Switchgear MCQs — Set 3

10 practice questions on isolators, disconnectors and earthing switches — the devices that make switchgear safe to work on, with answers and explanations.

Q1. An isolator (disconnector) must be operated only when the circuit is:

  • (a) Carrying full load
  • (b) On no load — the circuit is dead
  • (c) Short-circuited
  • (d) Earthed through a resistor

Answer: (b) On no load — the circuit is dead — an isolator has no arc-quenching device, so it must never break load current.

Q2. Why must an isolator never be opened on load?

  • (a) It would trip the relay
  • (b) It has no arc-quenching device, so a dangerous sustained arc would form
  • (c) It would overheat the busbar
  • (d) It would damage the CT

Answer: (b) It has no arc-quenching device, so a dangerous sustained arc would form — the arc can flash over to the operator or nearby phases.

Q3. What is the purpose of an earthing switch?

  • (a) To carry load current
  • (b) To connect a de-energised part to earth for safety during maintenance
  • (c) To increase the fault current
  • (d) To measure earth resistance

Answer: (b) To connect a de-energised part to earth for safety during maintenance — it discharges trapped charge and protects against accidental re-energisation.

Q4. What is the correct sequence to isolate a circuit for maintenance?

  • (a) Open the isolator, then open the breaker
  • (b) Open the breaker first, then open the isolator
  • (c) Close the earthing switch, then open the breaker
  • (d) Open the isolator, then close the earthing switch

Answer: (b) Open the breaker first, then open the isolator — the breaker interrupts the current, and the isolator then gives the visible break.

Q5. The main safety feature an isolator provides is:

  • (a) Fault-current interruption
  • (b) A visible break in the circuit
  • (c) Overcurrent protection
  • (d) Voltage regulation

Answer: (b) A visible break in the circuit — a worker can see with their own eyes that the circuit is disconnected.

Q6. Which isolator design is commonly used at 132 kV outdoor substations?

  • (a) Plug-in MCB
  • (b) Centre-break or vertical-break isolator
  • (c) Rotary drum switch
  • (d) Knife switch in a domestic board

Answer: (b) Centre-break or vertical-break isolator — these designs give the large clearances needed at 132 kV.

Q7. What is a load-break switch?

  • (a) A switch that can make and break load current but not fault current
  • (b) A switch that trips only on short circuits
  • (c) A switch with no moving parts
  • (d) A fuse combined with a relay

Answer: (a) A switch that can make and break load current but not fault current — it sits between an isolator and a circuit breaker in capability.

Q8. When is an earthing switch closed?

  • (a) Before the breaker is opened
  • (b) After the circuit is isolated and proved dead
  • (c) While the circuit is carrying load
  • (d) Only during a fault

Answer: (b) After the circuit is isolated and proved dead — closing it onto a live circuit would cause a short circuit.

Q9. Isolators are rated by voltage and continuous current, but NOT by:

  • (a) Rated voltage
  • (b) Breaking capacity
  • (c) Continuous current
  • (d) Insulation level

Answer: (b) Breaking capacity — isolators are not designed to break current, so they have no breaking capacity rating.

Q10. What does the mechanical interlock between a circuit breaker and its isolator prevent?

  • (a) The breaker from closing
  • (b) Opening the isolator while the breaker is still closed (on load)
  • (c) The relay from operating
  • (d) The busbar from overheating

Answer: (b) Opening the isolator while the breaker is still closed (on load) — the interlock forces the correct operating sequence.