Power Quality MCQs — Set 6
10 practice questions on voltage unbalance — how to calculate it, why it damages motors, and how to fix it.
Q1. What is the most common cause of voltage unbalance in a building?
- (a) Lightning
- (b) Single-phase loads unevenly shared across the three phases
- (c) A capacitor bank
- (d) A solar inverter
Answer: (b) Single-phase loads unevenly shared across the three phases — if one phase carries far more single-phase load than the others, its voltage sags and the system becomes unbalanced.
Q2. Three line voltages are 400 V, 390 V and 380 V. What is the voltage unbalance?
- (a) 1.3%
- (b) 2.6%
- (c) 5.0%
- (d) 10%
Answer: (b) 2.6% — average = (400 + 390 + 380) ÷ 3 = 390 V; maximum deviation is 10 V; unbalance = 10 ÷ 390 × 100 = 2.6%.
Q3. Three phase voltages are 230 V, 230 V and 220 V. What is the voltage unbalance?
- (a) 2.9%
- (b) 4.3%
- (c) 1.5%
- (d) 2.2%
Answer: (a) 2.9% — average = (230 + 230 + 220) ÷ 3 = 226.7 V; maximum deviation is 6.7 V; unbalance = 6.7 ÷ 226.7 × 100 = 2.9%.
Q4. Three line voltages are 415 V, 405 V and 395 V. What is the voltage unbalance?
- (a) 1.2%
- (b) 2.5%
- (c) 5.0%
- (d) 3.7%
Answer: (b) 2.5% — average = (415 + 405 + 395) ÷ 3 = 405 V; maximum deviation is 10 V; unbalance = 10 ÷ 405 × 100 = 2.5%.
Q5. A motor runs on a supply with 1% voltage unbalance. Roughly how much current unbalance should be expected?
- (a) About 1%
- (b) About 6–10%
- (c) About 50%
- (d) No current unbalance at all
Answer: (b) About 6–10% — a small voltage unbalance produces a much larger current unbalance in a motor, roughly 6 to 10 times the voltage unbalance.
Q6. What is the NEMA recommended maximum voltage unbalance at a motor’s terminals?
- (a) 1%
- (b) 5%
- (c) 10%
- (d) 20%
Answer: (a) 1% — NEMA MG-1 recommends no more than 1% voltage unbalance at motor terminals; above 5% the motor should not be operated.
Q7. Why does voltage unbalance overheat a three-phase motor?
- (a) It raises the supply frequency
- (b) It creates negative-sequence currents that produce a counter-rotating field and extra losses
- (c) It increases the power factor
- (d) It stops the cooling fan
Answer: (b) It creates negative-sequence currents that produce a counter-rotating field and extra losses — the negative-sequence field fights the rotor, causing heat, vibration and reduced torque.
Q8. How is voltage unbalance measured in the field?
- (a) By measuring all three line voltages and comparing each with their average
- (b) By measuring only one phase voltage
- (c) By measuring the earth resistance
- (d) By counting the frequency
Answer: (a) By measuring all three line voltages and comparing each with their average — unbalance is defined by the largest deviation from the average of the three voltages.
Q9. What is the first step in fixing voltage unbalance in a building?
- (a) Install a bigger transformer
- (b) Redistribute the single-phase loads evenly across the three phases
- (c) Add more harmonics
- (d) Reduce the supply frequency
Answer: (b) Redistribute the single-phase loads evenly across the three phases — balancing the load is the cheapest and most effective fix; also check for a blown fuse or loose connection on one phase.
Q10. Three phase voltages are 230 V, 225 V and 215 V. What is the voltage unbalance?
- (a) 2.2%
- (b) 3.7%
- (c) 2.6%
- (d) 5.0%
Answer: (b) 3.7% — average = (230 + 225 + 215) ÷ 3 = 223.3 V; maximum deviation is 8.3 V; unbalance = 8.3 ÷ 223.3 × 100 = 3.7%.
Also read: Voltage Drop Calculator | All MCQ Topics