Single-Phase Motor MCQs — Set 8
10 practice questions on single-phase motor faults and troubleshooting — humming, failure to start, overheating and tripping — with answers and explanations.
Q1. A capacitor-start motor only hums when switched on and does not rotate. What is the most likely cause?
- (a) The main winding is burnt out
- (b) The starting capacitor has failed open, so there is no starting torque
- (c) The rotor is running too fast
- (d) The supply frequency is too high
Answer: (b) The starting capacitor has failed open, so there is no starting torque — the motor hums on the pulsating field but cannot start; a push may get it going.
Q2. A single-phase motor starts normally but trips its overload protector after a few minutes of running. What is the most likely cause?
- (a) The motor is overloaded or the bearings are stiff, so it draws excess current
- (b) The run capacitor is too large
- (c) The supply voltage is too high
- (d) The centrifugal switch opened too early
Answer: (a) The motor is overloaded or the bearings are stiff, so it draws excess current — sustained overcurrent heats the windings and trips the overload device.
Q3. What does a burnt smell and darkened varnish on a single-phase motor’s windings indicate?
- (a) Normal operation
- (b) The windings have overheated, possibly from overload, a stalled rotor or a failed starting winding cut-out
- (c) The capacitor is charging
- (d) The motor is running at synchronous speed
Answer: (b) The windings have overheated, possibly from overload, a stalled rotor or a failed starting winding cut-out — insulation damage from overheating is a common cause of motor failure.
Q4. A split-phase motor runs in the wrong direction after rewinding. What is the most likely wiring error?
- (a) The capacitor value is too small
- (b) One winding was connected reversed relative to the other
- (c) The supply neutral and earth were swapped
- (d) The rotor was fitted backwards
Answer: (b) One winding was connected reversed relative to the other — reversing one winding reverses the phase sequence and therefore the direction of rotation.
Q5. A single-phase motor vibrates badly and makes a loud humming noise while running. Which check should come first?
- (a) Check the capacitor value
- (b) Check that the motor is firmly mounted, the shaft is not bent and the bearings are not worn
- (c) Increase the supply voltage
- (d) Fit a larger centrifugal switch
Answer: (b) Check that the motor is firmly mounted, the shaft is not bent and the bearings are not worn — mechanical imbalance and worn bearings are the usual causes of vibration and noise.
Q6. If a single-phase induction motor is stalled (rotor locked) for a long time, what will happen?
- (a) Nothing — it will simply wait
- (b) It will draw locked-rotor current continuously, overheat and can burn out
- (c) It will automatically reverse
- (d) Its speed will rise to synchronous speed
Answer: (b) It will draw locked-rotor current continuously, overheat and can burn out — at standstill the current is 5 to 7 times full-load current, so a stall must be cleared quickly.
Q7. A motor keeps blowing its supply fuse the moment it is switched on. Which fault is most likely?
- (a) A short circuit in a winding or a shorted capacitor
- (b) A worn bearing
- (c) A loose mounting bolt
- (d) A dusty fan cover
Answer: (a) A short circuit in a winding or a shorted capacitor — a short draws a very large current that blows the fuse instantly.
Q8. What is the synchronous speed of a 6-pole single-phase motor on a 60 Hz supply?
- (a) 1,000 rpm
- (b) 1,200 rpm
- (c) 1,500 rpm
- (d) 1,800 rpm
Answer: (b) 1,200 rpm — Ns = 120 × f ÷ P = 120 × 60 ÷ 6 = 1,200 rpm.
Q9. A ceiling fan runs much slower than normal and its capacitor feels swollen. What is the fault?
- (a) The main winding is open-circuited
- (b) The run capacitor has lost capacitance, reducing the auxiliary-winding current and torque
- (c) The centrifugal switch is stuck open
- (d) The supply frequency has dropped to zero
Answer: (b) The run capacitor has lost capacitance, reducing the auxiliary-winding current and torque — a weak capacitor is the most common cause of a slow ceiling fan.
Q10. A single-phase motor on a 20 A, 120 V circuit is rated for continuous duty. What is the maximum continuous load the NEC 80% rule allows on that circuit?
- (a) 2,400 W
- (b) 1,920 W
- (c) 1,200 W
- (d) 3,000 W
Answer: (b) 1,920 W — the NEC 80% rule limits continuous load to 20 × 120 × 0.8 = 1,920 W.
Also read: Washing Machine Motor Guide | All MCQ Topics