NEC Code MCQs — Set 6

10 practice questions on NEC Article 430 motors — full-load current, conductor sizing, overload and short-circuit protection.

Q1. Motor branch-circuit conductors must be sized for at least what percentage of the motor full-load current (FLC)?

  • (a) 100%
  • (b) 115%
  • (c) 125%
  • (d) 150%

Answer: (c) 125% — NEC 430.22 requires motor branch-circuit conductors to have an ampacity of at least 125% of the motor full-load current.

Q2. A 10 HP, 230 V, three-phase motor has a full-load current of 28 A. What is the minimum conductor ampacity for its branch circuit?

  • (a) 28 A
  • (b) 30 A
  • (c) 35 A
  • (d) 42 A

Answer: (c) 35 A — 28 A × 1.25 = 35 A, so the conductors must carry at least 35 A.

Q3. A motor with a service factor of 1.15 and a full-load current of 10 A needs overload protection set at no more than what current?

  • (a) 10 A
  • (b) 11.5 A
  • (c) 12.5 A
  • (d) 15 A

Answer: (c) 12.5 A — NEC 430.32(A)(1) allows overload protection up to 125% of FLC for a motor with a service factor of 1.15, so 10 A × 1.25 = 12.5 A.

Q4. An inverse-time circuit breaker protecting a motor branch circuit may be rated at most what percentage of the motor full-load current?

  • (a) 125%
  • (b) 175%
  • (c) 250%
  • (d) 300%

Answer: (c) 250% — NEC Table 430.52 allows an inverse-time breaker up to 250% of FLC, so a 20 A FLC motor may use up to a 50 A breaker.

Q5. A motor has a full-load current of 20 A. What is the largest inverse-time breaker allowed for its branch circuit short-circuit protection?

  • (a) 25 A
  • (b) 35 A
  • (c) 50 A
  • (d) 60 A

Answer: (c) 50 A — 20 A × 250% = 50 A per NEC Table 430.52.

Q6. How far away may a motor disconnecting means be and still be considered “within sight” of the motor?

  • (a) 10 ft
  • (b) 25 ft
  • (c) 50 ft
  • (d) 100 ft

Answer: (c) 50 ft — NEC 430.102 requires the disconnect to be within sight, defined as visible and not more than 50 ft away.

Q7. For sizing motor branch-circuit conductors and short-circuit protection, which full-load current value must be used?

  • (a) The motor nameplate value
  • (b) The NEC tables (430.247–430.250)
  • (c) The measured running current
  • (d) The locked-rotor current

Answer: (b) The NEC tables (430.247–430.250) — NEC 430.6(A) requires the table values for conductor and protection sizing, while the nameplate value is used for overload protection.

Q8. What is the job of motor overload protection?

  • (a) To clear short circuits
  • (b) To protect the motor from sustained overcurrent that would overheat its windings
  • (c) To start the motor
  • (d) To increase motor speed

Answer: (b) To protect the motor from sustained overcurrent that would overheat its windings — overload devices trip on prolonged overloads, while branch-circuit protection clears short circuits and ground faults.

Q9. A 5 HP, 230 V, three-phase motor has a full-load current of 15.2 A. What is the minimum conductor ampacity for its branch circuit?

  • (a) 15.2 A
  • (b) 17.5 A
  • (c) 19 A
  • (d) 25 A

Answer: (c) 19 A — 15.2 A × 1.25 = 19 A, so the conductors must carry at least 19 A.

Q10. Which NEC article covers motors, motor branch circuits and motor controllers?

  • (a) Article 210
  • (b) Article 250
  • (c) Article 300
  • (d) Article 430

Answer: (d) Article 430 — Article 430 covers motors, motor branch-circuit and feeder conductors, overload and short-circuit protection, and controllers.