Power Quality MCQs — Set 4

10 practice questions on flicker, long-duration voltage variations and voltage regulation — with worked answers.

Q1. Which load is the classic cause of voltage flicker?

  • (a) An electric arc furnace
  • (b) A small LED lamp
  • (c) A resistive water heater
  • (d) A phone charger

Answer: (a) An electric arc furnace — its rapidly changing, erratic current draw produces fast voltage fluctuations on the supply.

Q2. What is the usual limit for short-term flicker severity (Pst) at the point of common coupling?

  • (a) 0.1
  • (b) 1.0
  • (c) 5.0
  • (d) 10.0

Answer: (b) 1.0 — Pst = 1.0 is the threshold of perceptibility; values above it mean most people notice the lamp flicker.

Q3. A voltage that stays below 90% of nominal for more than 1 minute is classed as what?

  • (a) A sag
  • (b) An undervoltage
  • (c) A transient
  • (d) Flicker

Answer: (b) An undervoltage — long-duration variations (over 1 minute) are undervoltage below 90% and overvoltage above 110% of nominal.

Q4. A voltage that stays above 110% of nominal for more than 1 minute is classed as what?

  • (a) A swell
  • (b) A sag
  • (c) An overvoltage
  • (d) A notch

Answer: (c) An overvoltage — swells last less than 1 minute; the same high voltage lasting longer is an overvoltage.

Q5. A 230 V supply falls to 200 V and stays there for 2 minutes. How is this classified?

  • (a) A sag, because it is below 207 V
  • (b) An undervoltage, because it lasts over 1 minute at 87% of nominal
  • (c) An interruption
  • (d) Normal variation

Answer: (b) An undervoltage, because it lasts over 1 minute at 87% of nominal — 200 ÷ 230 = 87%, below the 90% line, and a 2-minute duration makes it a long-duration variation, not a sag.

Q6. A transformer gives 240 V at no load and 230 V at full load. What is its voltage regulation?

  • (a) 4.3%
  • (b) 2.4%
  • (c) 10%
  • (d) 4.2 V

Answer: (a) 4.3% — regulation = (no-load voltage − full-load voltage) ÷ full-load voltage × 100 = (240 − 230) ÷ 230 × 100 = 4.3%.

Q7. What is the main human effect of severe flicker?

  • (a) Electric shock
  • (b) Annoyance and eye strain from visible lamp brightness changes
  • (c) Hearing damage
  • (d) Overheating of cables

Answer: (b) Annoyance and eye strain from visible lamp brightness changes — flicker is mainly a comfort and productivity problem, and at certain frequencies it can even trigger headaches.

Q8. Which device is commonly used to reduce flicker from a large fluctuating load?

  • (a) A static VAR compensator (SVC) or STATCOM
  • (b) A surge arrester
  • (c) A fuse
  • (d) A wattmeter

Answer: (a) A static VAR compensator (SVC) or STATCOM — these inject or absorb reactive power within milliseconds, smoothing the voltage fluctuations that cause flicker.

Q9. How long must a voltage variation last to count as a long-duration variation?

  • (a) More than 1 minute
  • (b) More than 1 second
  • (c) More than 1 hour
  • (d) More than 1 cycle

Answer: (a) More than 1 minute — variations longer than 1 minute are long-duration (undervoltage, overvoltage or sustained interruption); shorter ones are sags, swells or momentary interruptions.

Q10. A 400 V supply rises to 420 V and stays there. Is this an overvoltage?

  • (a) Yes, because it is above 400 V
  • (b) No, because 420 V is only 105% of nominal, below the 110% (440 V) limit
  • (c) Yes, because it lasted more than a minute
  • (d) No, because it is a swell

Answer: (b) No, because 420 V is only 105% of nominal, below the 110% (440 V) limit — 420 ÷ 400 = 105%, which is within the normal ±10% supply tolerance band.