Surge Protection MCQs — Set 6
10 practice questions on coordinating Type 1, 2 and 3 SPDs and installing them correctly — location, wiring and lead length.
Q1. What does coordination between SPD types mean?
- (a) Each SPD type takes its share of the surge energy in turn, so no single device is overwhelmed
- (b) All SPDs trip the MCB at the same time
- (c) All SPDs are set to the same Uc value
- (d) The SPDs take turns supplying power to the load
Answer: (a) Each SPD type takes its share of the surge energy in turn, so no single device is overwhelmed — Type 1 takes the bulk lightning energy, Type 2 the remainder, and Type 3 the fine residual.
Q2. In a staged system, in which order does a surge meet the SPD types as it travels into the building?
- (a) Type 1 first, then Type 2, then Type 3 at the equipment
- (b) Type 3 first, then Type 2, then Type 1
- (c) Type 2 first, then Type 1, then Type 3
- (d) All three at exactly the same point
Answer: (a) Type 1 first, then Type 2, then Type 3 at the equipment — the stages are arranged from the service entrance toward the load, each reducing the surge further.
Q3. Why is adequate separation or a decoupling element needed between a Type 1 and a Type 2 SPD?
- (a) So the Type 1 SPD fires first and the Type 2 SPD only sees the reduced residual surge
- (b) So the two SPDs never operate at the same time of day
- (c) So the cable between them can act as a heater
- (d) So the Type 2 SPD can supply power to the Type 1 SPD
Answer: (a) So the Type 1 SPD fires first and the Type 2 SPD only sees the reduced residual surge — without separation the faster Type 2 could try to take the whole lightning current.
Q4. Why must the connecting leads of an SPD be kept as short as possible?
- (a) Long leads add inductance, which raises the voltage that reaches the protected equipment during a surge
- (b) Long leads make the SPD look untidy
- (c) Long leads reduce the supply voltage at normal times
- (d) Long leads prevent the MCB from tripping
Answer: (a) Long leads add inductance, which raises the voltage that reaches the protected equipment during a surge — every extra centimetre of lead worsens the effective Up.
Q5. Which wiring arrangement gives the lowest let-through voltage for an SPD?
- (a) Short, straight leads with no sharp bends or loops
- (b) Long leads coiled into loops inside the board
- (c) Leads routed around the outside of the board
- (d) Leads joined with many terminal blocks in series
Answer: (a) Short, straight leads with no sharp bends or loops — straight, short conductors have the least inductance and the lowest voltage drop during the fast surge.
Q6. How is an SPD normally connected into a circuit?
- (a) In parallel (shunt) across the supply, between line and earth, so the load current does not pass through it
- (b) In series with the load, so all load current passes through it
- (c) In place of the main switch
- (d) Across the MCB contacts only
Answer: (a) In parallel (shunt) across the supply, between line and earth, so the load current does not pass through it — the SPD sits idle until a surge makes it conduct.
Q7. Between which conductors must an SPD provide protection in a single-phase 230 V system?
- (a) Line to neutral and line to earth (and neutral to earth where required)
- (b) Line to line only, because there is only one phase
- (c) Earth to the metal enclosure only
- (d) Neutral to the water pipe only
Answer: (a) Line to neutral and line to earth (and neutral to earth where required) — surges can appear in any mode, so all paths to the equipment need clamping.
Q8. Why is a good, low-impedance earth connection essential for an SPD?
- (a) The surge current must flow to earth quickly; a poor earth forces the voltage at the equipment to rise
- (b) The SPD draws its operating power from the earth
- (c) A poor earth makes the SPD conduct at normal voltage
- (d) The earth connection is only decorative
Answer: (a) The surge current must flow to earth quickly; a poor earth forces the voltage at the equipment to rise — the SPD can only clamp as well as its earth path allows.
Q9. Where should a whole-house Type 2 SPD be fitted for the best protection of all circuits?
- (a) In the main distribution board, protecting the whole installation from one point
- (b) On one socket circuit only
- (c) Inside the most expensive appliance
- (d) On the roof
Answer: (a) In the main distribution board, protecting the whole installation from one point — one SPD at the board guards every circuit downstream of it.
Q10. Why is a Type 3 SPD at a socket not enough on its own for a whole house?
- (a) It is designed only for small residual surges at one piece of equipment, not for the full surge entering the building
- (b) It cannot be plugged into a socket
- (c) It protects only the lighting circuits
- (d) It works only when the Type 1 SPD is switched off
Answer: (a) It is designed only for small residual surges at one piece of equipment, not for the full surge entering the building — without upstream Type 1/2 stages, a large surge would overwhelm it.