Power Factor Correction MCQs — Set 9

10 practice questions on what can go wrong — over-correction, harmonics, resonance and capacitor safety.

Q1. What happens if too much capacitance is connected to a load?

  • (a) The power factor stays lagging
  • (b) The power factor becomes leading
  • (c) The real power increases
  • (d) The supply voltage falls to zero

Answer: (b) The power factor becomes leading — excess capacitance over-corrects the load, so the current leads the voltage.

Q2. A leading power factor at the load end of a long feeder tends to:

  • (a) Drop the voltage further
  • (b) Raise the voltage above normal
  • (c) Have no effect on voltage
  • (d) Reduce the real power to zero

Answer: (b) Raise the voltage above normal — leading current flowing through the feeder inductance produces a voltage rise (the Ferranti effect on lightly loaded lines).

Q3. Why can a fixed capacitor bank over-correct a load at night or at light load?

  • (a) Because the capacitor’s kVAR increases at night
  • (b) Because the load’s kVAR falls but the fixed capacitor keeps supplying the same kVAR
  • (c) Because the supply frequency rises at night
  • (d) Because the capacitor disconnects itself

Answer: (b) Because the load’s kVAR falls but the fixed capacitor keeps supplying the same kVAR — with little inductive load left, the fixed capacitance drives the power factor leading.

Q4. Resonance between a power factor correction capacitor and the supply inductance can:

  • (a) Reduce all harmonics to zero
  • (b) Amplify harmonic currents and overheat or damage the capacitor
  • (c) Improve the power factor to 2.0
  • (d) Stop the flow of real power

Answer: (b) Amplify harmonic currents and overheat or damage the capacitor — at the resonant frequency the capacitor and inductance exchange large harmonic currents.

Q5. What is the purpose of a detuned reactor fitted in series with a correction capacitor?

  • (a) To increase the capacitance
  • (b) To shift the resonance frequency away from harmful harmonics
  • (c) To discharge the capacitor
  • (d) To convert AC to DC

Answer: (b) To shift the resonance frequency away from harmful harmonics — the reactor detunes the LC circuit so harmonic currents are not amplified.

Q6. Which load is a common source of harmonics that can stress power factor correction capacitors?

  • (a) Resistive heater
  • (b) Variable frequency drive (VFD)
  • (c) Incandescent lamp
  • (d) Electric iron

Answer: (b) Variable frequency drive (VFD) — VFDs and other electronic loads draw non-sinusoidal current rich in harmonics, which heat capacitors.

Q7. Why is each capacitor unit in a bank usually fitted with its own fuse?

  • (a) To increase the total kVAR
  • (b) To isolate a faulty unit so the rest of the bank keeps working
  • (c) To discharge the capacitor
  • (d) To measure the power factor

Answer: (b) To isolate a faulty unit so the rest of the bank keeps working — a shorted unit is disconnected by its fuse instead of tripping the whole bank.

Q8. Before handling a disconnected power factor correction capacitor, you should:

  • (a) Touch both terminals immediately
  • (b) Wait for the discharge resistor to bring it to a safe voltage, then verify it is discharged
  • (c) Short it with a screwdriver while it is still connected
  • (d) Spray it with water

Answer: (b) Wait for the discharge resistor to bring it to a safe voltage, then verify it is discharged — capacitors store charge and can give a severe shock after disconnection.

Q9. Which of these is a visible sign that a power factor correction capacitor has failed?

  • (a) Its case is swollen, bulging or leaking
  • (b) Its terminals are clean and tight
  • (c) It runs cooler than normal
  • (d) Its kVAR rating has increased

Answer: (a) Its case is swollen, bulging or leaking — heat and internal pressure swell or rupture a failing capacitor; such a unit must be replaced.

Q10. If a capacitor bank stays connected to an induction motor that is switched off from the supply, the motor may:

  • (a) Stop instantly
  • (b) Self-excite and generate a dangerous overvoltage
  • (c) Draw more real power
  • (d) Reverse its direction of rotation

Answer: (b) Self-excite and generate a dangerous overvoltage — the spinning motor with capacitors can act as a generator, so capacitors should be switched with the motor.

Also read: Voltage Drop Calculator | All MCQ Topics