Power Quality MCQs — Set 2
10 practice questions on voltage sags and swells — their causes, how long they last, and how to tell one from the other.
Q1. Which of these is the most common cause of a voltage sag?
- (a) A large motor starting
- (b) A capacitor bank switching on
- (c) A light bulb burning out
- (d) A solar panel in bright sun
Answer: (a) A large motor starting — a motor draws 5–7 times its full-load current at start-up, pulling the supply voltage down for a short time.
Q2. According to IEEE 1159, a voltage sag typically lasts for how long?
- (a) 0.5 cycle to 1 minute
- (b) 1 to 5 minutes
- (c) 1 to 24 hours
- (d) Less than half a cycle only
Answer: (a) 0.5 cycle to 1 minute — sags are short-duration events; anything longer than 1 minute below 90% is classed as an undervoltage.
Q3. A 400 V system sags to 320 V during a fault. What is the sag depth?
- (a) 10%
- (b) 80%
- (c) 20%
- (d) 40%
Answer: (c) 20% — the retained voltage is 320 ÷ 400 = 80% of nominal, so the sag depth is 100% − 80% = 20%.
Q4. Which event commonly causes a voltage swell on the unfaulted phases?
- (a) A single line-to-ground fault
- (b) A motor starting
- (c) A lamp switching on
- (d) A battery charging
Answer: (a) A single line-to-ground fault — during a ground fault on one phase, the voltages on the healthy phases can rise above normal.
Q5. On a 230 V system, the voltage rises to 240 V for a few seconds. Is this a swell?
- (a) Yes, any rise is a swell
- (b) No, because it is below the 253 V swell threshold
- (c) Yes, because it exceeds 230 V
- (d) No, because it lasted too long
Answer: (b) No, because it is below the 253 V swell threshold — a swell needs more than 110% of nominal: 230 × 1.1 = 253 V, and 240 V is below that.
Q6. A voltage interruption lasting 2 seconds falls into which category?
- (a) Instantaneous interruption
- (b) Momentary interruption
- (c) Temporary interruption
- (d) Sustained interruption
Answer: (b) Momentary interruption — momentary interruptions last from 0.5 cycle to 3 s; a 2 s outage fits this band.
Q7. An interruption that lasts longer than 1 minute is called what?
- (a) A momentary interruption
- (b) A sustained interruption
- (c) A transient
- (d) A sag
Answer: (b) A sustained interruption — interruptions longer than 1 minute are classed as sustained, and usually need manual restoration.
Q8. Why do voltage sags trip adjustable-speed drives and drop out contactors?
- (a) The current rises too high
- (b) The DC bus voltage in the drive falls and contactor coils lose hold-in voltage
- (c) The frequency changes
- (d) The power factor becomes leading
Answer: (b) The DC bus voltage in the drive falls and contactor coils lose hold-in voltage — a sag starves the drive’s DC bus and weakens the magnetic hold of contactors, so they drop out even though the dip lasts only a few cycles.
Q9. On a 120 V system, the voltage dips to 95 V. Is this a sag?
- (a) No, 95 V is within normal limits
- (b) Yes, because 95 V is below 108 V
- (c) No, because it is above 90 V
- (d) Yes, because any dip is a sag
Answer: (b) Yes, because 95 V is below 108 V — the sag threshold is 90% of nominal: 120 × 0.9 = 108 V, and 95 V is below it.
Q10. What is the ITIC (CBEMA) curve used for in power quality work?
- (a) To size circuit breakers
- (b) To show which sag and swell magnitudes and durations sensitive equipment can tolerate
- (c) To calculate harmonic distortion
- (d) To measure earth resistance
Answer: (b) To show which sag and swell magnitudes and durations sensitive equipment can tolerate — the curve plots voltage against duration; events inside the envelope should not upset computers and similar loads.