Switchgear MCQs — Set 3
10 practice questions on isolators, disconnectors and earthing switches — the devices that make switchgear safe to work on, with answers and explanations.
Q1. An isolator (disconnector) must be operated only when the circuit is:
- (a) Carrying full load
- (b) On no load — the circuit is dead
- (c) Short-circuited
- (d) Earthed through a resistor
Answer: (b) On no load — the circuit is dead — an isolator has no arc-quenching device, so it must never break load current.
Q2. Why must an isolator never be opened on load?
- (a) It would trip the relay
- (b) It has no arc-quenching device, so a dangerous sustained arc would form
- (c) It would overheat the busbar
- (d) It would damage the CT
Answer: (b) It has no arc-quenching device, so a dangerous sustained arc would form — the arc can flash over to the operator or nearby phases.
Q3. What is the purpose of an earthing switch?
- (a) To carry load current
- (b) To connect a de-energised part to earth for safety during maintenance
- (c) To increase the fault current
- (d) To measure earth resistance
Answer: (b) To connect a de-energised part to earth for safety during maintenance — it discharges trapped charge and protects against accidental re-energisation.
Q4. What is the correct sequence to isolate a circuit for maintenance?
- (a) Open the isolator, then open the breaker
- (b) Open the breaker first, then open the isolator
- (c) Close the earthing switch, then open the breaker
- (d) Open the isolator, then close the earthing switch
Answer: (b) Open the breaker first, then open the isolator — the breaker interrupts the current, and the isolator then gives the visible break.
Q5. The main safety feature an isolator provides is:
- (a) Fault-current interruption
- (b) A visible break in the circuit
- (c) Overcurrent protection
- (d) Voltage regulation
Answer: (b) A visible break in the circuit — a worker can see with their own eyes that the circuit is disconnected.
Q6. Which isolator design is commonly used at 132 kV outdoor substations?
- (a) Plug-in MCB
- (b) Centre-break or vertical-break isolator
- (c) Rotary drum switch
- (d) Knife switch in a domestic board
Answer: (b) Centre-break or vertical-break isolator — these designs give the large clearances needed at 132 kV.
Q7. What is a load-break switch?
- (a) A switch that can make and break load current but not fault current
- (b) A switch that trips only on short circuits
- (c) A switch with no moving parts
- (d) A fuse combined with a relay
Answer: (a) A switch that can make and break load current but not fault current — it sits between an isolator and a circuit breaker in capability.
Q8. When is an earthing switch closed?
- (a) Before the breaker is opened
- (b) After the circuit is isolated and proved dead
- (c) While the circuit is carrying load
- (d) Only during a fault
Answer: (b) After the circuit is isolated and proved dead — closing it onto a live circuit would cause a short circuit.
Q9. Isolators are rated by voltage and continuous current, but NOT by:
- (a) Rated voltage
- (b) Breaking capacity
- (c) Continuous current
- (d) Insulation level
Answer: (b) Breaking capacity — isolators are not designed to break current, so they have no breaking capacity rating.
Q10. What does the mechanical interlock between a circuit breaker and its isolator prevent?
- (a) The breaker from closing
- (b) Opening the isolator while the breaker is still closed (on load)
- (c) The relay from operating
- (d) The busbar from overheating
Answer: (b) Opening the isolator while the breaker is still closed (on load) — the interlock forces the correct operating sequence.