Surge Protection MCQs — Set 2

10 practice questions on SPD Types 1, 2 and 3 — where each type is installed and what kind of surge it is built to handle.

Q1. What is a surge protective device (SPD)?

  • (a) A device that limits transient overvoltages by diverting surge current to earth
  • (b) A device that increases the supply voltage during a surge
  • (c) A device that disconnects the supply when the frequency changes
  • (d) A device that stores surge energy in a battery

Answer: (a) A device that limits transient overvoltages by diverting surge current to earth — the SPD clamps the voltage by giving the surge current a low-impedance path to earth.

Q2. Where is a Type 1 SPD normally installed?

  • (a) At the main incoming supply / service entrance of the building
  • (b) Inside a television set
  • (c) At the far end of a garden lighting circuit
  • (d) Inside a plug top

Answer: (a) At the main incoming supply / service entrance of the building — Type 1 is the first line of defence against direct lightning current entering the installation.

Q3. Where is a Type 2 SPD normally installed?

  • (a) In the main distribution board, downstream of the Type 1 SPD
  • (b) On the roof next to the lightning rod
  • (c) Inside the electricity meter only
  • (d) On the outside of the building wall

Answer: (a) In the main distribution board, downstream of the Type 1 SPD — Type 2 protects the installation against indirect lightning and switching surges.

Q4. Where is a Type 3 SPD normally installed?

  • (a) Close to the sensitive equipment it protects, for example at a socket outlet
  • (b) At the power station supplying the area
  • (c) On the high-voltage transmission tower
  • (d) In the street distribution pillar only

Answer: (a) Close to the sensitive equipment it protects, for example at a socket outlet — Type 3 gives fine, final-stage protection right at the load.

Q5. Which current waveform is a Type 1 SPD tested with?

  • (a) The 10/350 µs lightning-current waveform
  • (b) The 8/20 µs induced-surge waveform
  • (c) A 50 Hz sine wave
  • (d) A pure DC current

Answer: (a) The 10/350 µs lightning-current waveform — the long 350 µs tail represents the large energy of a direct lightning strike.

Q6. Which current waveform is a Type 2 SPD tested with?

  • (a) The 8/20 µs waveform
  • (b) The 10/350 µs waveform
  • (c) A 1/50 µs waveform
  • (d) A square wave

Answer: (a) The 8/20 µs waveform — Type 2 SPDs are rated against shorter, induced surges and switching transients.

Q7. What is the main job of a Type 3 SPD compared with a Type 1 SPD?

  • (a) Type 3 provides a low voltage protection level close to the equipment; Type 1 handles large lightning currents at the entrance
  • (b) Type 3 handles larger currents than Type 1
  • (c) Type 3 is installed before Type 1 in the supply path
  • (d) Type 3 replaces the main switch of the building

Answer: (a) Type 3 provides a low voltage protection level close to the equipment; Type 1 handles large lightning currents at the entrance — each type has a different role in the staged system.

Q8. What is a combined Type 1+2 SPD?

  • (a) A single device that meets both the Type 1 lightning-current test and the Type 2 induced-surge test
  • (b) Two Type 3 SPDs wired in series
  • (c) A Type 1 SPD with a built-in MCB only
  • (d) An SPD that works only on DC supplies

Answer: (a) A single device that meets both the Type 1 lightning-current test and the Type 2 induced-surge test — it saves space in the distribution board while covering both jobs.

Q9. In a building with an external lightning protection system, which SPD type is needed at the service entrance?

  • (a) Type 1, because part of the direct lightning current can enter through the supply
  • (b) Type 3 only, because the lightning rod takes all the current
  • (c) No SPD at all, because the lightning rod protects everything
  • (d) A fuse, because fuses stop lightning

Answer: (a) Type 1, because part of the direct lightning current can enter through the supply — a lightning rod alone does not stop surges travelling in on the mains conductors.

Q10. Why can a Type 2 SPD not simply replace a Type 1 SPD at the service entrance of a lightning-exposed building?

  • (a) A Type 2 SPD is not designed for the high-energy 10/350 µs direct lightning current
  • (b) A Type 2 SPD is physically too large to fit at the entrance
  • (c) A Type 2 SPD only works on three-phase supplies
  • (d) A Type 2 SPD needs a battery to operate

Answer: (a) A Type 2 SPD is not designed for the high-energy 10/350 µs direct lightning current — it would be overwhelmed by the energy of a direct strike, so Type 1 must take that first.

Also read: AFCI Breaker Keeps Tripping | All MCQ Topics