Surge Protection MCQs — Set 6

10 practice questions on coordinating Type 1, 2 and 3 SPDs and installing them correctly — location, wiring and lead length.

Q1. What does coordination between SPD types mean?

  • (a) Each SPD type takes its share of the surge energy in turn, so no single device is overwhelmed
  • (b) All SPDs trip the MCB at the same time
  • (c) All SPDs are set to the same Uc value
  • (d) The SPDs take turns supplying power to the load

Answer: (a) Each SPD type takes its share of the surge energy in turn, so no single device is overwhelmed — Type 1 takes the bulk lightning energy, Type 2 the remainder, and Type 3 the fine residual.

Q2. In a staged system, in which order does a surge meet the SPD types as it travels into the building?

  • (a) Type 1 first, then Type 2, then Type 3 at the equipment
  • (b) Type 3 first, then Type 2, then Type 1
  • (c) Type 2 first, then Type 1, then Type 3
  • (d) All three at exactly the same point

Answer: (a) Type 1 first, then Type 2, then Type 3 at the equipment — the stages are arranged from the service entrance toward the load, each reducing the surge further.

Q3. Why is adequate separation or a decoupling element needed between a Type 1 and a Type 2 SPD?

  • (a) So the Type 1 SPD fires first and the Type 2 SPD only sees the reduced residual surge
  • (b) So the two SPDs never operate at the same time of day
  • (c) So the cable between them can act as a heater
  • (d) So the Type 2 SPD can supply power to the Type 1 SPD

Answer: (a) So the Type 1 SPD fires first and the Type 2 SPD only sees the reduced residual surge — without separation the faster Type 2 could try to take the whole lightning current.

Q4. Why must the connecting leads of an SPD be kept as short as possible?

  • (a) Long leads add inductance, which raises the voltage that reaches the protected equipment during a surge
  • (b) Long leads make the SPD look untidy
  • (c) Long leads reduce the supply voltage at normal times
  • (d) Long leads prevent the MCB from tripping

Answer: (a) Long leads add inductance, which raises the voltage that reaches the protected equipment during a surge — every extra centimetre of lead worsens the effective Up.

Q5. Which wiring arrangement gives the lowest let-through voltage for an SPD?

  • (a) Short, straight leads with no sharp bends or loops
  • (b) Long leads coiled into loops inside the board
  • (c) Leads routed around the outside of the board
  • (d) Leads joined with many terminal blocks in series

Answer: (a) Short, straight leads with no sharp bends or loops — straight, short conductors have the least inductance and the lowest voltage drop during the fast surge.

Q6. How is an SPD normally connected into a circuit?

  • (a) In parallel (shunt) across the supply, between line and earth, so the load current does not pass through it
  • (b) In series with the load, so all load current passes through it
  • (c) In place of the main switch
  • (d) Across the MCB contacts only

Answer: (a) In parallel (shunt) across the supply, between line and earth, so the load current does not pass through it — the SPD sits idle until a surge makes it conduct.

Q7. Between which conductors must an SPD provide protection in a single-phase 230 V system?

  • (a) Line to neutral and line to earth (and neutral to earth where required)
  • (b) Line to line only, because there is only one phase
  • (c) Earth to the metal enclosure only
  • (d) Neutral to the water pipe only

Answer: (a) Line to neutral and line to earth (and neutral to earth where required) — surges can appear in any mode, so all paths to the equipment need clamping.

Q8. Why is a good, low-impedance earth connection essential for an SPD?

  • (a) The surge current must flow to earth quickly; a poor earth forces the voltage at the equipment to rise
  • (b) The SPD draws its operating power from the earth
  • (c) A poor earth makes the SPD conduct at normal voltage
  • (d) The earth connection is only decorative

Answer: (a) The surge current must flow to earth quickly; a poor earth forces the voltage at the equipment to rise — the SPD can only clamp as well as its earth path allows.

Q9. Where should a whole-house Type 2 SPD be fitted for the best protection of all circuits?

  • (a) In the main distribution board, protecting the whole installation from one point
  • (b) On one socket circuit only
  • (c) Inside the most expensive appliance
  • (d) On the roof

Answer: (a) In the main distribution board, protecting the whole installation from one point — one SPD at the board guards every circuit downstream of it.

Q10. Why is a Type 3 SPD at a socket not enough on its own for a whole house?

  • (a) It is designed only for small residual surges at one piece of equipment, not for the full surge entering the building
  • (b) It cannot be plugged into a socket
  • (c) It protects only the lighting circuits
  • (d) It works only when the Type 1 SPD is switched off

Answer: (a) It is designed only for small residual surges at one piece of equipment, not for the full surge entering the building — without upstream Type 1/2 stages, a large surge would overwhelm it.