Power Factor Correction MCQs — Set 5

10 practice questions on what power factor correction actually saves — current, losses and transformer capacity.

Q1. A load’s power factor improves from 0.7 to 1.0 while its kW stays the same. By what percentage does the supply current fall?

  • (a) 70%
  • (b) 30%
  • (c) 20%
  • (d) 50%

Answer: (b) 30% — current is proportional to 1/pf, so the new current is 0.7 of the old one: a 30% reduction.

Q2. A load’s power factor improves from 0.8 to 1.0 at constant kW. By what percentage does the supply current fall?

  • (a) 25%
  • (b) 10%
  • (c) 20%
  • (d) 36%

Answer: (c) 20% — the new current is 0.8 of the old one (I ∝ 1/pf), so it falls by 20%.

Q3. A load’s power factor improves from 0.6 to 1.0 at constant kW. By what percentage does the supply current fall?

  • (a) 60%
  • (b) 40%
  • (c) 36%
  • (d) 64%

Answer: (b) 40% — the new current is 0.6 of the old one, so it falls by 40%.

Q4. A load’s power factor improves from 0.5 to 1.0 at constant kW. By what percentage does the supply current fall?

  • (a) 25%
  • (b) 75%
  • (c) 50%
  • (d) 100%

Answer: (c) 50% — the new current is 0.5 of the old one, so it falls by 50%.

Q5. A load’s power factor improves from 0.8 to 1.0. By what percentage do the copper (I²R) losses in the supply cables fall?

  • (a) 20%
  • (b) 64%
  • (c) 36%
  • (d) 80%

Answer: (c) 36% — current falls to 0.8 of its old value, so losses fall to 0.8² = 0.64 of their old value: a 36% reduction.

Q6. A load’s power factor improves from 0.7 to 1.0. By what percentage do the copper losses fall?

  • (a) 30%
  • (b) 49%
  • (c) 51%
  • (d) 70%

Answer: (c) 51% — current falls to 0.7 of its old value, so losses fall to 0.7² = 0.49 of their old value: a 51% reduction.

Q7. A load’s power factor improves from 0.6 to 1.0. By what percentage do the copper losses fall?

  • (a) 40%
  • (b) 36%
  • (c) 64%
  • (d) 60%

Answer: (c) 64% — current falls to 0.6 of its old value, so losses fall to 0.6² = 0.36 of their old value: a 64% reduction.

Q8. A 100 kW load runs at 0.8 power factor. If it is corrected to 0.95, how much kVA capacity is freed up on the supply?

  • (a) 25 kVA
  • (b) 19.7 kVA
  • (c) 20 kVA
  • (d) 42.1 kVA

Answer: (b) 19.7 kVA — kVA falls from 100 ÷ 0.8 = 125 to 100 ÷ 0.95 = 105.3, freeing 125 − 105.3 = 19.7 kVA.

Q9. A 200 kW load runs at 0.8 power factor. If it is corrected to 0.95, how much kVA capacity is freed up?

  • (a) 84.3 kVA
  • (b) 39.5 kVA
  • (c) 50 kVA
  • (d) 40 kVA

Answer: (b) 39.5 kVA — kVA falls from 200 ÷ 0.8 = 250 to 200 ÷ 0.95 = 210.5, freeing 250 − 210.5 = 39.5 kVA.

Q10. A load’s power factor improves from 0.8 to 0.95 at constant kW. By about what percentage does the supply current fall?

  • (a) 15%
  • (b) 16%
  • (c) 20%
  • (d) 5%

Answer: (b) 16% — the new current is 0.8 ÷ 0.95 = 0.842 of the old one, so it falls by about 15.8%, roughly 16%.

Also read: Home Load Calculator | All MCQ Topics