NEC Code MCQs — Set 4

10 practice questions on NEC Article 250 grounding and bonding — electrodes, grounding conductors and bonding jumpers.

Q1. What is the main purpose of grounding an electrical system?

  • (a) To save electricity
  • (b) To provide a low-impedance path so fault current trips the overcurrent device quickly
  • (c) To increase the voltage
  • (d) To reduce the size of conductors

Answer: (b) To provide a low-impedance path so fault current trips the overcurrent device quickly — grounding clears faults fast and keeps exposed metal parts near earth potential.

Q2. How long must a ground rod electrode be?

  • (a) 4 ft
  • (b) 6 ft
  • (c) 8 ft
  • (d) 10 ft

Answer: (c) 8 ft — NEC 250.52(A)(5) requires a rod electrode to be at least 8 ft long and driven so at least 8 ft is in contact with the soil.

Q3. A single ground rod measures more than 25 ohms to earth. What does the NEC require?

  • (a) Nothing — one rod is always enough
  • (b) A second electrode must be added
  • (c) The rod must be replaced with a longer one only
  • (d) The service must be upsized

Answer: (b) A second electrode must be added — NEC 250.53(A)(2) requires a second electrode if a single rod exceeds 25 ohms to earth.

Q4. What does the main bonding jumper connect at the service?

  • (a) The neutral (grounded) conductor to the equipment grounding conductor and the service enclosure
  • (b) Two hot conductors together
  • (c) The meter to the transformer
  • (d) The ground rod to the water pipe only

Answer: (a) The neutral (grounded) conductor to the equipment grounding conductor and the service enclosure — the main bonding jumper is the one place where neutral and ground are joined.

Q5. What size copper equipment grounding conductor is required for a 20 A branch circuit?

  • (a) 14 AWG
  • (b) 12 AWG
  • (c) 10 AWG
  • (d) 8 AWG

Answer: (b) 12 AWG — NEC Table 250.122 requires a 12 AWG copper equipment grounding conductor for a 20 A overcurrent device.

Q6. What size copper equipment grounding conductor is required for a 100 A feeder?

  • (a) 12 AWG
  • (b) 10 AWG
  • (c) 8 AWG
  • (d) 6 AWG

Answer: (c) 8 AWG — NEC Table 250.122 requires an 8 AWG copper equipment grounding conductor for a 100 A overcurrent device.

Q7. What size copper equipment grounding conductor is required for a 60 A circuit?

  • (a) 12 AWG
  • (b) 10 AWG
  • (c) 8 AWG
  • (d) 6 AWG

Answer: (b) 10 AWG — NEC Table 250.122 requires a 10 AWG copper equipment grounding conductor for a 60 A overcurrent device.

Q8. What is the grounding electrode conductor?

  • (a) The conductor that connects the system grounded conductor to the grounding electrode
  • (b) The conductor inside a flexible cord
  • (c) The wire that feeds a receptacle
  • (d) The conductor between two panels

Answer: (a) The conductor that connects the system grounded conductor to the grounding electrode — it ties the electrical system to earth through the electrode.

Q9. What is the difference between grounding and bonding?

  • (a) They are the same thing
  • (b) Grounding connects a system to earth; bonding joins metal parts together so they stay at the same potential
  • (c) Grounding is for DC only; bonding is for AC only
  • (d) Bonding is done only outdoors

Answer: (b) Grounding connects a system to earth; bonding joins metal parts together so they stay at the same potential — bonding makes sure fault current has a path back, grounding ties that path to earth.

Q10. A metal water pipe used as a grounding electrode must have its bonding connection made within what distance of where it enters the building?

  • (a) 1 ft
  • (b) 5 ft
  • (c) 10 ft
  • (d) 25 ft

Answer: (b) 5 ft — NEC 250.52(A)(1) requires the connection to a metal water pipe electrode to be within 5 ft of its point of entry into the building.