Surge Protection MCQs — Set 9
10 worked numerical questions on SPD ratings and protected loads — Imax, Uc headroom, Up and P = V × I — with every calculation shown.
Q1. A Type 2 SPD has In = 20 kA and Imax = 40 kA. A surge of 30 kA (8/20 µs) arrives. What does this mean?
- (a) The surge is above In but below Imax, so the SPD can handle it as a single event
- (b) The SPD cannot handle it because it exceeds In
- (c) The SPD will handle it repeatedly without any wear
- (d) The surge current is too small for the SPD to notice
Answer: (a) The surge is above In but below Imax, so the SPD can handle it as a single event — 20 kA < 30 kA < 40 kA, so it is within the maximum rating but beyond the nominal rating.
Q2. What is the difference between Imax = 40 kA and In = 20 kA for a Type 2 SPD?
- (a) 20 kA
- (b) 60 kA
- (c) 2 kA
- (d) 800 kA
Answer: (a) 20 kA — 40 − 20 = 20 kA separates the maximum single-event rating from the nominal rating.
Q3. A Type 1 SPD has Iimp = 25 kA per pole. How much larger is this than a Type 2 SPD’s In of 20 kA?
- (a) 5 kA larger
- (b) 45 kA larger
- (c) 500 kA larger
- (d) It is smaller, not larger
Answer: (a) 5 kA larger — 25 − 20 = 5 kA, and note the two ratings use different waveforms (10/350 µs versus 8/20 µs), so they are not directly interchangeable.
Q4. The Uc of an SPD is 275 V on a 230 V system. What percentage is Uc above the nominal voltage?
- (a) About 20%
- (b) About 2%
- (c) About 45%
- (d) About 120%
Answer: (a) About 20% — the margin is 275 − 230 = 45 V, and 45 ÷ 230 × 100 ≈ 19.6%, about 20%.
Q5. A Type 2 SPD has Up below 1.5 kV on a 230 V system. How many times the nominal voltage is 1.5 kV?
- (a) About 6.5 times
- (b) About 1.5 times
- (c) About 15 times
- (d) About 230 times
Answer: (a) About 6.5 times — 1,500 ÷ 230 ≈ 6.5, so even a well-clamped surge still lets through several times the normal voltage, which equipment insulation must withstand.
Q6. A protected load draws 10 A from a 230 V supply. What power does it consume?
- (a) 2,300 W
- (b) 230 W
- (c) 23 W
- (d) 23,000 W
Answer: (a) 2,300 W — P = V × I = 230 × 10 = 2,300 W.
Q7. A 20 A, 120 V circuit is protected by an SPD. Using the 80% continuous-load rule, what is the maximum safe continuous power?
- (a) 1,920 W
- (b) 2,400 W
- (c) 120 W
- (d) 9,600 W
Answer: (a) 1,920 W — full rating is 120 × 20 = 2,400 W, and 80% of 2,400 = 1,920 W for continuous loads.
Q8. A load draws 20 A from a 230 V supply. What power does it consume?
- (a) 4,600 W
- (b) 460 W
- (c) 11.5 W
- (d) 46,000 W
Answer: (a) 4,600 W — P = V × I = 230 × 20 = 4,600 W.
Q9. Two identical Type 2 SPDs are compared: one has Up = 1.5 kV and the other Up = 1.2 kV. How much lower is the better Up?
- (a) 0.3 kV (300 V) lower
- (b) 2.7 kV lower
- (c) 1.5 kV lower
- (d) They are the same
Answer: (a) 0.3 kV (300 V) lower — 1.5 − 1.2 = 0.3 kV, so the 1.2 kV SPD lets 300 V less through to the equipment.
Q10. A surge of 5 kA (8/20 µs) hits a Type 2 SPD rated In = 20 kA. What fraction of In is this surge?
- (a) One quarter (25%) of In
- (b) Twice In
- (c) Four times In
- (d) Equal to Imax
Answer: (a) One quarter (25%) of In — 5 ÷ 20 = 0.25, so the surge is well inside the SPD’s nominal capability.