Power Factor Correction MCQs — Set 7
10 practice questions on synchronous condensers and other alternatives to capacitors for power factor correction.
Q1. A load draws 100 kVA at a power factor of 0.8. How much reactive power (kVAR) does it draw?
- (a) 80 kVAR
- (b) 60 kVAR
- (c) 100 kVAR
- (d) 20 kVAR
Answer: (b) 60 kVAR — real power is 100 × 0.8 = 80 kW, so reactive power = √(100² − 80²) = √3,600 = 60 kVAR.
Q2. An over-excited synchronous motor connected to the supply:
- (a) Absorbs reactive power like an inductor
- (b) Supplies leading reactive power like a capacitor
- (c) Supplies only real power
- (d) Draws no current at all
Answer: (b) Supplies leading reactive power like a capacitor — over-excitation makes the machine deliver kVAR to the network, improving the power factor.
Q3. An under-excited synchronous motor connected to the supply:
- (a) Supplies leading reactive power
- (b) Absorbs lagging reactive power from the supply
- (c) Runs at unity power factor always
- (d) Generates real power
Answer: (b) Absorbs lagging reactive power from the supply — reducing the excitation makes the machine behave like an inductor, taking kVAR from the system.
Q4. What is the main advantage of a synchronous condenser over a capacitor bank?
- (a) It is much cheaper to buy
- (b) It gives smooth, stepless control of reactive power
- (c) It needs no maintenance
- (d) It consumes no power at all
Answer: (b) It gives smooth, stepless control of reactive power — varying the excitation changes the kVAR continuously, while capacitor banks switch in fixed steps.
Q5. What is the main disadvantage of using a synchronous condenser for power factor correction?
- (a) It can only correct small loads
- (b) It is expensive, needs maintenance and has running losses
- (c) It cannot supply reactive power
- (d) It only works on DC supplies
Answer: (b) It is expensive, needs maintenance and has running losses — a rotating machine costs far more to buy and run than static capacitors.
Q6. A phase advancer is used with which machine to improve its power factor?
- (a) DC shunt motor
- (b) Induction motor
- (c) Stepper motor
- (d) Universal motor
Answer: (b) Induction motor — a phase advancer injects a leading current into the rotor circuit of a slip-ring induction motor, improving its power factor.
Q7. A static VAR compensator (SVC) corrects power factor by:
- (a) Switching capacitors and reactors with thyristors in milliseconds
- (b) Spinning a synchronous motor
- (c) Adding resistance to the circuit
- (d) Changing the supply frequency
Answer: (a) Switching capacitors and reactors with thyristors in milliseconds — an SVC reacts far faster than contactor-switched capacitor banks, suiting rapidly changing loads.
Q8. For a small workshop with a few motors, which power factor correction method is usually the cheapest?
- (a) Synchronous condenser
- (b) Static VAR compensator
- (c) Shunt capacitor bank
- (d) Phase advancer on every motor
Answer: (c) Shunt capacitor bank — capacitors are cheap, static and almost maintenance-free, so they are the standard choice for small installations.
Q9. A synchronous motor running at normal excitation with a mechanical load operates at:
- (a) Lagging power factor
- (b) Leading power factor
- (c) Approximately unity power factor
- (d) Zero power factor
Answer: (c) Approximately unity power factor — at normal excitation a synchronous motor draws almost no reactive power, so its pf is near 1.0.
Q10. Which device can BOTH supply and absorb reactive power, depending on how it is controlled?
- (a) A fixed capacitor bank
- (b) A synchronous condenser
- (c) A resistor bank
- (d) A diode rectifier
Answer: (b) A synchronous condenser — over-excitation supplies kVAR and under-excitation absorbs kVAR, so one machine can correct in either direction.