Power Quality MCQs — Set 6

10 practice questions on voltage unbalance — how to calculate it, why it damages motors, and how to fix it.

Q1. What is the most common cause of voltage unbalance in a building?

  • (a) Lightning
  • (b) Single-phase loads unevenly shared across the three phases
  • (c) A capacitor bank
  • (d) A solar inverter

Answer: (b) Single-phase loads unevenly shared across the three phases — if one phase carries far more single-phase load than the others, its voltage sags and the system becomes unbalanced.

Q2. Three line voltages are 400 V, 390 V and 380 V. What is the voltage unbalance?

  • (a) 1.3%
  • (b) 2.6%
  • (c) 5.0%
  • (d) 10%

Answer: (b) 2.6% — average = (400 + 390 + 380) ÷ 3 = 390 V; maximum deviation is 10 V; unbalance = 10 ÷ 390 × 100 = 2.6%.

Q3. Three phase voltages are 230 V, 230 V and 220 V. What is the voltage unbalance?

  • (a) 2.9%
  • (b) 4.3%
  • (c) 1.5%
  • (d) 2.2%

Answer: (a) 2.9% — average = (230 + 230 + 220) ÷ 3 = 226.7 V; maximum deviation is 6.7 V; unbalance = 6.7 ÷ 226.7 × 100 = 2.9%.

Q4. Three line voltages are 415 V, 405 V and 395 V. What is the voltage unbalance?

  • (a) 1.2%
  • (b) 2.5%
  • (c) 5.0%
  • (d) 3.7%

Answer: (b) 2.5% — average = (415 + 405 + 395) ÷ 3 = 405 V; maximum deviation is 10 V; unbalance = 10 ÷ 405 × 100 = 2.5%.

Q5. A motor runs on a supply with 1% voltage unbalance. Roughly how much current unbalance should be expected?

  • (a) About 1%
  • (b) About 6–10%
  • (c) About 50%
  • (d) No current unbalance at all

Answer: (b) About 6–10% — a small voltage unbalance produces a much larger current unbalance in a motor, roughly 6 to 10 times the voltage unbalance.

Q6. What is the NEMA recommended maximum voltage unbalance at a motor’s terminals?

  • (a) 1%
  • (b) 5%
  • (c) 10%
  • (d) 20%

Answer: (a) 1% — NEMA MG-1 recommends no more than 1% voltage unbalance at motor terminals; above 5% the motor should not be operated.

Q7. Why does voltage unbalance overheat a three-phase motor?

  • (a) It raises the supply frequency
  • (b) It creates negative-sequence currents that produce a counter-rotating field and extra losses
  • (c) It increases the power factor
  • (d) It stops the cooling fan

Answer: (b) It creates negative-sequence currents that produce a counter-rotating field and extra losses — the negative-sequence field fights the rotor, causing heat, vibration and reduced torque.

Q8. How is voltage unbalance measured in the field?

  • (a) By measuring all three line voltages and comparing each with their average
  • (b) By measuring only one phase voltage
  • (c) By measuring the earth resistance
  • (d) By counting the frequency

Answer: (a) By measuring all three line voltages and comparing each with their average — unbalance is defined by the largest deviation from the average of the three voltages.

Q9. What is the first step in fixing voltage unbalance in a building?

  • (a) Install a bigger transformer
  • (b) Redistribute the single-phase loads evenly across the three phases
  • (c) Add more harmonics
  • (d) Reduce the supply frequency

Answer: (b) Redistribute the single-phase loads evenly across the three phases — balancing the load is the cheapest and most effective fix; also check for a blown fuse or loose connection on one phase.

Q10. Three phase voltages are 230 V, 225 V and 215 V. What is the voltage unbalance?

  • (a) 2.2%
  • (b) 3.7%
  • (c) 2.6%
  • (d) 5.0%

Answer: (b) 3.7% — average = (230 + 225 + 215) ÷ 3 = 223.3 V; maximum deviation is 8.3 V; unbalance = 8.3 ÷ 223.3 × 100 = 3.7%.