Relay MCQs — Set 3

10 practice questions on thermal overload relays — how the bimetallic strip works, the 1.0–1.2× setting range and trip class.

Q1. What does a thermal overload relay protect a motor against?

  • (a) Lightning strikes
  • (b) Sustained overload current that overheats the motor windings
  • (c) Loss of supply voltage only
  • (d) Mechanical vibration

Answer: (b) Sustained overload current that overheats the motor windings — it trips before the heat damages the insulation.

Q2. How does a thermal overload relay sense an overload?

  • (a) A current transformer sends a signal to a microprocessor
  • (b) A bimetallic strip heats up and bends, opening the trip contact
  • (c) A magnetic coil pulls the armature instantly
  • (d) A gas-filled bulb expands and breaks the circuit

Answer: (b) A bimetallic strip heats up and bends, opening the trip contact — the strip is heated by the motor current passing through a heater element.

Q3. A motor has a full-load current of 10 A. What is the usual thermal overload relay setting range?

  • (a) 5–6 A
  • (b) 10–12 A
  • (c) 15–20 A
  • (d) 20–25 A

Answer: (b) 10–12 A — the setting range is typically 1.0–1.2 times full-load current, so 10 × 1.0 = 10 A and 10 × 1.2 = 12 A.

Q4. Why does a thermal overload relay take time to trip instead of tripping instantly?

  • (a) Its contacts are too slow by design
  • (b) It mimics the heating of the motor, so it tolerates the brief high current at starting
  • (c) It waits for the fuse to blow first
  • (d) It only works on a timer, not on current

Answer: (b) It mimics the heating of the motor, so it tolerates the brief high current at starting — a motor draws several times full-load current for a few seconds at start-up.

Q5. A motor has a full-load current of 20 A. What is the usual thermal overload relay setting range?

  • (a) 10–12 A
  • (b) 20–24 A
  • (c) 25–30 A
  • (d) 40–48 A

Answer: (b) 20–24 A — 1.0–1.2 times full-load current gives 20 × 1.0 = 20 A to 20 × 1.2 = 24 A.

Q6. What happens if a thermal overload relay is set far above the motor’s full-load current?

  • (a) The motor starts faster
  • (b) The motor can overheat and burn out before the relay trips
  • (c) The relay trips on every start
  • (d) Nothing changes at all

Answer: (b) The motor can overheat and burn out before the relay trips — the setting must match the motor’s full-load current.

Q7. What is the main difference between a thermal overload relay and a fuse?

  • (a) A fuse can be reset and an overload relay cannot
  • (b) An overload relay trips on sustained overload and can be reset, while a fuse melts once, mainly on short circuit
  • (c) A fuse protects against overload and an overload relay does not
  • (d) There is no difference between them

Answer: (b) An overload relay trips on sustained overload and can be reset, while a fuse melts once, mainly on short circuit — the relay is for overload, the fuse is for short-circuit backup.

Q8. What does a Class 10 trip rating mean for an overload relay?

  • (a) It trips in 10 minutes at full load
  • (b) It trips within 10 seconds when the current reaches 7.2 times its setting
  • (c) It can be reset 10 times
  • (d) It protects 10 motors at once

Answer: (b) It trips within 10 seconds when the current reaches 7.2 times its setting — the class number is the maximum trip time in seconds at 7.2 times the set current.

Q9. A motor has a full-load current of 15 A. What is the usual thermal overload relay setting range?

  • (a) 7.5–9 A
  • (b) 15–18 A
  • (c) 18–22 A
  • (d) 30–36 A

Answer: (b) 15–18 A — 1.0–1.2 times full-load current gives 15 × 1.0 = 15 A to 15 × 1.2 = 18 A.

Q10. After a thermal overload relay trips, why must you wait a short time before resetting it?

  • (a) The supply must be switched off for 10 minutes by law
  • (b) The bimetallic strip must cool down and return to its normal shape
  • (c) The fuse needs time to re-form
  • (d) The motor bearings need oil

Answer: (b) The bimetallic strip must cool down and return to its normal shape — resetting while it is still hot would let the motor restart into the same overload.

Also read: GFCI Outlet Keeps Tripping | All MCQ Topics