer: (b) 3,601 MVA — breaking capacity = √3 × 66 × 31.5 = 1.732 × 2,079 = 3,600.8 ≈ 3,601 MVA.
Q10. What is the breaking capacity of an 11 kV breaker rated at 20 kA?
- (a) 305 MVA
- (b) 381 MVA
- (c) 476 MVA
- (d) 238 MVA
Answer: (b) 381 MVA — breaking capacity = √3 × 11 × 20 = 1.732 × 220 = 381.0 ≈ 381 MVA.