Power Quality MCQs — Set 2

10 practice questions on voltage sags and swells — their causes, how long they last, and how to tell one from the other.

Q1. Which of these is the most common cause of a voltage sag?

  • (a) A large motor starting
  • (b) A capacitor bank switching on
  • (c) A light bulb burning out
  • (d) A solar panel in bright sun

Answer: (a) A large motor starting — a motor draws 5–7 times its full-load current at start-up, pulling the supply voltage down for a short time.

Q2. According to IEEE 1159, a voltage sag typically lasts for how long?

  • (a) 0.5 cycle to 1 minute
  • (b) 1 to 5 minutes
  • (c) 1 to 24 hours
  • (d) Less than half a cycle only

Answer: (a) 0.5 cycle to 1 minute — sags are short-duration events; anything longer than 1 minute below 90% is classed as an undervoltage.

Q3. A 400 V system sags to 320 V during a fault. What is the sag depth?

  • (a) 10%
  • (b) 80%
  • (c) 20%
  • (d) 40%

Answer: (c) 20% — the retained voltage is 320 ÷ 400 = 80% of nominal, so the sag depth is 100% − 80% = 20%.

Q4. Which event commonly causes a voltage swell on the unfaulted phases?

  • (a) A single line-to-ground fault
  • (b) A motor starting
  • (c) A lamp switching on
  • (d) A battery charging

Answer: (a) A single line-to-ground fault — during a ground fault on one phase, the voltages on the healthy phases can rise above normal.

Q5. On a 230 V system, the voltage rises to 240 V for a few seconds. Is this a swell?

  • (a) Yes, any rise is a swell
  • (b) No, because it is below the 253 V swell threshold
  • (c) Yes, because it exceeds 230 V
  • (d) No, because it lasted too long

Answer: (b) No, because it is below the 253 V swell threshold — a swell needs more than 110% of nominal: 230 × 1.1 = 253 V, and 240 V is below that.

Q6. A voltage interruption lasting 2 seconds falls into which category?

  • (a) Instantaneous interruption
  • (b) Momentary interruption
  • (c) Temporary interruption
  • (d) Sustained interruption

Answer: (b) Momentary interruption — momentary interruptions last from 0.5 cycle to 3 s; a 2 s outage fits this band.

Q7. An interruption that lasts longer than 1 minute is called what?

  • (a) A momentary interruption
  • (b) A sustained interruption
  • (c) A transient
  • (d) A sag

Answer: (b) A sustained interruption — interruptions longer than 1 minute are classed as sustained, and usually need manual restoration.

Q8. Why do voltage sags trip adjustable-speed drives and drop out contactors?

  • (a) The current rises too high
  • (b) The DC bus voltage in the drive falls and contactor coils lose hold-in voltage
  • (c) The frequency changes
  • (d) The power factor becomes leading

Answer: (b) The DC bus voltage in the drive falls and contactor coils lose hold-in voltage — a sag starves the drive’s DC bus and weakens the magnetic hold of contactors, so they drop out even though the dip lasts only a few cycles.

Q9. On a 120 V system, the voltage dips to 95 V. Is this a sag?

  • (a) No, 95 V is within normal limits
  • (b) Yes, because 95 V is below 108 V
  • (c) No, because it is above 90 V
  • (d) Yes, because any dip is a sag

Answer: (b) Yes, because 95 V is below 108 V — the sag threshold is 90% of nominal: 120 × 0.9 = 108 V, and 95 V is below it.

Q10. What is the ITIC (CBEMA) curve used for in power quality work?

  • (a) To size circuit breakers
  • (b) To show which sag and swell magnitudes and durations sensitive equipment can tolerate
  • (c) To calculate harmonic distortion
  • (d) To measure earth resistance

Answer: (b) To show which sag and swell magnitudes and durations sensitive equipment can tolerate — the curve plots voltage against duration; events inside the envelope should not upset computers and similar loads.

Also read: Voltage Drop Calculator | All MCQ Topics