Surge Protection MCQs — Set 5

10 practice questions on SPD current ratings — In, Imax and Iimp — and the 8/20 µs and 10/350 µs waveforms they are tested with.

Q1. What does In mean on an SPD rating plate?

  • (a) Nominal discharge current — the 8/20 µs surge current the SPD is designed to handle repeatedly
  • (b) The normal load current of the circuit
  • (c) The current drawn by the SPD at normal voltage
  • (d) The tripping current of the MCB

Answer: (a) Nominal discharge current — the 8/20 µs surge current the SPD is designed to handle repeatedly — for a common Type 2 SPD, In is 20 kA.

Q2. What does Imax mean on an SPD rating plate?

  • (a) Maximum discharge current — the largest 8/20 µs surge current the SPD can handle in a single event
  • (b) The maximum load current the circuit can supply
  • (c) The short-circuit current of the supply
  • (d) The current at which the SPD becomes a battery

Answer: (a) Maximum discharge current — the largest 8/20 µs surge current the SPD can handle in a single event — for a common Type 2 SPD, Imax is 40 kA.

Q3. A Type 2 SPD is rated In = 20 kA and Imax = 40 kA. How many times larger is Imax than In?

  • (a) 2 times
  • (b) 4 times
  • (c) 10 times
  • (d) 20 times

Answer: (a) 2 times — 40 ÷ 20 = 2, so the maximum discharge current is twice the nominal discharge current.

Q4. What does Iimp mean on a Type 1 SPD rating plate?

  • (a) Impulse current — the 10/350 µs lightning current the SPD can divert, typically 25 kA per pole
  • (b) The impulse voltage of the supply
  • (c) The current consumed by the SPD indicator lamp
  • (d) The input current of the protected load

Answer: (a) Impulse current — the 10/350 µs lightning current the SPD can divert, typically 25 kA per pole — Iimp is the defining rating of a Type 1 SPD.

Q5. What does the “8/20 µs” waveform description mean?

  • (a) The surge current rises to its peak in 8 µs and falls to half its peak in 20 µs
  • (b) The surge lasts exactly 8 seconds and repeats every 20 seconds
  • (c) The SPD carries 8 kA for 20 hours
  • (d) The supply voltage is 8 V for 20 µs

Answer: (a) The surge current rises to its peak in 8 µs and falls to half its peak in 20 µs — the two numbers describe the shape of an induced surge.

Q6. What does the “10/350 µs” waveform description mean?

  • (a) The lightning current rises to its peak in 10 µs and falls to half its peak in 350 µs
  • (b) The lightning current lasts 10 seconds and repeats after 350 seconds
  • (c) The SPD carries 10 kA for 350 hours
  • (d) The supply voltage is 10 V for 350 µs

Answer: (a) The lightning current rises to its peak in 10 µs and falls to half its peak in 350 µs — the long tail carries far more energy than the 8/20 µs wave.

Q7. Why does the 10/350 µs lightning wave carry much more energy than an 8/20 µs wave of the same peak current?

  • (a) Because its current flows for a much longer time, so the total charge and energy are far greater
  • (b) Because its peak voltage is lower
  • (c) Because it travels through air instead of cable
  • (d) Because it has a higher frequency

Answer: (a) Because its current flows for a much longer time, so the total charge and energy are far greater — energy depends on current over time, not just on the peak.

Q8. A surge of 10 kA (8/20 µs) hits a Type 2 SPD rated In = 20 kA, Imax = 40 kA. What should happen?

  • (a) The SPD diverts it comfortably, since 10 kA is below its 20 kA nominal rating
  • (b) The SPD explodes immediately
  • (c) The SPD cannot divert any current below Imax
  • (d) The MCB trips before the SPD can act

Answer: (a) The SPD diverts it comfortably, since 10 kA is below its 20 kA nominal rating — 10 kA is half of In, well within the SPD’s designed capability.

Q9. A single surge of 40 kA (8/20 µs) hits the same SPD (In = 20 kA, Imax = 40 kA). What does the rating say?

  • (a) The SPD can handle it once, because 40 kA equals its Imax — but it is at its maximum limit
  • (b) The SPD cannot handle it at all, because it exceeds In
  • (c) The SPD will handle it repeatedly forever
  • (d) The SPD will turn the surge into useful power

Answer: (a) The SPD can handle it once, because 40 kA equals its Imax — but it is at its maximum limit — Imax is a single-event maximum, not a rating for repeated surges.

Q10. Which SPD rating tells you whether it can survive a direct lightning strike at the service entrance?

  • (a) Iimp, the 10/350 µs impulse current rating of a Type 1 SPD
  • (b) In, the 8/20 µs nominal discharge current of a Type 2 SPD
  • (c) The Uc of a Type 3 SPD
  • (d) The tripping current of the RCCB

Answer: (a) Iimp, the 10/350 µs impulse current rating of a Type 1 SPD — only Iimp describes the high-energy lightning current a service-entrance SPD must divert.