Surge Protection MCQs — Set 4
10 practice questions on the two key voltage ratings of an SPD — Uc, the maximum continuous operating voltage, and Up, the voltage protection level.
Q1. What does Uc mean on an SPD rating plate?
- (a) Maximum continuous operating voltage the SPD can withstand indefinitely
- (b) The voltage at which the SPD explodes
- (c) The surge current the SPD can carry
- (d) The voltage of the protected load
Answer: (a) Maximum continuous operating voltage the SPD can withstand indefinitely — the SPD must tolerate this voltage continuously without conducting or overheating.
Q2. For a 230 V AC supply, a common Uc rating for a Type 2 SPD is 275 V. Why is Uc set above the nominal 230 V?
- (a) So the SPD does not conduct during normal voltage variations above 230 V
- (b) So the SPD conducts continuously at normal voltage
- (c) So the SPD can supply 275 V to the load
- (d) So the SPD trips the MCB at 230 V
Answer: (a) So the SPD does not conduct during normal voltage variations above 230 V — the margin keeps the MOV in its high-resistance state during ordinary supply swings.
Q3. How much higher is a Uc of 275 V than the nominal 230 V supply?
- (a) 45 V
- (b) 5 V
- (c) 230 V
- (d) 505 V
Answer: (a) 45 V — 275 − 230 = 45 V of headroom above the nominal supply voltage.
Q4. What happens if an SPD with too low a Uc is installed on a 230 V system?
- (a) It may conduct at normal supply voltage, overheat, and fail early
- (b) It will protect the equipment better than any other SPD
- (c) Nothing at all will happen
- (d) It will increase the supply voltage to 275 V
Answer: (a) It may conduct at normal supply voltage, overheat, and fail early — with no margin above the supply, ordinary voltage rises push the MOV into conduction.
Q5. What does Up mean on an SPD rating plate?
- (a) Voltage protection level — the maximum voltage the protected equipment will see during a surge
- (b) The supply voltage upstream of the SPD
- (c) The current the SPD can carry
- (d) The power consumed by the SPD
Answer: (a) Voltage protection level — the maximum voltage the protected equipment will see during a surge — Up is the residual (let-through) voltage after the SPD clamps.
Q6. For a 230 V system, a typical Type 2 SPD has a Up below 1.5 kV. What does this tell the user?
- (a) During a surge, the voltage reaching the equipment is limited to under 1,500 V
- (b) The SPD can only be used on supplies below 1.5 V
- (c) The SPD itself is rated at 1.5 kV continuous supply
- (d) The SPD trips at 1.5 kV of current
Answer: (a) During a surge, the voltage reaching the equipment is limited to under 1,500 V — Up is the clamped voltage the downstream equipment must survive.
Q7. When comparing two SPDs for the same 230 V circuit, which Up gives better protection?
- (a) The lower Up, because less voltage reaches the protected equipment
- (b) The higher Up, because more voltage reaches the equipment
- (c) Up makes no difference to protection
- (d) The Up that equals the supply voltage exactly
Answer: (a) The lower Up, because less voltage reaches the protected equipment — a lower let-through voltage means less stress on insulation and electronics.
Q8. Up is measured while the SPD carries its nominal discharge current. Why is that test condition important?
- (a) The clamping voltage rises with current, so Up must be quoted at a defined current to be comparable
- (b) The SPD only works when no current flows
- (c) Current has no effect on voltage in an SPD
- (d) It proves the SPD can act as a battery
Answer: (a) The clamping voltage rises with current, so Up must be quoted at a defined current to be comparable — an Up value without its test current would be meaningless.
Q9. Why must the SPD’s Up be lower than the impulse withstand voltage of the equipment it protects?
- (a) Otherwise the equipment would still see a voltage above what its insulation can survive
- (b) Otherwise the SPD would draw too much current at normal voltage
- (c) Otherwise the MCB would trip on every surge
- (d) Otherwise the supply frequency would change
Answer: (a) Otherwise the equipment would still see a voltage above what its insulation can survive — protection only works if the clamped voltage stays below the equipment’s withstand limit.
Q10. A 230 V circuit needs an SPD. Which Uc choice is correct?
- (a) Uc of 275 V, comfortably above the 230 V nominal supply
- (b) Uc of 150 V, well below the 230 V nominal supply
- (c) Uc of 12 V, like a car battery
- (d) Uc does not matter at all for a 230 V circuit
Answer: (a) Uc of 275 V, comfortably above the 230 V nominal supply — Uc must always exceed the highest continuous voltage the system can present.