Sensor MCQs — Set 9

10 practice questions on sensor faults and troubleshooting — open loops, drift, false triggering, noise and calibration.

Q1. A 4–20 mA loop reads 0 mA at the controller. What is the most likely fault?

  • (a) The measured value is at 0%
  • (b) The loop is open — a broken wire, loose terminal or failed transmitter
  • (c) The transmitter is over-ranged
  • (d) The 250 Ω resistor is too large

Answer: (b) The loop is open — a broken wire, loose terminal or failed transmitter — a healthy loop never reads 0 mA, because even 0% gives 4 mA; 0 mA means no current can flow at all.

Q2. A 4–20 mA temperature loop is stuck at 4 mA even though the process is hot. What does this suggest?

  • (a) The temperature is at the bottom of the range or the sensor has failed low
  • (b) The loop is definitely broken
  • (c) The temperature is above full scale
  • (d) The transmitter is over-ranged

Answer: (a) The temperature is at the bottom of the range or the sensor has failed low — 4 mA is a valid 0% reading, so check the actual process temperature and the sensor before assuming a wiring fault.

Q3. A 4–20 mA loop reads a steady 20 mA (or slightly above) all the time. What does this suggest?

  • (a) The process is at 0%
  • (b) The measured value is at or above full scale, or the transmitter has failed high
  • (c) The loop wiring is open
  • (d) The sensor is disconnected

Answer: (b) The measured value is at or above full scale, or the transmitter has failed high — check the real process value first, then the sensor, because a genuine over-range condition also drives the loop to 20 mA.

Q4. An inductive proximity sensor on a machine keeps false-triggering even when no part is present. What is a likely cause?

  • (a) Metal chips or filings stuck on the sensor face, or vibration moving a nearby metal part into range
  • (b) The sensor is too far from the target
  • (c) The supply voltage is exactly 24 V
  • (d) The sensor is a PNP type

Answer: (a) Metal chips or filings stuck on the sensor face, or vibration moving a nearby metal part into range — clean the sensor face and check the mounting gap before replacing the sensor.

Q5. A photoelectric sensor starts false-triggering after months of good operation. What should be checked first?

  • (a) The sensor’s IP rating
  • (b) Dust or dirt on the lens, a knocked-out-of-alignment beam, or a new source of strong ambient light
  • (c) The colour of the cable
  • (d) The motor’s overload setting

Answer: (b) Dust or dirt on the lens, a knocked-out-of-alignment beam, or a new source of strong ambient light — these build up gradually, so a sensor that worked for months usually has a dirty lens or a shifted mounting, not a sudden electronic failure.

Q6. A 2-wire RTD starts reading several degrees too high and the error keeps growing. What is the most likely cause?

  • (a) The RTD element is drifting
  • (b) The lead resistance has increased because of a loose or corroded connection
  • (c) The temperature has genuinely risen
  • (d) The thermocouple type is wrong

Answer: (b) The lead resistance has increased because of a loose or corroded connection — in a 2-wire RTD the lead resistance adds directly to the measured resistance, so a bad joint reads as extra temperature; a 3-wire connection avoids this.

Q7. A thermocouple temperature reading is wrong and even goes down when the process heats up. What is a likely cause?

  • (a) The thermocouple wires are reversed, or the wrong type of extension cable is used
  • (b) The thermocouple is too long
  • (c) The process temperature is too stable
  • (d) The cold junction is too cold

Answer: (a) The thermocouple wires are reversed, or the wrong type of extension cable is used — reversed polarity inverts the reading, and the wrong extension wire creates extra junctions that corrupt the voltage.

Q8. A sensor’s readings slowly wander away from the true value over months. What is this called, and what fixes it?

  • (a) Hysteresis; replace the sensor
  • (b) Drift; recalibration against a known reference
  • (c) Noise; fit a larger cable
  • (d) Overload; fit a bigger sensor

Answer: (b) Drift; recalibration against a known reference — ageing, contamination and temperature cycling shift a sensor’s output over time, so periodic calibration brings it back within tolerance.

Q9. An RTD reads slightly high, and the error gets worse when the excitation current is increased. What is the cause?

  • (a) The RTD element is too long
  • (b) Self-heating — the excitation current warms the RTD element above the temperature being measured
  • (c) The lead wires are too short
  • (d) The thermocouple type is wrong

Answer: (b) Self-heating — the excitation current warms the RTD element above the temperature being measured — the measuring current must be kept small (typically about 1 mA) so the heating it causes is negligible.

Q10. A sensor signal running beside a variable-frequency drive (VFD) motor cable is noisy and unstable. What is the best fix?

  • (a) Use a longer sensor cable
  • (b) Route the sensor cable away from the power cable and use earthed shielded cable
  • (c) Increase the supply voltage to 230 V
  • (d) Remove the sensor’s earth connection

Answer: (b) Route the sensor cable away from the power cable and use earthed shielded cable — the VFD cable radiates electromagnetic interference, and separation plus a shield keeps it out of the small sensor signal.

Also read: AC Circuit MCQs | All MCQ Topics