Power Quality MCQs — Set 9

10 practice questions on fixing power quality problems — UPS systems, filters, voltage restorers and regulators.

Q1. What is the main job of a UPS during a supply interruption?

  • (a) To filter harmonics
  • (b) To keep the load running from its battery until the supply returns or a generator starts
  • (c) To balance the phases
  • (d) To raise the frequency

Answer: (b) To keep the load running from its battery until the supply returns or a generator starts — a UPS bridges short outages and gives time for an orderly shutdown or generator start.

Q2. What is the transfer time of an online double-conversion UPS?

  • (a) 0 ms
  • (b) 10 ms
  • (c) 100 ms
  • (d) 1 second

Answer: (a) 0 ms — the load is always supplied by the inverter, so there is no switching break when the mains fails.

Q3. What does a dynamic voltage restorer (DVR) do?

  • (a) It stores energy in a battery
  • (b) It injects a series voltage to restore the load voltage during a sag
  • (c) It filters out harmonics
  • (d) It measures power factor

Answer: (b) It injects a series voltage to restore the load voltage during a sag — a DVR adds the missing voltage in series with the supply within milliseconds.

Q4. What is the difference between a passive harmonic filter and an active harmonic filter?

  • (a) A passive filter uses tuned LC circuits; an active filter uses power electronics to inject cancelling currents
  • (b) There is no difference
  • (c) A passive filter needs a battery
  • (d) An active filter only works on DC

Answer: (a) A passive filter uses tuned LC circuits; an active filter uses power electronics to inject cancelling currents — passive filters are fixed at one harmonic, while active filters adapt to changing loads.

Q5. A passive harmonic filter is built from what components?

  • (a) Inductors and capacitors tuned to a harmonic frequency
  • (b) Only resistors
  • (c) Only transformers
  • (d) Diodes and fuses

Answer: (a) Inductors and capacitors tuned to a harmonic frequency — the LC branch has very low impedance at its tuned frequency, so that harmonic current flows into the filter instead of the supply.

Q6. How does an isolation transformer help with power quality?

  • (a) It blocks common-mode noise and transients from passing between primary and secondary
  • (b) It removes all harmonics
  • (c) It corrects the power factor
  • (d) It increases the supply voltage

Answer: (a) It blocks common-mode noise and transients from passing between primary and secondary — the separate windings with an earthed screen stop high-frequency noise reaching sensitive equipment.

Q7. Where should a surge protective device (SPD) be installed for best protection?

  • (a) Only at the far end of the installation
  • (b) At the service entrance, with additional SPDs near sensitive equipment
  • (c) Inside the meter only
  • (d) On the earth electrode

Answer: (b) At the service entrance, with additional SPDs near sensitive equipment — a layered approach clamps the big surge at entry and the residual at the equipment.

Q8. What does a servo voltage stabiliser do?

  • (a) It switches the load off during a sag
  • (b) It continuously adjusts a variable transformer to hold the output voltage steady
  • (c) It filters harmonics
  • (d) It stores energy in a flywheel

Answer: (b) It continuously adjusts a variable transformer to hold the output voltage steady — a motor-driven brush moves along the transformer winding to correct slow voltage variations.

Q9. How does a soft starter reduce voltage sags at motor start?

  • (a) It limits the starting current by ramping the voltage up gradually
  • (b) It disconnects the motor
  • (c) It raises the supply voltage
  • (d) It adds harmonics

Answer: (a) It limits the starting current by ramping the voltage up gradually — lower inrush current means a smaller voltage dip on the supply.

Q10. A 5 kW load must be backed up for 10 minutes by a UPS. How much energy must the battery deliver?

  • (a) 0.5 kWh
  • (b) 0.83 kWh
  • (c) 5 kWh
  • (d) 50 kWh

Answer: (b) 0.83 kWh — energy = power × time = 5 kW × (10 ÷ 60) h = 5 × 0.167 = 0.83 kWh (before allowing for inverter losses and battery ageing).