Electrical Maintenance MCQs — Set 6

10 practice questions on insulation resistance testing — megger testing, test voltages and reading the results — with answers and explanations.

Q1. How is the polarisation index (PI) of insulation calculated?

  • (a) Insulation resistance after 10 minutes ÷ insulation resistance after 1 minute
  • (b) Insulation resistance after 1 minute ÷ insulation resistance after 10 minutes
  • (c) Test voltage ÷ test current
  • (d) Insulation resistance at 500 V ÷ insulation resistance at 1,000 V

Answer: (a) Insulation resistance after 10 minutes ÷ insulation resistance after 1 minute — PI = R10 ÷ R1, where R10 is the reading after 10 minutes and R1 is the reading after 1 minute.

Q2. What is the generally accepted minimum insulation resistance for a low-voltage installation?

  • (a) Less than 1 Ω
  • (b) More than 1 MΩ
  • (c) Exactly 230 Ω
  • (d) Less than 0.5 Ω

Answer: (b) More than 1 MΩ — insulation resistance should be greater than 1 MΩ when tested at 500 V DC; a lower value means the insulation is damaged or damp.

Q3. What DC test voltage is normally used for insulation resistance testing of a low-voltage installation?

  • (a) 12 V DC
  • (b) 230 V DC
  • (c) 500 V DC
  • (d) 11,000 V DC

Answer: (c) 500 V DC — 500 V DC is the standard test voltage for low-voltage installations, high enough to stress the insulation but suited to 230/400 V equipment.

Q4. Why must sensitive electronic equipment be disconnected before an insulation resistance test?

  • (a) Because electronics make the reading too high
  • (b) Because the 500 V DC test voltage can damage electronic components
  • (c) Because electronics stop the megger from switching on
  • (d) Because the test takes too long with electronics connected

Answer: (b) Because the 500 V DC test voltage can damage electronic components — devices such as dimmers, electronic ballasts and control boards are not built to withstand the test voltage.

Q5. An insulation resistance reading on a motor has fallen from 50 MΩ to 0.4 MΩ. What does this mean?

  • (a) The insulation has improved
  • (b) The insulation has deteriorated or become damp and needs investigation
  • (c) The motor is now more efficient
  • (d) The reading is normal and can be ignored

Answer: (b) The insulation has deteriorated or become damp and needs investigation — 0.4 MΩ is below the 1 MΩ minimum, so the motor should be dried out or repaired before use.

Q6. When should an insulation resistance test be carried out on a new installation?

  • (a) Only after the first fault occurs
  • (b) Before the installation is energised for the first time
  • (c) Never, new installations do not need testing
  • (d) Only when the installation is ten years old

Answer: (b) Before the installation is energised for the first time — the test proves the insulation is sound before voltage is applied, so hidden damage is found safely.

Q7. Which two factors most affect an insulation resistance reading?

  • (a) The colour of the cable and the length of the test leads
  • (b) Temperature and moisture
  • (c) The brand of the megger and the time of day
  • (d) The number of sockets in the building

Answer: (b) Temperature and moisture — warm, damp insulation reads much lower than cold, dry insulation, so readings must be compared under similar conditions.

Q8. What is the polarisation index (PI) of insulation?

  • (a) The ratio of the insulation resistance at 10 minutes to the value at 1 minute
  • (b) The voltage rating printed on the cable
  • (c) The number of cores in the cable
  • (d) The thickness of the insulation in millimetres

Answer: (a) The ratio of the insulation resistance at 10 minutes to the value at 1 minute — in healthy insulation the resistance keeps rising as the test continues, so a rising value (a PI above 1) is a good sign.

Q9. Between which points is insulation resistance measured in a typical test?

  • (a) Between the live conductors and earth, and between the live conductors themselves
  • (b) Between two earth rods only
  • (c) Between the neutral and the sky
  • (d) Across the terminals of a switched-off lamp only

Answer: (a) Between the live conductors and earth, and between the live conductors themselves — the test checks that the insulation keeps live parts separated from each other and from earth.

Q10. Why are insulation resistance readings recorded over the years instead of just once?

  • (a) To fill up the logbook
  • (b) So the trend can be followed and gradual deterioration spotted before failure
  • (c) Because a single reading is always wrong
  • (d) To prove the megger still works

Answer: (b) So the trend can be followed and gradual deterioration spotted before failure — a slow fall over several years warns that the insulation is ageing, even while each single reading still passes.