Motor Starter MCQs — Set 9
10 practice questions on overload protection inside motor starters — thermal relays, trip class, single phasing, and the difference from short-circuit protection — with answers and explanations.
Q1. What does the thermal overload relay in a starter protect the motor against?
- (a) Short circuit
- (b) Sustained overload — overcurrent lasting long enough to overheat the windings
- (c) Lightning strikes
- (d) Loss of supply frequency
Answer: (b) Sustained overload — overcurrent lasting long enough to overheat the windings — a short circuit is far too fast for a thermal relay and is cleared by a fuse or MCB instead.
Q2. A motor’s full-load current is 14 A. The overload relay should be set to:
- (a) 7 A
- (b) 14 A
- (c) 28 A
- (d) 84 A
Answer: (b) 14 A — the overload relay is set to the motor’s full-load current, so it trips only when the motor is genuinely overloaded.
Q3. Which device protects the circuit against short circuit, while the thermal relay handles overload?
- (a) The contactor
- (b) A fuse or MCB
- (c) The start push button
- (d) The timer
Answer: (b) A fuse or MCB — the fuse or breaker clears the huge short-circuit current instantly, while the thermal relay deals with smaller, longer-lasting overloads.
Q4. What is single phasing?
- (a) Running a three-phase motor on a single-phase supply by design
- (b) The loss of one supply phase, so the motor keeps running on two phases, draws excess current and overheats
- (c) Starting a motor in star and running it in delta
- (d) A motor with only one winding
Answer: (b) The loss of one supply phase, so the motor keeps running on two phases, draws excess current and overheats — a blown fuse in one phase is a common cause, and a differential overload relay is used to detect it.
Q5. A class 10 overload relay trips within 10 seconds at what multiple of its current setting?
- (a) 1.5 × its setting
- (b) 3 × its setting
- (c) 7.2 × its setting
- (d) 12 × its setting
Answer: (c) 7.2 × its setting — the trip class number is the maximum tripping time in seconds at 7.2 times the set current, so class 10 means within 10 seconds.
Q6. Why does a thermal overload relay have a reset button?
- (a) To increase the motor speed after a trip
- (b) After tripping it must cool down and be reset manually before the motor can restart
- (c) To test the supply voltage
- (d) To bypass the contactor
Answer: (b) After tripping it must cool down and be reset manually before the motor can restart — manual reset stops the motor from restarting itself while the fault is still there.
Q7. How does a bimetallic thermal relay sense an overload?
- (a) A coil measures the supply frequency
- (b) Motor current heats a bimetallic strip, which bends and trips the contactor coil circuit
- (c) A magnet pulls the contacts open
- (d) A capacitor charges up and discharges into the coil
Answer: (b) Motor current heats a bimetallic strip, which bends and trips the contactor coil circuit — the two metals expand at different rates, so the strip curls as it warms.
Q8. A 30 mA RCCB in a motor circuit protects mainly against:
- (a) Motor overload
- (b) Short circuit between phases
- (c) Earth leakage and electric shock
- (d) Single phasing
Answer: (c) Earth leakage and electric shock — the RCCB trips when current leaks to earth, even a small 30 mA leak that would not blow a fuse.
Q9. Where is the overload relay connected in a DOL starter?
- (a) Across the supply lines
- (b) In series with the motor in the main power circuit, with its trip contact in the contactor coil circuit
- (c) In parallel with the start button only
- (d) Inside the motor terminal box, across the windings
Answer: (b) In series with the motor in the main power circuit, with its trip contact in the contactor coil circuit — the heater elements carry the motor current, and the trip contact drops the contactor out.
Q10. Why can’t the fuse alone protect a motor from overload?
- (a) A fuse is too slow to clear a short circuit
- (b) The fuse rating must pass the heavy starting current, so a small sustained overload would never blow it — the motor would burn out first
- (c) A fuse only works on single-phase supplies
- (d) A fuse cannot carry the motor’s running current
Answer: (b) The fuse rating must pass the heavy starting current, so a small sustained overload would never blow it — the motor would burn out first — which is why the thermal overload relay is fitted as well.