Relay MCQs — Set 5
10 practice questions on differential relays — the current-comparison principle, biased protection and transformer differential schemes.
Q1. On what principle does a differential relay work?
- (a) It measures the voltage drop across a resistor
- (b) It compares the current entering a protected zone with the current leaving it
- (c) It measures the temperature of the windings
- (d) It counts the number of switching operations
Answer: (b) It compares the current entering a protected zone with the current leaving it — under healthy conditions the two currents are equal (Kirchhoff’s current law).
Q2. What is differential protection best suited to protect?
- (a) Long overhead transmission lines only
- (b) Transformers, generators and busbars against internal faults
- (c) Domestic lighting circuits
- (d) Battery chargers
Answer: (b) Transformers, generators and busbars against internal faults — it detects faults inside a clearly defined zone very fast.
Q3. Under normal healthy conditions, what is the differential current in a differential relay?
- (a) Equal to the full load current
- (b) Nearly zero, because the current entering equals the current leaving
- (c) Equal to the short-circuit current
- (d) Always 5 A
Answer: (b) Nearly zero, because the current entering equals the current leaving — the relay only operates when a difference appears.
Q4. A differential relay sees 5 A entering a zone and 4.8 A leaving it. What is the differential current?
- (a) 0.2 A
- (b) 9.8 A
- (c) 5 A
- (d) 4.8 A
Answer: (a) 0.2 A — differential current = 5 − 4.8 = 0.2 A, the difference between the two CT secondary currents.
Q5. Why is percentage (biased) differential protection used instead of plain differential protection?
- (a) It makes the relay cheaper
- (b) It prevents false tripping caused by CT errors and mismatches during heavy external faults
- (c) It removes the need for CTs
- (d) It makes the relay operate on voltage instead of current
Answer: (b) It prevents false tripping caused by CT errors and mismatches during heavy external faults — the relay becomes less sensitive as the through current grows.
Q6. What is the job of the restraining coil in a biased differential relay?
- (a) To trip the breaker directly
- (b) To produce a restraining force proportional to the through current, opposing the operating coil
- (c) To step down the CT voltage
- (d) To cool the relay
Answer: (b) To produce a restraining force proportional to the through current, opposing the operating coil — the relay trips only when the differential current outweighs the restraint.
Q7. Where are the current transformers placed for transformer differential protection?
- (a) Only on the high-voltage side
- (b) On both the high-voltage and low-voltage sides of the transformer
- (c) Only on the neutral point
- (d) Inside the transformer tank
Answer: (b) On both the high-voltage and low-voltage sides of the transformer — the relay compares the currents on the two sides.
Q8. Why can transformer magnetising inrush current cause a differential relay to trip falsely?
- (a) Inrush current is too small to measure
- (b) Inrush flows only on one side of the transformer, so it looks like an internal fault current difference
- (c) Inrush current reverses the CT polarity
- (d) Inrush current heats the relay coil
Answer: (b) Inrush flows only on one side of the transformer, so it looks like an internal fault current difference — modern relays block this using second-harmonic restraint.
Q9. Which type of fault does differential protection detect fastest?
- (a) A fault far away on another feeder
- (b) An internal fault inside its own protected zone
- (c) A lightning strike on the line
- (d) An overload on a neighbouring transformer
Answer: (b) An internal fault inside its own protected zone — the current difference appears immediately and the relay trips without intentional delay.
Q10. A generator differential relay sees 5 A entering and 5 A leaving the generator zone. What does the relay do?
- (a) It trips the breaker instantly
- (b) It does not operate, because the differential current is zero
- (c) It sounds an alarm only
- (d) It increases the excitation current
Answer: (b) It does not operate, because the differential current is zero — equal in and out currents mean no fault inside the zone.