Power Factor Correction MCQs — Set 7

10 practice questions on synchronous condensers and other alternatives to capacitors for power factor correction.

Q1. A load draws 100 kVA at a power factor of 0.8. How much reactive power (kVAR) does it draw?

  • (a) 80 kVAR
  • (b) 60 kVAR
  • (c) 100 kVAR
  • (d) 20 kVAR

Answer: (b) 60 kVAR — real power is 100 × 0.8 = 80 kW, so reactive power = √(100² − 80²) = √3,600 = 60 kVAR.

Q2. An over-excited synchronous motor connected to the supply:

  • (a) Absorbs reactive power like an inductor
  • (b) Supplies leading reactive power like a capacitor
  • (c) Supplies only real power
  • (d) Draws no current at all

Answer: (b) Supplies leading reactive power like a capacitor — over-excitation makes the machine deliver kVAR to the network, improving the power factor.

Q3. An under-excited synchronous motor connected to the supply:

  • (a) Supplies leading reactive power
  • (b) Absorbs lagging reactive power from the supply
  • (c) Runs at unity power factor always
  • (d) Generates real power

Answer: (b) Absorbs lagging reactive power from the supply — reducing the excitation makes the machine behave like an inductor, taking kVAR from the system.

Q4. What is the main advantage of a synchronous condenser over a capacitor bank?

  • (a) It is much cheaper to buy
  • (b) It gives smooth, stepless control of reactive power
  • (c) It needs no maintenance
  • (d) It consumes no power at all

Answer: (b) It gives smooth, stepless control of reactive power — varying the excitation changes the kVAR continuously, while capacitor banks switch in fixed steps.

Q5. What is the main disadvantage of using a synchronous condenser for power factor correction?

  • (a) It can only correct small loads
  • (b) It is expensive, needs maintenance and has running losses
  • (c) It cannot supply reactive power
  • (d) It only works on DC supplies

Answer: (b) It is expensive, needs maintenance and has running losses — a rotating machine costs far more to buy and run than static capacitors.

Q6. A phase advancer is used with which machine to improve its power factor?

  • (a) DC shunt motor
  • (b) Induction motor
  • (c) Stepper motor
  • (d) Universal motor

Answer: (b) Induction motor — a phase advancer injects a leading current into the rotor circuit of a slip-ring induction motor, improving its power factor.

Q7. A static VAR compensator (SVC) corrects power factor by:

  • (a) Switching capacitors and reactors with thyristors in milliseconds
  • (b) Spinning a synchronous motor
  • (c) Adding resistance to the circuit
  • (d) Changing the supply frequency

Answer: (a) Switching capacitors and reactors with thyristors in milliseconds — an SVC reacts far faster than contactor-switched capacitor banks, suiting rapidly changing loads.

Q8. For a small workshop with a few motors, which power factor correction method is usually the cheapest?

  • (a) Synchronous condenser
  • (b) Static VAR compensator
  • (c) Shunt capacitor bank
  • (d) Phase advancer on every motor

Answer: (c) Shunt capacitor bank — capacitors are cheap, static and almost maintenance-free, so they are the standard choice for small installations.

Q9. A synchronous motor running at normal excitation with a mechanical load operates at:

  • (a) Lagging power factor
  • (b) Leading power factor
  • (c) Approximately unity power factor
  • (d) Zero power factor

Answer: (c) Approximately unity power factor — at normal excitation a synchronous motor draws almost no reactive power, so its pf is near 1.0.

Q10. Which device can BOTH supply and absorb reactive power, depending on how it is controlled?

  • (a) A fixed capacitor bank
  • (b) A synchronous condenser
  • (c) A resistor bank
  • (d) A diode rectifier

Answer: (b) A synchronous condenser — over-excitation supplies kVAR and under-excitation absorbs kVAR, so one machine can correct in either direction.

Also read: Watt Calculator | All MCQ Topics