Lightning Protection MCQs — Set 10
10 practice questions on lightning protection classes, standards and applications, with answers and explanations. Work each one out before checking the answer.
Q1. Which international standard covers the design, installation and maintenance of lightning protection systems?
- (a) IEC 60364
- (b) IEC 62305
- (c) IEC 60076
- (d) IEC 60204
Answer: (b) IEC 62305 — IEC 62305 is the international standard for protection against lightning, covering risk assessment, external and internal protection, and inspection.
Q2. How many classes of lightning protection system (LPS) are there?
- (a) Two
- (b) Three
- (c) Four
- (d) Six
Answer: (c) Four — LPS Classes I, II, III and IV, with Class I the strictest and Class IV the least strict.
Q3. Which lightning protection class should be used for structures storing explosives or flammable materials?
- (a) Class I, the highest level of protection
- (b) Class II
- (c) Class III
- (d) Class IV, the lowest level of protection
Answer: (a) Class I, the highest level of protection — hazardous structures need the strictest protection, with the smallest rolling sphere radius (20 m) and the closest down-conductor spacing.
Q4. What does a lightning risk assessment determine?
- (a) The colour of the down conductors
- (b) Whether a lightning protection system is needed and which class it should be
- (c) The price of the surge protector
- (d) The height of the building
Answer: (b) Whether a lightning protection system is needed and which class it should be — the assessment weighs the strike frequency, the type of structure and the consequences of a strike.
Q5. Which type of structure most needs a lightning protection system?
- (a) A low building in a valley
- (b) A tall, isolated building or one with many occupants
- (c) A building made entirely of plastic
- (d) An underground car park
Answer: (b) A tall, isolated building or one with many occupants — height, isolation and occupancy all raise the risk, so such buildings are the first candidates for lightning protection.
Q6. For which kind of structure is LPS Class IV normally suitable?
- (a) A hospital
- (b) An explosives store
- (c) An ordinary structure with a lower assessed lightning risk
- (d) A chemical plant
Answer: (c) An ordinary structure with a lower assessed lightning risk — Class IV gives the basic level of protection (60 m rolling sphere radius) where the risk assessment shows a lower level is enough.
Q7. What is a natural component of a lightning protection system?
- (a) A plastic roof tile
- (b) An existing metal part of the building, such as a metal roof or steel frame, used as part of the system
- (c) A wooden beam
- (d) A glass window
Answer: (b) An existing metal part of the building, such as a metal roof or steel frame, used as part of the system — natural components can serve as air terminals, down conductors or earth electrodes if they meet the standard’s requirements.
Q8. What is the Faraday cage idea behind a mesh lightning protection system?
- (a) A single rod attracts all lightning
- (b) A network of interconnected conductors encloses the structure so a strike is intercepted and carried around the outside
- (c) A metal box that stores lightning energy
- (d) A cage that keeps birds off the roof
Answer: (b) A network of interconnected conductors encloses the structure so a strike is intercepted and carried around the outside — like a Faraday cage, the mesh keeps the lightning current on the outside of the building.
Q9. Why do thatched roofs need special attention in lightning protection?
- (a) Thatch attracts more lightning than other roofs
- (b) Thatch is highly flammable, so a strike or a side flash can easily start a fire
- (c) Thatch cannot be bonded
- (d) Thatch roofs are always the tallest buildings
Answer: (b) Thatch is highly flammable, so a strike or a side flash can easily start a fire — thatched buildings need careful air termination, separation and bonding to keep any spark away from the thatch.
Q10. A building has a perimeter of 120 m and needs Class III lightning protection, with down conductors spaced about 15 m apart. How many down conductors are needed?
- (a) 4
- (b) 6
- (c) 8
- (d) 12
Answer: (c) 8 — 120 m ÷ 15 m = 8 down conductors, spaced evenly around the perimeter.
Also read: Electrical Safety MCQs | All MCQ Topics