Safety PPE MCQs — Set 7
10 practice questions on test-before-touch — proving testers, the live-dead-live check and proving a circuit is dead.
Q1. What does test-before-touch mean?
- (a) Touch the conductor first, then test it
- (b) Test the circuit with a suitable instrument to prove it is dead before touching any conductor
- (c) Test the circuit only after the work is finished
- (d) Touch the tester to the wall before use
Answer: (b) Test the circuit with a suitable instrument to prove it is dead before touching any conductor — never assume a circuit is dead because a switch is off.
Q2. What is the correct live-dead-live test sequence?
- (a) Test the dead circuit, then test a known live source
- (b) Test the tester on a known live source, test the circuit to be worked on, then re-test the tester on the known live source
- (c) Test the circuit twice and skip the live source
- (d) Test the tester once a week only
Answer: (b) Test the tester on a known live source, test the circuit to be worked on, then re-test the tester on the known live source — this proves the tester was working both before and after the dead test.
Q3. What is a proving unit used for?
- (a) To charge the tester’s batteries
- (b) To provide a known voltage source to check that a voltage tester is working
- (c) To measure insulation resistance
- (d) To discharge capacitors
Answer: (b) To provide a known voltage source to check that a voltage tester is working — if no live source is available, the proving unit is the known source for the live-dead-live check.
Q4. What is a key limitation of a non-contact voltage tester (voltage pen)?
- (a) It is too accurate
- (b) It can give a false negative, so it must not be the only test used to prove a circuit dead
- (c) It cannot detect any voltage at all
- (d) It only works on DC circuits
Answer: (b) It can give a false negative, so it must not be the only test used to prove a circuit dead — a contact two-pole tester should confirm the dead test.
Q5. What must a test instrument be rated for before it is used?
- (a) Only the colour of the leads
- (b) The voltage and category (CAT rating) of the circuit being tested
- (c) The brand of the instrument
- (d) The age of the instrument
Answer: (b) The voltage and category (CAT rating) of the circuit being tested — an under-rated tester can fail dangerously on a higher-energy circuit.
Q6. Why should insulated gloves be worn while testing for absence of voltage?
- (a) To keep the hands clean
- (b) Because the circuit may still be live, and the gloves protect against shock during the test
- (c) Gloves make the tester more accurate
- (d) Gloves are only needed in cold weather
Answer: (b) Because the circuit may still be live, and the gloves protect against shock during the test — until the circuit is proven dead, it must be treated as live.
Q7. What should a worker do if the tester shows voltage on a circuit that was supposed to be isolated?
- (a) Ignore the reading and start work
- (b) Treat the circuit as live, stop work and find out why it is still energised
- (c) Test again with bare hands
- (d) Remove the tester batteries
Answer: (b) Treat the circuit as live, stop work and find out why it is still energised — the isolation may be on the wrong circuit or a second supply may be present.
Q8. When proving a three-phase circuit dead, what must be tested?
- (a) Only one phase
- (b) Each phase to earth and each phase to each other phase
- (c) Only the neutral
- (d) Only the earth conductor
Answer: (b) Each phase to earth and each phase to each other phase — testing only one phase could miss another phase that is still live.
Q9. Why is a purpose-built two-pole voltage tester preferred over a general multimeter for proving dead?
- (a) It is cheaper
- (b) It is designed for the job, with no range switch to set wrongly and clear voltage indication
- (c) It measures resistance as well
- (d) It has a longer battery life
Answer: (b) It is designed for the job, with no range switch to set wrongly and clear voltage indication — a multimeter on the wrong range can show zero on a live circuit.
Q10. What does the final re-test on the known live source prove?
- (a) That the circuit is live
- (b) That the tester did not fail during the dead test, so the “dead” reading can be trusted
- (c) That the batteries are new
- (d) That the proving unit is working
Answer: (b) That the tester did not fail during the dead test, so the “dead” reading can be trusted — a tester that fails silently could show zero on a live circuit.