Power Quality MCQs — Set 8
10 practice questions on measuring power quality — analysers, meters, standards and the point of common coupling.
Q1. What does a power quality analyser measure that an ordinary voltmeter does not?
- (a) Only the voltage magnitude
- (b) Sags, swells, transients, harmonics, flicker, unbalance and frequency — all at once
- (c) Only the resistance
- (d) Only the current
Answer: (b) Sags, swells, transients, harmonics, flicker, unbalance and frequency — all at once — a PQ analyser records the full set of disturbances over time, while a voltmeter shows only an instantaneous RMS value.
Q2. Why must a true-RMS meter be used on a circuit with harmonic distortion?
- (a) An average-responding meter assumes a pure sine wave and reads low on distorted waveforms
- (b) A true-RMS meter is cheaper
- (c) An average meter cannot measure DC
- (d) True-RMS meters measure frequency only
Answer: (a) An average-responding meter assumes a pure sine wave and reads low on distorted waveforms — it measures the average and scales it by 1.11, which is only correct for a sine wave; a true-RMS meter measures the actual heating value.
Q3. Why does a power quality analyser need a very high sampling rate?
- (a) To measure the supply frequency
- (b) To capture short transients and high-order harmonics accurately
- (c) To save battery power
- (d) To measure resistance
Answer: (b) To capture short transients and high-order harmonics accurately — a microsecond spike or a 50th harmonic cannot be seen if the instrument only takes a few samples per cycle.
Q4. Which standard covers recommended practices for harmonic control in power systems?
- (a) IEEE 519
- (b) IEEE 1159
- (c) IEC 61000-4-30
- (d) EN 50160
Answer: (a) IEEE 519 — it sets the limits for harmonic voltage and current distortion at the point of common coupling.
Q5. Which standard defines how power quality should be monitored and classified?
- (a) IEEE 519
- (b) IEEE 1159
- (c) IEC 60076
- (d) BS 7671
Answer: (b) IEEE 1159 — it defines power quality phenomena, their categories and the monitoring methods used to record them.
Q6. EN 50160 requires that 95% of the 10-minute RMS voltage values stay within what band for low-voltage supplies?
- (a) ±1%
- (b) ±5%
- (c) ±10%
- (d) ±20%
Answer: (c) ±10% — EN 50160 is the European standard for voltage characteristics of public supply networks.
Q7. What is the crest factor of a pure sine wave?
- (a) 1.0
- (b) 1.41
- (c) 2.0
- (d) 0.707
Answer: (b) 1.41 — crest factor = peak ÷ RMS = √2 ≈ 1.41 for a sine wave; a much higher value signals a distorted, peaky waveform.
Q8. A waveform has a peak voltage of 325 V and an RMS voltage of 230 V. What is its crest factor?
- (a) 1.0
- (b) 1.41
- (c) 1.55
- (d) 0.71
Answer: (b) 1.41 — crest factor = 325 ÷ 230 = 1.41, the value expected for a clean sine wave.
Q9. Where should harmonic measurements be taken to check compliance with IEEE 519?
- (a) At the point of common coupling (PCC)
- (b) At the far end of the cable only
- (c) Inside the motor terminal box
- (d) At the earth electrode
Answer: (a) At the point of common coupling (PCC) — the PCC is where the consumer’s system connects to the utility, and it is the point where the limits apply.
Q10. How long is a typical power quality survey run when checking compliance with EN 50160?
- (a) 10 minutes
- (b) 1 hour
- (c) One week
- (d) One year
Answer: (c) One week — a week-long recording captures daily and weekly load patterns, including weekend changes, so the 95% statistics are meaningful.