NEC Code MCQs — Set 2
10 practice questions on NEC Article 210 branch circuits — receptacle spacing, kitchen, bathroom and laundry circuits.
Q1. Under NEC 210.52, what is the maximum distance from any point along a dwelling wall to a receptacle?
- (a) 3 ft
- (b) 6 ft
- (c) 10 ft
- (d) 12 ft
Answer: (b) 6 ft — no point along the floor line of a wall may be more than 6 ft from a receptacle outlet.
Q2. What is the maximum spacing between receptacles along a dwelling wall?
- (a) 6 ft
- (b) 8 ft
- (c) 12 ft
- (d) 18 ft
Answer: (c) 12 ft — with the 6 ft rule on each side, receptacles are at most 12 ft apart along a wall.
Q3. How many 20 A small-appliance branch circuits must a dwelling kitchen have at minimum?
- (a) One
- (b) Two
- (c) Three
- (d) Four
Answer: (b) Two — NEC 210.11(C)(1) requires at least two 20 A small-appliance branch circuits serving the kitchen, dining and pantry receptacles.
Q4. What is the minimum rating of the branch circuit serving a bathroom receptacle?
- (a) 15 A
- (b) 20 A
- (c) 30 A
- (d) 40 A
Answer: (b) 20 A — NEC 210.11(C)(3) requires at least one 20 A branch circuit for bathroom receptacles.
Q5. How many dedicated 20 A laundry branch circuits does a dwelling require?
- (a) None
- (b) One
- (c) Two
- (d) One per bedroom
Answer: (b) One — NEC 210.11(C)(2) requires at least one 20 A laundry branch circuit serving the laundry receptacles.
Q6. Along a kitchen countertop, what is the maximum distance from any point to a receptacle?
- (a) 12 in (1 ft)
- (b) 24 in (2 ft)
- (c) 48 in (4 ft)
- (d) 72 in (6 ft)
Answer: (b) 24 in (2 ft) — NEC 210.52(C)(1) requires that no point along the countertop wall be more than 24 in from a receptacle, so receptacles are at most 4 ft apart.
Q7. A hallway in a dwelling is 12 ft long. How many receptacles does the NEC require in it?
- (a) None
- (b) One
- (c) Two
- (d) Three
Answer: (b) One — NEC 210.52(H) requires at least one receptacle in a hallway 10 ft or longer.
Q8. Which of these appliances normally requires its own dedicated branch circuit?
- (a) A table lamp
- (b) A phone charger
- (c) An electric range
- (d) A ceiling fan
Answer: (c) An electric range — large fixed appliances such as electric ranges, water heaters and dryers are served by their own dedicated branch circuits, while lamps, chargers and fans share general-purpose circuits.
Q9. A floor receptacle counts toward the required wall receptacles if it is within what distance of the wall?
- (a) 6 in
- (b) 12 in
- (c) 18 in
- (d) 24 in
Answer: (c) 18 in — NEC 210.52(A)(3) allows a floor receptacle within 18 in of the wall to count as a required wall receptacle.
Q10. In a multiwire branch circuit, two ungrounded conductors share one neutral. What must be true of the two ungrounded conductors?
- (a) They must be the same phase
- (b) They must be on opposite phases (or legs) so the neutral carries only the unbalanced current
- (c) They must both be 15 A
- (d) They must not have a breaker
Answer: (b) They must be on opposite phases (or legs) so the neutral carries only the unbalanced current — on the same phase the neutral would carry the sum of both currents and could overload.