NEC Code MCQs — Set 3
10 practice questions on NEC Article 220 load calculations — lighting loads, demand factors, dryers, ranges and service size.
Q1. What is the general lighting load allowance for a dwelling unit under NEC Article 220?
- (a) 1 VA per sq ft
- (b) 3 VA per sq ft
- (c) 5 VA per sq ft
- (d) 10 VA per sq ft
Answer: (b) 3 VA per sq ft — NEC Table 220.12 gives 3 VA per sq ft of floor area for dwelling-unit general lighting and receptacle loads.
Q2. A dwelling has 1,500 sq ft of floor area. What is its general lighting load?
- (a) 3,000 VA
- (b) 4,500 VA
- (c) 5,000 VA
- (d) 6,000 VA
Answer: (b) 4,500 VA — 1,500 sq ft × 3 VA per sq ft = 4,500 VA.
Q3. For a dwelling, the first 3,000 VA of general load is taken at 100% and the remainder at 35%. What is the demand load for a 4,500 VA general load?
- (a) 3,000 VA
- (b) 3,525 VA
- (c) 4,000 VA
- (d) 4,500 VA
Answer: (b) 3,525 VA — 3,000 VA at 100% = 3,000 VA, plus 1,500 VA at 35% = 525 VA, for a total of 3,525 VA.
Q4. A dwelling has 2,000 sq ft of floor area. What is its demand load for general lighting and receptacles?
- (a) 3,525 VA
- (b) 4,050 VA
- (c) 6,000 VA
- (d) 6,500 VA
Answer: (b) 4,050 VA — gross load is 2,000 × 3 = 6,000 VA; demand is 3,000 VA at 100% plus 3,000 VA at 35% (1,050 VA), totalling 4,050 VA.
Q5. What is the minimum load allowance for an electric clothes dryer in a dwelling load calculation?
- (a) 3,000 VA
- (b) 4,000 VA
- (c) 5,000 VA
- (d) 8,000 VA
Answer: (c) 5,000 VA — NEC 220.54 requires a minimum of 5,000 VA for an electric dryer, or the nameplate rating if higher.
Q6. A dryer is calculated at 5,000 VA on a 240 V circuit. What current does it draw?
- (a) 12.5 A
- (b) 20.8 A
- (c) 25 A
- (d) 41.7 A
Answer: (b) 20.8 A — I = 5,000 ÷ 240 = 20.8 A, which is why a dryer is normally on a 30 A circuit.
Q7. What is the minimum load allowance for a household electric range in a load calculation?
- (a) 5,000 VA
- (b) 6,000 VA
- (c) 8,000 VA
- (d) 12,000 VA
Answer: (c) 8,000 VA — NEC 220.55 uses 8 kW as the minimum for a household electric range, or the nameplate rating if larger.
Q8. How much load is allowed for each small-appliance branch circuit in a dwelling load calculation?
- (a) 1,000 VA
- (b) 1,500 VA
- (c) 2,000 VA
- (d) 3,000 VA
Answer: (b) 1,500 VA — NEC 220.52(A) allows 1,500 VA per small-appliance circuit, so two circuits add 3,000 VA to the load calculation.
Q9. What is the minimum service size for a dwelling unit under the NEC?
- (a) 60 A
- (b) 100 A
- (c) 150 A
- (d) 200 A
Answer: (b) 100 A — NEC 230.79(C) requires a minimum 100 A service for a one-family dwelling.
Q10. How much load is allowed for the laundry branch circuit in a dwelling load calculation?
- (a) 1,000 VA
- (b) 1,500 VA
- (c) 3,000 VA
- (d) 5,000 VA
Answer: (b) 1,500 VA — NEC 220.52(B) allows 1,500 VA for the laundry circuit, the same as one small-appliance circuit.
Also read: Voltage Drop Calculator | All MCQ Topics