Power Factor Correction MCQs — Set 9
10 practice questions on what can go wrong — over-correction, harmonics, resonance and capacitor safety.
Q1. What happens if too much capacitance is connected to a load?
- (a) The power factor stays lagging
- (b) The power factor becomes leading
- (c) The real power increases
- (d) The supply voltage falls to zero
Answer: (b) The power factor becomes leading — excess capacitance over-corrects the load, so the current leads the voltage.
Q2. A leading power factor at the load end of a long feeder tends to:
- (a) Drop the voltage further
- (b) Raise the voltage above normal
- (c) Have no effect on voltage
- (d) Reduce the real power to zero
Answer: (b) Raise the voltage above normal — leading current flowing through the feeder inductance produces a voltage rise (the Ferranti effect on lightly loaded lines).
Q3. Why can a fixed capacitor bank over-correct a load at night or at light load?
- (a) Because the capacitor’s kVAR increases at night
- (b) Because the load’s kVAR falls but the fixed capacitor keeps supplying the same kVAR
- (c) Because the supply frequency rises at night
- (d) Because the capacitor disconnects itself
Answer: (b) Because the load’s kVAR falls but the fixed capacitor keeps supplying the same kVAR — with little inductive load left, the fixed capacitance drives the power factor leading.
Q4. Resonance between a power factor correction capacitor and the supply inductance can:
- (a) Reduce all harmonics to zero
- (b) Amplify harmonic currents and overheat or damage the capacitor
- (c) Improve the power factor to 2.0
- (d) Stop the flow of real power
Answer: (b) Amplify harmonic currents and overheat or damage the capacitor — at the resonant frequency the capacitor and inductance exchange large harmonic currents.
Q5. What is the purpose of a detuned reactor fitted in series with a correction capacitor?
- (a) To increase the capacitance
- (b) To shift the resonance frequency away from harmful harmonics
- (c) To discharge the capacitor
- (d) To convert AC to DC
Answer: (b) To shift the resonance frequency away from harmful harmonics — the reactor detunes the LC circuit so harmonic currents are not amplified.
Q6. Which load is a common source of harmonics that can stress power factor correction capacitors?
- (a) Resistive heater
- (b) Variable frequency drive (VFD)
- (c) Incandescent lamp
- (d) Electric iron
Answer: (b) Variable frequency drive (VFD) — VFDs and other electronic loads draw non-sinusoidal current rich in harmonics, which heat capacitors.
Q7. Why is each capacitor unit in a bank usually fitted with its own fuse?
- (a) To increase the total kVAR
- (b) To isolate a faulty unit so the rest of the bank keeps working
- (c) To discharge the capacitor
- (d) To measure the power factor
Answer: (b) To isolate a faulty unit so the rest of the bank keeps working — a shorted unit is disconnected by its fuse instead of tripping the whole bank.
Q8. Before handling a disconnected power factor correction capacitor, you should:
- (a) Touch both terminals immediately
- (b) Wait for the discharge resistor to bring it to a safe voltage, then verify it is discharged
- (c) Short it with a screwdriver while it is still connected
- (d) Spray it with water
Answer: (b) Wait for the discharge resistor to bring it to a safe voltage, then verify it is discharged — capacitors store charge and can give a severe shock after disconnection.
Q9. Which of these is a visible sign that a power factor correction capacitor has failed?
- (a) Its case is swollen, bulging or leaking
- (b) Its terminals are clean and tight
- (c) It runs cooler than normal
- (d) Its kVAR rating has increased
Answer: (a) Its case is swollen, bulging or leaking — heat and internal pressure swell or rupture a failing capacitor; such a unit must be replaced.
Q10. If a capacitor bank stays connected to an induction motor that is switched off from the supply, the motor may:
- (a) Stop instantly
- (b) Self-excite and generate a dangerous overvoltage
- (c) Draw more real power
- (d) Reverse its direction of rotation
Answer: (b) Self-excite and generate a dangerous overvoltage — the spinning motor with capacitors can act as a generator, so capacitors should be switched with the motor.
Also read: Voltage Drop Calculator | All MCQ Topics