Relay MCQs — Set 6

10 practice questions on the Buchholz relay — where it sits, how gas and oil surge operate it, and which transformer faults it catches.

Q1. Where is a Buchholz relay installed on a transformer?

  • (a) Inside the tap changer
  • (b) In the pipe between the main tank and the conservator
  • (c) On the transformer neutral point
  • (d) At the bottom of the cooling radiator

Answer: (b) In the pipe between the main tank and the conservator — gas rising from the tank must pass through it on the way to the conservator.

Q2. What does a Buchholz relay detect in a transformer?

  • (a) Overvoltage on the supply
  • (b) Gas produced by internal faults in the transformer oil
  • (c) Loose bolts on the bushings
  • (d) Low power factor

Answer: (b) Gas produced by internal faults in the transformer oil — arcing and overheating break the oil down and release gas.

Q3. Which type of transformer uses a Buchholz relay?

  • (a) Dry-type transformers
  • (b) Oil-immersed transformers, typically 500 kVA and above
  • (c) Small plug-in adaptor transformers
  • (d) Current transformers

Answer: (b) Oil-immersed transformers, typically 500 kVA and above — the relay needs oil and gas to work, so it is fitted on larger oil-filled units.

Q4. What happens in a Buchholz relay during a minor internal fault?

  • (a) The breaker trips instantly
  • (b) Gas accumulates in the relay chamber, the upper float drops and an alarm is raised
  • (c) The oil level in the conservator rises
  • (d) Nothing happens until the transformer explodes

Answer: (b) Gas accumulates in the relay chamber, the upper float drops and an alarm is raised — a slow gas build-up warns of an incipient fault.

Q5. What makes a Buchholz relay trip the circuit breaker?

  • (a) A slow rise in oil temperature
  • (b) A sudden surge of oil from the tank towards the conservator during a severe fault
  • (c) A drop in the supply voltage
  • (d) A loose connection on the relay terminal

Answer: (b) A sudden surge of oil from the tank towards the conservator during a severe fault — the oil flow pushes the lower float down and closes the trip contact.

Q6. Which gas is mainly produced when arcing breaks down transformer oil?

  • (a) Oxygen
  • (b) Hydrogen
  • (c) Nitrogen
  • (d) Carbon dioxide

Answer: (b) Hydrogen — arcing in oil releases mostly hydrogen, along with small amounts of hydrocarbon gases.

Q7. Why does a Buchholz relay have two floats?

  • (a) One measures oil level and the other measures temperature
  • (b) The upper float gives an alarm for slow gas accumulation and the lower float trips on a sudden oil surge
  • (c) One is a spare in case the other fails
  • (d) One works on AC and the other on DC

Answer: (b) The upper float gives an alarm for slow gas accumulation and the lower float trips on a sudden oil surge — alarm first, trip only for a serious fault.

Q8. What should be done after a Buchholz relay gives an alarm?

  • (a) Ignore it and keep the transformer loaded
  • (b) Take a gas sample from the relay and have it analysed to identify the fault
  • (c) Top up the oil immediately without checking
  • (d) Reset the relay and switch the transformer back on

Answer: (b) Take a gas sample from the relay and have it analysed to identify the fault — the gas composition shows whether the fault is arcing, overheating or corona.

Q9. Can a Buchholz relay be used on a dry-type transformer?

  • (a) Yes, it works exactly the same way
  • (b) No, because there is no oil to produce gas or an oil surge
  • (c) Yes, but only below 100 kVA
  • (d) No, because dry-type transformers never develop faults

Answer: (b) No, because there is no oil to produce gas or an oil surge — the Buchholz principle depends entirely on oil and the gas it releases.

Q10. Which fault is a Buchholz relay most sensitive to?

  • (a) A heavy external short circuit on the feeder
  • (b) A slow-developing internal fault, such as an inter-turn or core fault that produces gas before the current rises much
  • (c) A lightning strike on the line
  • (d) An overload on a neighbouring transformer

Answer: (b) A slow-developing internal fault, such as an inter-turn or core fault that produces gas before the current rises much — these faults may not draw enough current to operate an overcurrent relay.

Also read: GFCI vs AFCI | All MCQ Topics