Relay MCQs — Set 6
10 practice questions on the Buchholz relay — where it sits, how gas and oil surge operate it, and which transformer faults it catches.
Q1. Where is a Buchholz relay installed on a transformer?
- (a) Inside the tap changer
- (b) In the pipe between the main tank and the conservator
- (c) On the transformer neutral point
- (d) At the bottom of the cooling radiator
Answer: (b) In the pipe between the main tank and the conservator — gas rising from the tank must pass through it on the way to the conservator.
Q2. What does a Buchholz relay detect in a transformer?
- (a) Overvoltage on the supply
- (b) Gas produced by internal faults in the transformer oil
- (c) Loose bolts on the bushings
- (d) Low power factor
Answer: (b) Gas produced by internal faults in the transformer oil — arcing and overheating break the oil down and release gas.
Q3. Which type of transformer uses a Buchholz relay?
- (a) Dry-type transformers
- (b) Oil-immersed transformers, typically 500 kVA and above
- (c) Small plug-in adaptor transformers
- (d) Current transformers
Answer: (b) Oil-immersed transformers, typically 500 kVA and above — the relay needs oil and gas to work, so it is fitted on larger oil-filled units.
Q4. What happens in a Buchholz relay during a minor internal fault?
- (a) The breaker trips instantly
- (b) Gas accumulates in the relay chamber, the upper float drops and an alarm is raised
- (c) The oil level in the conservator rises
- (d) Nothing happens until the transformer explodes
Answer: (b) Gas accumulates in the relay chamber, the upper float drops and an alarm is raised — a slow gas build-up warns of an incipient fault.
Q5. What makes a Buchholz relay trip the circuit breaker?
- (a) A slow rise in oil temperature
- (b) A sudden surge of oil from the tank towards the conservator during a severe fault
- (c) A drop in the supply voltage
- (d) A loose connection on the relay terminal
Answer: (b) A sudden surge of oil from the tank towards the conservator during a severe fault — the oil flow pushes the lower float down and closes the trip contact.
Q6. Which gas is mainly produced when arcing breaks down transformer oil?
- (a) Oxygen
- (b) Hydrogen
- (c) Nitrogen
- (d) Carbon dioxide
Answer: (b) Hydrogen — arcing in oil releases mostly hydrogen, along with small amounts of hydrocarbon gases.
Q7. Why does a Buchholz relay have two floats?
- (a) One measures oil level and the other measures temperature
- (b) The upper float gives an alarm for slow gas accumulation and the lower float trips on a sudden oil surge
- (c) One is a spare in case the other fails
- (d) One works on AC and the other on DC
Answer: (b) The upper float gives an alarm for slow gas accumulation and the lower float trips on a sudden oil surge — alarm first, trip only for a serious fault.
Q8. What should be done after a Buchholz relay gives an alarm?
- (a) Ignore it and keep the transformer loaded
- (b) Take a gas sample from the relay and have it analysed to identify the fault
- (c) Top up the oil immediately without checking
- (d) Reset the relay and switch the transformer back on
Answer: (b) Take a gas sample from the relay and have it analysed to identify the fault — the gas composition shows whether the fault is arcing, overheating or corona.
Q9. Can a Buchholz relay be used on a dry-type transformer?
- (a) Yes, it works exactly the same way
- (b) No, because there is no oil to produce gas or an oil surge
- (c) Yes, but only below 100 kVA
- (d) No, because dry-type transformers never develop faults
Answer: (b) No, because there is no oil to produce gas or an oil surge — the Buchholz principle depends entirely on oil and the gas it releases.
Q10. Which fault is a Buchholz relay most sensitive to?
- (a) A heavy external short circuit on the feeder
- (b) A slow-developing internal fault, such as an inter-turn or core fault that produces gas before the current rises much
- (c) A lightning strike on the line
- (d) An overload on a neighbouring transformer
Answer: (b) A slow-developing internal fault, such as an inter-turn or core fault that produces gas before the current rises much — these faults may not draw enough current to operate an overcurrent relay.