Power Factor Correction MCQs — Set 4

10 practice questions on sizing the capacitor kVAR needed to lift power factor to a target value — with the working shown.

Q1. A 50 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to correct it to unity power factor?

  • (a) 21.1 kVAR
  • (b) 50 kVAR
  • (c) 37.5 kVAR
  • (d) 62.5 kVAR

Answer: (c) 37.5 kVAR — to reach unity pf the capacitor must supply all the existing reactive power, which is 37.5 kVAR.

Q2. A 100 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 75 kVAR
  • (b) 32.9 kVAR
  • (c) 42.1 kVAR
  • (d) 60 kVAR

Answer: (c) 42.1 kVAR — existing kVAR = 100 × 0.75 = 75; at pf 0.95 the load still needs 100 × 0.329 = 32.9 kVAR, so add 75 − 32.9 = 42.1 kVAR.

Q3. An 80 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to correct it to unity?

  • (a) 80 kVAR
  • (b) 100 kVAR
  • (c) 60 kVAR
  • (d) 48 kVAR

Answer: (c) 60 kVAR — the existing reactive power is 80 ÷ 0.8 × 0.6 = 60 kVAR, and unity pf needs all of it supplied by capacitors.

Q4. A 40 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 30 kVAR
  • (b) 13.1 kVAR
  • (c) 16.9 kVAR
  • (d) 20 kVAR

Answer: (c) 16.9 kVAR — existing kVAR = 40 × 0.75 = 30; at pf 0.95 the load needs 40 × 0.329 = 13.1 kVAR, so add 30 − 13.1 = 16.9 kVAR.

Q5. A 30 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.9?

  • (a) 22.5 kVAR
  • (b) 14.5 kVAR
  • (c) 8.0 kVAR
  • (d) 30 kVAR

Answer: (c) 8.0 kVAR — existing kVAR = 30 × 0.75 = 22.5; at pf 0.9 (tan φ = 0.484) the load needs 30 × 0.484 = 14.5 kVAR, so add 22.5 − 14.5 = 8.0 kVAR.

Q6. A 120 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 90 kVAR
  • (b) 39.4 kVAR
  • (c) 50.6 kVAR
  • (d) 60 kVAR

Answer: (c) 50.6 kVAR — existing kVAR = 120 × 0.75 = 90; at pf 0.95 the load needs 120 × 0.329 = 39.4 kVAR, so add 90 − 39.4 = 50.6 kVAR.

Q7. A 60 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 45 kVAR
  • (b) 19.7 kVAR
  • (c) 25.3 kVAR
  • (d) 30 kVAR

Answer: (c) 25.3 kVAR — existing kVAR = 60 × 0.75 = 45; at pf 0.95 the load needs 60 × 0.329 = 19.7 kVAR, so add 45 − 19.7 = 25.3 kVAR.

Q8. A 50 kW load runs at 0.6 power factor. How much capacitor kVAR is needed to raise it to 0.9?

  • (a) 66.7 kVAR
  • (b) 24.2 kVAR
  • (c) 42.5 kVAR
  • (d) 50 kVAR

Answer: (c) 42.5 kVAR — existing kVAR = 50 × 1.333 = 66.7; at pf 0.9 the load needs 50 × 0.484 = 24.2 kVAR, so add 66.7 − 24.2 = 42.5 kVAR.

Q9. A 90 kW load runs at 0.6 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 120 kVAR
  • (b) 29.6 kVAR
  • (c) 90.4 kVAR
  • (d) 60 kVAR

Answer: (c) 90.4 kVAR — existing kVAR = 90 × 1.333 = 120; at pf 0.95 the load needs 90 × 0.329 = 29.6 kVAR, so add 120 − 29.6 = 90.4 kVAR.

Q10. A 200 kW load runs at 0.8 power factor. How much capacitor kVAR is needed to raise it to 0.95?

  • (a) 150 kVAR
  • (b) 65.7 kVAR
  • (c) 84.3 kVAR
  • (d) 100 kVAR

Answer: (c) 84.3 kVAR — existing kVAR = 200 × 0.75 = 150; at pf 0.95 the load needs 200 × 0.329 = 65.7 kVAR, so add 150 − 65.7 = 84.3 kVAR.