Power Factor Correction MCQs — Set 10
10 applied practice questions — capacitor currents, freed transformer capacity and real plant scenarios.
Q1. What is the current drawn by a 10 kVAR single-phase capacitor at 230 V?
- (a) 23 A
- (b) 43.5 A
- (c) 10 A
- (d) 100 A
Answer: (b) 43.5 A — I = kVAR × 1000 ÷ V = 10,000 ÷ 230 = 43.5 A.
Q2. What is the current drawn by a 5 kVAR single-phase capacitor at 230 V?
- (a) 43.5 A
- (b) 5 A
- (c) 21.7 A
- (d) 11.5 A
Answer: (c) 21.7 A — I = 5,000 ÷ 230 = 21.7 A, exactly half the current of a 10 kVAR capacitor at the same voltage.
Q3. What is the current drawn by a 60 kVAR three-phase capacitor bank at 400 V?
- (a) 43.3 A
- (b) 60 A
- (c) 86.6 A
- (d) 150 A
Answer: (c) 86.6 A — I = 60,000 ÷ (1.732 × 400) = 86.6 A.
Q4. A load’s power factor improves from 0.75 to 1.0 at constant kW. By what percentage does the supply current fall?
- (a) 15%
- (b) 25%
- (c) 33%
- (d) 75%
Answer: (b) 25% — the new current is 0.75 of the old one (I ∝ 1/pf), so it falls by 25%.
Q5. A load’s power factor improves from 0.7 to 0.9 at constant kW. By about what percentage does the supply current fall?
- (a) 20%
- (b) 22.2%
- (c) 30%
- (d) 10%
Answer: (b) 22.2% — the new current is 0.7 ÷ 0.9 = 0.778 of the old one, so it falls by about 22.2%.
Q6. An 80 kW load runs at 0.8 power factor. If it is corrected to 0.9, how much kVA capacity is freed up?
- (a) 20 kVA
- (b) 11.1 kVA
- (c) 25 kVA
- (d) 8.9 kVA
Answer: (b) 11.1 kVA — kVA falls from 80 ÷ 0.8 = 100 to 80 ÷ 0.9 = 88.9, freeing 100 − 88.9 = 11.1 kVA.
Q7. A 60 kW load runs at 0.75 power factor. If it is corrected to 0.95, how much kVA capacity is freed up?
- (a) 20 kVA
- (b) 16.8 kVA
- (c) 63.2 kVA
- (d) 10 kVA
Answer: (b) 16.8 kVA — kVA falls from 60 ÷ 0.75 = 80 to 60 ÷ 0.95 = 63.2, freeing 80 − 63.2 = 16.8 kVA.
Q8. A 150 kW load runs at 0.8 power factor. If it is corrected to 0.95, how much kVA capacity is freed up?
- (a) 42.1 kVA
- (b) 29.6 kVA
- (c) 30 kVA
- (d) 187.5 kVA
Answer: (b) 29.6 kVA — kVA falls from 150 ÷ 0.8 = 187.5 to 150 ÷ 0.95 = 157.9, freeing 187.5 − 157.9 = 29.6 kVA.
Q9. A 500 kVA transformer is fully loaded by a 400 kW load at 0.8 power factor. After correction to 0.95, how much spare capacity does the transformer have?
- (a) 100 kVA
- (b) 79 kVA
- (c) 421 kVA
- (d) 21 kVA
Answer: (b) 79 kVA — the load now draws 400 ÷ 0.95 = 421 kVA, so the 500 kVA transformer has 500 − 421 = 79 kVA spare.
Q10. A feeder’s copper loss is 10 kW when the load runs at 0.8 power factor. If the load is corrected to unity power factor at the same kW, what is the new copper loss?
- (a) 8 kW
- (b) 6.4 kW
- (c) 3.6 kW
- (d) 10 kW
Answer: (b) 6.4 kW — current falls to 0.8 of its old value, so loss falls to 0.8² = 0.64 of 10 kW, which is 6.4 kW.