NEC Code MCQs — Set 9

10 practice questions on ampacity and derating — the NEC 80% continuous-load rule, with worked wattage limits.

Q1. What is the NEC rule for a continuous load on a circuit breaker?

  • (a) A continuous load may use 100% of the breaker rating
  • (b) A continuous load must not exceed 80% of the breaker rating
  • (c) A continuous load must not exceed 50% of the breaker rating
  • (d) There is no rule for continuous loads

Answer: (b) A continuous load must not exceed 80% of the breaker rating — NEC 210.19(A)(1) requires conductors and breakers for continuous loads to be sized at 125% of the load, which is the same as loading the breaker to only 80%.

Q2. What is the maximum continuous load on a 20 A, 120 V circuit?

  • (a) 1,440 W
  • (b) 1,920 W
  • (c) 2,400 W
  • (d) 3,000 W

Answer: (b) 1,920 W — 20 A × 120 V = 2,400 W at full rating, and 80% of that is 2,400 × 0.8 = 1,920 W for a continuous load.

Q3. What is the maximum continuous load on a 15 A, 120 V circuit?

  • (a) 1,200 W
  • (b) 1,440 W
  • (c) 1,800 W
  • (d) 2,400 W

Answer: (b) 1,440 W — 15 A × 120 V = 1,800 W, and 80% of that is 1,800 × 0.8 = 1,440 W.

Q4. What is the maximum continuous load on a 30 A, 240 V circuit?

  • (a) 5,760 W
  • (b) 7,200 W
  • (c) 9,600 W
  • (d) 12,000 W

Answer: (a) 5,760 W — 30 A × 240 V = 7,200 W, and 80% of that is 7,200 × 0.8 = 5,760 W.

Q5. What is the maximum continuous load on a 50 A, 240 V circuit?

  • (a) 7,200 W
  • (b) 9,600 W
  • (c) 12,000 W
  • (d) 15,000 W

Answer: (b) 9,600 W — 50 A × 240 V = 12,000 W, and 80% of that is 12,000 × 0.8 = 9,600 W.

Q6. A continuous load draws 40 A at 240 V. What is the minimum breaker size for it?

  • (a) 40 A
  • (b) 45 A
  • (c) 50 A
  • (d) 60 A

Answer: (c) 50 A — a continuous load needs a breaker rated at 125% of the load, so 40 A × 1.25 = 50 A.

Q7. How long must a load run to be classed as a “continuous load” under the NEC?

  • (a) 30 minutes or more
  • (b) 1 hour or more
  • (c) 3 hours or more
  • (d) 8 hours or more

Answer: (c) 3 hours or more — the NEC defines a continuous load as one where the maximum current is expected to continue for 3 hours or more.

Q8. A raceway carries 4 to 6 current-carrying conductors. What ampacity adjustment factor applies?

  • (a) 100%
  • (b) 90%
  • (c) 80%
  • (d) 70%

Answer: (c) 80% — NEC Table 310.15(C)(1) requires an 80% adjustment factor when 4 to 6 current-carrying conductors are bundled in one raceway, because they heat each other.

Q9. What happens to a conductor’s ampacity as the ambient temperature rises?

  • (a) It increases
  • (b) It stays the same
  • (c) It decreases — a correction factor below 1.0 must be applied
  • (d) It doubles

Answer: (c) It decreases — a correction factor below 1.0 must be applied — hotter surroundings leave less room for the conductor’s own heating, so its safe current drops.

Q10. A 5 kW load runs at 230 V with a power factor of 0.9. What current does it draw?

  • (a) 19.4 A
  • (b) 21.7 A
  • (c) 24.2 A
  • (d) 26.9 A

Answer: (c) 24.2 A — I = P ÷ (V × pf) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.